Service Facts
SEQUENCE OF OPERATION
THERMOSTAT CALL FOR HEAT
R and W thermostat contacts close signaling the control
module to run its self-check routine. After the control module
has verified that the pressure switch contacts are open and
the limit switch(es) contacts are closed, the draft blower will
be energized.
As the induced draft blower comes up to speed, the pressure
switch contacts will close and the ignitor warm up period will
begin. The ignitor will heat for approx. 17 seconds, then the
gas valve is energized to permit gas flow to the burners. The
flame sensor confirms that ignition has been achieved within
the 4 second ignition trial period.
SAFETY SECTION
▲
WARNING
!
The cabinet must have an uninterrupted or unbroken ground
according to National Electrical Code, ANSI/NFPA 70 -
“latest edition” and Canadian Electrical Code, CSA C22.1 or
local codes to minimize personal injury if an electrical fault
should occur. A failure to follow this warning could result
in an electrical shock, fire, injury, or death.
▲
CAUTION
!
The integrated furnace control is polarity sensitive. The hot
leg of the 115 VAC power must be connected to the BLACK
field lead.
▲
WARNING
!
FIRE OR EXPLOSION HAZARD
Failure to follow the safety warnings exactly could result in
serious injury, death or property damage.
Never test for gas leaks with an open flame. Use a com-
mercially available soap solution made specifically for the
detection of leaks to check all connections. A fire or
explosion may result causing property damage, personal
injury, or loss of life.
▲
WARNING
!
FIRE OR EXPLOSION HAZARD
Failure to follow the safety warnings exactly could result in
serious injury, death or property damage.
Improper servicing could result in dangerous operation,
serious injury, death, or property damage.
After the flame sensor confirms that ignition has been
achieved, the delay to fan ON period begins timing and after
approx. 45 seconds the indoor blower motor will be energized
and will continue to run during the heating cycle.
When the thermostat is satisfied,
R and W thermostat
contacts open, the gas valve will close, the flames will
extinguish, and the induced draft blower will be de-energized.
The indoor blower motor will continue to run for the fan off
period (Field selectable at 60, 100, 140 or 180 seconds), then
will be de-energized by the control module.
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each
appliance connected to the venting system being
placed into operation could result in carbon monoxide
poisoning or death.
The following steps shall be followed for each appliance
connected to the venting system being placed into
operation, while all other appliances connected to the
venting system are not in operation:
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and
horizontal pitch, as required in the National Fuel Gas
Code, ANSI Z223.1/NFPA 54 or the CAN/CGA B149
Installation Codes and these instructions. Determine
that there is no blockage or restriction, leakage,
corrosion and other deficiencies which could cause an
unsafe condition.
3. As far as practical, close all building doors and
windows and all doors between the space in which the
appliance(s) connected to the venting system are
located and other deficiencies which could cause an
unsafe condition.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not
connected to the venting system. Turn on any exhaust
fans, such as range hoods and bathroom exhausts, so
they are operating at maximum speed. Do not operate
a summer exhaust fan.
6. Follow the lighting instructions. Place the appliance
being inspected into operation. Adjust the thermostat
so appliance is operating continuously.
7. If improper venting is observed during any of the above
tests, the venting system must be corrected in
accordance with the National Fuel Gas Code,
ANSI Z221.1/NFPA 54 and/or CAN/CGA B149
Installation Codes.
8. After it has been determined that each appliance
connected to the venting system properly vents where
tested as outlined above, return doors, windows,
exhaust fans, fireplace dampers and any other gas-fired
burning appliance to their previous conditions of use.
▲
WARNING
!
Содержание TDE060A936M
Страница 6: ...6 Page B 635 422 Service Facts WIRING DIAGRAM continued on next page From Dwg D341828 Rev 1 ...
Страница 7: ...Page B 635 422 7 Service Facts SCHEMATIC DIAGRAM From Dwg D341828 Rev 1 ...
Страница 8: ...8 Page B 635 422 Service Facts continued on next page WIRING DIAGRAM From Dwg D341830 Rev 1 ...
Страница 9: ...Page B 635 422 9 Service Facts SCHEMATIC DIAGRAM From Dwg D341830 Rev 1 ...