background image

2

 

                                           

 

 

 

 

2” Combustion Air / 

Vent Pipe

3” Combustion Air / 

Vent pipe

 

Max

Max

 

15’ 

(4.5M)

2

 

100’ 

(30M)

 

6

 

NOTE: Ensure all vents are properly supported.

I. Power Connections

II. Dip Switch

A. OPEN THE WATER AND GAS LINE VALVES

B. ADJUST CONTROL PANEL ON WATER HEATER FRONT COVER

C. MEASURING INLET GAS PRESSURE

LP GAS

NATURAL GAS

Minimum Pressure

3.5” WC

Minim

um Pressure

3.5” WC

Maximum Pressure

14” WC

Maximum Pressure

14” WC

 

NOTICE

   

 

 

NOTE TO CONSUMER: PLEASE KEEP ALL INSTRUCTIONS FOR 

FUTURE REFERENCE. 

Dip Switch

Off

On

 

1 –

 

3

 

Not used
Not used

Not used
Not used

4

 

5

 

Gas Type

LP

 

NG

 

6

 

High Fire

Normal

 

High Fire

7

 

Low Fire

 

Normal

 

Low Fire

 

1. Check Installation completely.

2. Check for leaks along Gas Pipes & Installation.

3. Check Exhaust Vent and Intake Pipe Instal lation for leaks. Ensure all vent pipes

are properly supported.

4. Check Condensate Drain Installation.

5. Ensure DIP switches are properly installed.

6. Check the Electrical Supply Power connections are correct.

7. Check Burner Flame for proper operation.

WARNING

The pipe size used for the supply of heated water should be the same size 

used for the water return pipe. The correct size of the hot water supply 
pipe should be ¾” diameter. Install tankless isolation valves to avoid future 

service.

E. CONDENSATE DRAIN CONNECTION

Condensate must be drained in accordance with all
local codes & regulations. Follow local codes
regarding the disposal of condensate & drainage.

Diagram left; (1) Condensate to neutralizer, (2) to
floor drains, (3) to bathtub, (4) to condensate
pump. Use only corrosion resistant materials for
the condensate drain lines, such as ½” PVC,
CPVC, Polypropylene, or the included plastic hose.
If a neutralizer is installed, periodic replacement of
the limestone (or neutralizing agent) will be

required. The rate of depletion of limestone varies

upon usage of the water heater. During the first
year of operation, check the neutralizer every few
months for depletion.

F. VENTING

Acceptable Vent Lengths (PVC, CPVC, PP)

Models

TCWH180S-AS
TCWH199S-AS

Maximum 

Number of 

Elbows

Maximum 

Number of 

Elbows

G. POWER CONNECTIONS & DIP SWITCH

Ensure that all electrical connections and wiring are installed in accordance with 

all local codes. In the absence of local codes, follow the National Electrical Code, 
NFPA 70, and/or CSA C22.1 Electrical Code-Part 1 in Canada. For your safety, 

turn off the electrical power supply at the service entrance panel before making 

any electrical connections to avoid possible electrical shock hazard. Failure to do 

so may result in property damage, severe personal injury, or death.
NOTE: DO NOT disconnect the power supply during normal water heater 
operation.

Ensure water heater is powered ON. Press & hold the         button for standby 
mode. Current ‘DHW’ set-point will display and flash. Concurrently, the caution 
mark ‘H’ will display. Current ‘DHW’ set-point can be changed by rotating the dial. 
After changing the temperature, press the Center Button to save settings.

NOTE: Refer to Installation Manual when adjusting gas pressure.

1. The water heater and its individual shutoff valve must be disconnected from
the gas supply during pressure testing of the system at test pressures greater

than ½ psi (3.5 kPa).

2. The water heater must be isolated from the gas supply by closing the manual

shutoff valve during pressure testing of the gas supply at test pressures equal to
or greater than ½ psi (3.5 kPa).

The minimum and maximum inlet gas line pressures must meet the requirements

shown below:

Do not attempt to ignite/operate water heater until all connections have been 

completed and the heat exchange is filled with water. Doing so will damage the 

water heater and void the warranty.

NOTICE: American Standard Water Heaters reserves the right to make product 
changes or updates without notice and will not be held liable for typographical 
errors in literature. 

www.americanstandardwaterheaters.com

TCWH180S-AS / TCWH199S-AS  

REV 06/16

CHAPTER 5 – FINAL CHECK

CHAPTER 4 – AFTER INSTALLATION 

12" OVER 

MAXIMUM SNOW 

LEVEL OR 24" - 

WHICHEVER IS 

GREATER

VENT KIT

EXHAUST

MAINTAIN 12" 

MINIMUM

CLEARANCE ABOVE

HIGHEST ANTICIPATED

SNOW LEVEL OR

GRADE, WHICHEVER IS

GREATER

IMPORTANT:

INTAKE LEG 

MUST

BE FACING UP

INTAKE

MAINTAIN 12" 

MINIMUM 

CLEARANCE ABOVE 

HIGHEST 

ANTICIPATED SNOW 

LEVEL OR GRADE, 

WHICHEVER IS           

GREATER

IMPORTANT:

INTAKE LEG MUST

BE FACING UP

CONCENTRIC VENT KIT

CONCENTRIC VENT KIT

1” MIN.

EXHAUST

Relief Valve

Gas Valve

Isolation Valve

Cold Water Inlet Line

Hot Water Outlet Line

Gas Supply Line

Discharge Pipe

Condensate Drain Pipe