Table 1

T deg F

RESISTANCE (OHMS

X 1000)

10K THERMISTOR

T deg F

RESISTANCE (OHMS

X 1000)

10K THERMISTOR

T deg F

RESISTANCE

(OHMS X 1000)

10K THERMISTOR

-15

138.9

35

30.0

80

9.3

-10

117.7

40

26.1

85

8.3

-5

99.9

45

22.7

90

7.3

0

85.1

50

19.9

95

6.5

5

72.7

55

17.4

100

5.8

10

62.3

60

15.3

105

5.2

15

53.5

65

13.5

110

4.7

20

46.1

70

11.9

115

4.2

25

39.8

75

10.5

120

3.8

30

34.5

Troubleshooting

Display shows two dashes when outdoor

temperature button is pressed.

Sensor not connected properly, shorted or open

wiring or sensor.

Control displays very high outdoor temperature.

Wires are touching (shorted together) or sensor is
damaged.

Control displays very low temperature.

Improper wiring connection to sensor or sensor is

damaged.

The sensor and the sensor field wiring can be checked by measuring the resistance at the control's
subbase with the control removed. See Table 1 for proper values.  

If the resistance value is /- 5

% of Table 1 values, the sensor is good.