Outdoor Temperature Sensor

ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES

IMPORTANT —

This Document is 

customer property

 and is to remain with the outdoor unit.

Please return to service information pack upon completion of work.

Installer's Guide

BAYSEN01ATEMPA

18-HD61D1-2

The BAYSEN01ATEMPA is a 10K ohm thermistor sensor
assembly used to sense outdoor temperature. Proper installa-
tion of this sensor is required for it to accurately sense outdoor
temperature.
Read this entire installation instruction before beginning the
installation.

CAUTION

!

Turn off all power to the heating and cooling equipment
before attempting to connect control wiring to Comfort
Control's subbase.

WARNING

!

This information is for use by individuals having adequate
backgrounds of electrical and mechanical experience. Any
attempt to repair a central air conditioning product may
result in personal injury and/or property damage. The
manufacturer or seller cannot be responsible for the
interpretation of this information, nor can it assume any
liability in connection with its use.

Installation

- Location

Careful consideration of the following recommendations will
help to insure that the outdoor sensor provides accurate
readings:

1. Mount the outdoor sensor on the north facing side of the

building in an area where it is exposed to freely circulat-
ing airflow and out of direct sunlight.

2. Do not allow hot air from the attic or drafts from inside

exterior walls to bias the sensor's operation. Always seal
the hole where sensor's wiring passes to the outside of
the structure. Use non-hardening caulk, putty, or
insulation.

3. Avoid locations such as near dryer vents or close to, or

directly above, the outdoor unit where it would be
exposed to hot discharge air from the condenser fan.

4. Install the sensor a minimum of 12 inches above normal

expected snow accumulation.

Wiring

Maximum length of field wiring to sensor is 200 feet.

Minimum wire gauge is 18AWG.

1. Turn all power off to the indoor air handler or furnace.

© 2005 American Standard Inc.  All Rights Reserved

Pub. No. 18-HD61D1-1

2. Separate the control from the mounting base. Route

sensor wires through the large hole in mounting base.

3. Adjust length and routing of the sensor wires to reach

the roper terminals on the connector block on mounting
base. Strip only 1/4-in. of insulation from each wire to
prevent adjacent wires from shorting together when
connected.

4. Connect the sensor's wires to the proper terminals on

the connector block.

5. Push any excess wire back into the wall and 

seal the

hole to prevent air leaks

.

Note:
Air leaks in the wall behind the control can cause improper
operation.

Control setup and checkout

1. Reinstall the control on its mounting base.

2. Turn ON power to the furnace or air handler.

3. Enter the Comfort Control's Installer Setup mode and

enable the Outdoor Temperature for display only or
for display and control. See the control's installation/
setup  instructions for details.

4. After setup is complete, verify that the sensor and

control are operating properly. The outdoor tempera-
ture should display with no service icon present.