Service Facts

SEQUENCE OF OPERATION

THERMOSTAT CALL FOR HEAT

R and W thermostat contacts close signaling the control
module to run its self-check routine.  After the control module
has verified that the pressure switch contacts are open and
the limit switch(es) contacts are closed, the draft blower will
be energized.

As the induced draft blower comes up to speed, the pressure
switch contacts will close and the ignitor warm up period will
begin.  The ignitor will heat for approx. 17 seconds, then the
gas valve is energized to permit gas flow to the burners.  The
flame sensor confirms that ignition has been achieved within
the 4 second ignition trial period.

SAFETY SECTION

WARNING

!

The cabinet must have an uninterrupted or unbroken ground
according to National Electrical Code, ANSI/NFPA 70 -
“latest edition” and Canadian Electrical Code, CSA C22.1 or
local codes to minimize personal injury if an electrical fault
should occur.  A failure to follow this warning could result
in an electrical shock, fire, injury, or death.

CAUTION

!

The integrated furnace control is polarity sensitive. The hot
leg of the 115 VAC power must be connected to the BLACK
field lead.

WARNING

!

FIRE OR EXPLOSION HAZARD

Failure to follow the safety warnings exactly could result in
serious injury, death or property damage.

Never test for gas leaks with an open flame.  Use a com-
mercially available soap solution made specifically for the
detection of leaks to check all connections.  A fire or
explosion may result causing property damage, personal
injury, or loss of life.

WARNING

!

FIRE OR EXPLOSION HAZARD

Failure to follow the safety warnings exactly could result in
serious injury, death or property damage.

Improper servicing could result in dangerous operation,
serious injury, death, or property damage.

After the flame sensor confirms that ignition has been
achieved, the delay to fan ON period begins timing and after
approx. 45 seconds the indoor blower motor will be energized
and will continue to run during the heating cycle.

When the thermostat is satisfied,

 

R and W thermostat

contacts open, the gas valve will close, the flames will
extinguish, and the induced draft blower will be de-energized.
The indoor blower motor will continue to run for the fan off
period (Field selectable at 60, 100, 140 or 180 seconds), then
will be de-energized by the control module.

CARBON MONOXIDE POISONING HAZARD

Failure to follow the steps outlined below for each 
appliance connected to the venting system being 
placed into operation could result in carbon monoxide 
poisoning or death.

The following steps shall be followed for each appliance 
connected to the venting system being placed into 
operation, while all other appliances connected to the 
venting system are not in operation:

1. Seal any unused openings in the venting system.

2. Inspect the venting system for proper size and 

horizontal pitch, as required in the National Fuel Gas 
Code, ANSI Z223.1/NFPA 54 or the CAN/CGA B149 
Installation Codes and these instructions.  Determine 
that there is no blockage or restriction, leakage, 
corrosion and other deficiencies which could cause an 
unsafe condition.

3. As far as practical, close all building doors and 

windows and all doors between the space in which the 
appliance(s) connected to the venting system are 
located and other deficiencies which could cause an 
unsafe condition.

4. Close fireplace dampers.

5. Turn on clothes dryers and any appliance not 

connected to the venting system. Turn on any exhaust 
fans, such as range hoods and bathroom exhausts, so 
they are operating at maximum speed.  Do not operate 
a summer exhaust fan.

6. Follow the lighting instructions. Place the appliance 

being inspected into operation. Adjust the thermostat 
so appliance is operating continuously.

7. If improper venting is observed during any of the above 

tests, the venting system must be corrected in 
accordance with the National Fuel Gas Code, 
ANSI Z221.1/NFPA 54 and/or CAN/CGA B149 
Installation Codes.

8. After it has been determined that each appliance 

connected to the venting system properly vents where 
tested as outlined above, return doors, windows, 
exhaust fans, fireplace dampers and any other gas-fired 
burning appliance to their previous conditions of use.

WARNING

!

Содержание TDE060A936M

Страница 1: ... 1 2 H x W x D 41 3 4 x 16 1 2 x 30 1 2 119 110 TUE060A936L Upflow Horizontal 60 000 47 000 30 60 Direct 10 x 6 1 4 See Fan Performance Table 1 3 1075 115 1 60 Centrifugal Direct 1 1 50 3180 115 1 60 1 09 No High Velocity 1 16x25 1 in 4 Round Alum Steel 20 3 45 3 56 Redundant Single Stage Hot Surface Ignition Multiport Inshot 3 115 1 60 9 0 15 1 2 H x W x D 41 3 4 x 16 1 2 x 30 1 2 127 118 TUE080A...

Страница 2: ...ingle Stage Hot Surface Ignition Multiport Inshot 6 115 1 60 13 4 20 1 2 H x W x D 41 3 4 x 26 1 2 x 30 1 2 186 174 TUE080A948L Upflow Horizontal 80 000 64 000 30 60 Direct 10 x 8 1 4 See Fan Performance Table 1 3 1075 115 1 60 Centrifugal Direct 1 1 50 3180 115 1 60 1 09 No High Velocity 1 17x25 1 in 4 Round Alum Steel 20 4 45 4 56 Redundant Single Stage Hot Surface Ignition Multiport Inshot 4 11...

Страница 3: ...ee Fan Performance Table 1 2 1075 115 1 60 Centrifugal Direct 1 1 50 3180 115 1 60 1 09 No High Velocity 2 16x20 1 in 4 Round Alum Steel Type I 20 6 45 6 56 Redundant Single Stage Hot Surface Ignition Multiport Inshot 6 115 1 60 12 8 15 1 2 H x W x D 41 3 4 x 26 1 2 x 30 1 2 189 176 TDE060A936M Downflow Horizontal 60 000 48 000 30 60 DIRECT 10 x 7 1 4 See Fan Performance Table 1 2 1075 115 1 60 Ce...

Страница 4: ...cle When the thermostat is satisfied R and W thermostat contacts open the gas valve will close the flames will extinguish and the induced draft blower will be de energized The indoor blower motor will continue to run for the fan off period Field selectable at 60 100 140 or 180 seconds then will be de energized by the control module CARBON MONOXIDE POISONING HAZARD Failure to follow the steps outli...

Страница 5: ...E On LP propane units some light yellow tipping of the outer mantle is normal Inner mantle should be bright blue Natural gas units should not have any yellow tipped flames This condition indicates that a service call is required For best operation burners must be cleaned annually using brushes and vacuum cleaner NOTE On LP propane units due to variations in BTU content and altitude servicing may b...

Страница 6: ...6 Page B 635 422 Service Facts WIRING DIAGRAM continued on next page From Dwg D341828 Rev 1 ...

Страница 7: ...Page B 635 422 7 Service Facts SCHEMATIC DIAGRAM From Dwg D341828 Rev 1 ...

Страница 8: ...8 Page B 635 422 Service Facts continued on next page WIRING DIAGRAM From Dwg D341830 Rev 1 ...

Страница 9: ...Page B 635 422 9 Service Facts SCHEMATIC DIAGRAM From Dwg D341830 Rev 1 ...

Страница 10: ...0A948L 4 3 2 1 HIGH Black MED HIGH Blue MED LOW Yellow LOW Red 1880 1662 1428 1208 1846 1635 1421 1215 1799 1598 1402 1210 1740 1551 1370 1193 1669 1493 1326 1164 1595 1424 1269 1124 1489 1345 1199 1073 1381 1256 1117 1009 1260 1157 1022 935 TUE100A960L 4 3 2 1 HIGH Black MED HIGH Blue MED LOW Yellow LOW Red 2181 1908 1621 1443 2143 1888 1609 1419 2104 1868 1597 1395 2053 1834 1582 1381 2001 1800 ...

Страница 11: ... Yellow LOW Red 1767 1382 1130 840 1731 1354 1138 831 1669 1323 1115 815 1615 1292 1085 792 1546 1254 1054 762 1469 1207 1015 731 1392 1177 977 700 1300 1108 938 654 1146 1038 877 625 TDE100A960M 4 3 2 1 HIGH Black MED HIGH Blue MED LOW Yellow LOW Red 2165 1962 1705 1492 2113 1927 1688 1467 2060 1891 1671 1442 1995 1839 1636 1414 1929 1786 1600 1385 1842 1724 1547 1346 1755 1662 1492 1307 1674 158...

Страница 12: ...LASH CODES Flashing Slow Normal No call for Heat Flashing Fast Normal Call for Heat Continuous ON Replace IFC Continuous OFF Check Power 2 Flashes System Lockout Retries or Recycles exceeded 3 Flashes Draft Pressure Error Possible problems a Venting problem b Pressure switch problem c Inducer problem 4 Flashes Open Temperature Limit Circuit 5 Flashes Flame sensed when no flame should be present 6 ...

Отзывы: