American Standard 4A6H5 Скачать руководство пользователя страница 19

11-BC26D1-11-EN 

 

    19 

STEP 8

 - Verify typical performance.

Refer to System Pressure Curves in the Service 
Facts to verify typical performance.

STEP 6

 - Adjust refrigerant level to attain 

proper gage pressure.

Add refrigerant

 if the Liquid Gage Pressure 

is lower than the chart value.

1.  Connect gages to refrigerant bottle 

and unit as illustrated.

2.  Purge all hoses.
3.  Open bottle.
4.  Stop adding refrigerant when liquid 

line temperature and Liquid Gage 
Pressure matches the charging chart 
Final Subcooling value.

Recover refrigerant 

if the Liquid Gage Pres-

sure is higher than the chart value.

(Example only - see Service Facts)

20 MIN.

STEP 7 

-  Stabilize the system.

1.  Wait 20 minutes for the system condi-

tion to stabilize between adjustments.

Note: 

When the Liquid Line Temperature and 

Gage Pressure approximately match the chart, 
the system is properly charged.

2.  Remove gages.
3.  Replace service port caps to prevent 

leaks.  Tighten finger tight plus an ad-
ditional 1/6 turn.

PRESSURE CURVES FOR  4TWR3036B1000A

TAM4A0A36S31

TAM4A0A36S31

Cooling

Heating

DI

SCHARG

PRESSURE 

(PSI

G

)

OUTDOOR TEMPERATURE (Degree F)

SUCTI

O

N

 PRESSURE 

(PSI

G

)

OUTDOOR TEMPERATURE (Degree F)

COOLING PERFORMANCE CAN BE CHECKED WHEN THE OUTDOOR TEMP IS ABOVE 65 DEG F.

TO CHECK COOLING PERFORMANCE, SELECT THE PROPER INDOOR CFM, ALLOW PRESSURES TO STABILIZE.  MEASURE INDOOR WET BULB 
TEMPERATURE, OUTDOOR TEMPERATURE, DISCHARGE AND SUCTION PRESSURES.  ON THE PLOTS LOCATE OUTDOOR TEMPERATURE (1); 
LOCATE INDOOR WET BULB (2);  FIND INTERSECTION OF OD TEMP. & ID W.B. (3); READ DISCHARGE OR SUCTION PRESSURE IN LEFT 
COLUMN (4) or (5).

EXAMPLE: (1) OUTDOOR TEMP. 82 F. 

                  (2) INDOOR WET BULB 67 F.  

                  (3) AT INTERSECTION

ACTUAL: 

                  (4) DISCHARGE PRESSURE IS 315 PSIG

DISCHARGE PRESSURE SHOULD BE +/- 10 PSI OF CHART

                  (5) SUCTION PRESSURE IS 135 PSIG

SUCTION PRESSURE SHOULD BE +/- 3 PSIG OF CHART

INTERCONNECTING LINES
GAS - 3/4" O.D.
LIQUID - 3/8" O.D.

DWG.NO. 4TWR3036B1

(2)

(5)

(3)

(1)

110

115

120

125

130

135

140

145

150

155

160

55

65

75

85

95

105

115

(2)

(4)

(3)

(1)

200

250

300

350

400

450

500

55

65

75

85

95

105

115

INDOOR ENTERING WET BULB CURVES TOP TO BOTTOM 71, 
67, 63 AND 59 DEG F.

INDOOR ENTERING WET BULB CURVES TOP TO BOTTOM 

71, 67, 63 AND 59 DEG F.

40

50

60

70

80

90

100

110

120

130

140

150

160

-5

5

15

25

35

45

55

65

250

300

350

400

450

500

-5

5

15

25

35

45

55

65

INDOOR ENTERING DRY BULB CURVES TOP TO BOTTOM 80, 70, AND 60 
DEG F.

INDOOR ENTERING DRY BULB CURVESTOP TO BOTTOM 80, 70, AND 
60 DEG F.

Содержание 4A6H5

Страница 1: ...pproved matched indoor and outdoor systems All of the manufacture s split systems are AHRI rated only with TXV EEV indoor systems Some of the benefits of installing approved matched indoor and out doo...

Страница 2: ...ponent replacement For specific handling concerns with R 410A and POE oil reference Retrofit Bulletins SS APG006 EN and APP APG011 EN or APP APG012 EN Extreme caution should be exercised when opening...

Страница 3: ...or other line lengths Refer to Refriger ant Piping Application Guide SS APG006 EN or Refrigerant Piping Software Program 32 3312 03 or latest revision When mounting the outdoor unit on a roof be sure...

Страница 4: ...w drift barrier should be installed around the unit to prevent a build up of snow on the sides of the unit Min 12 Snow Barrier 3 12 Elevation Snow Legs Pad Ensure the top discharge area is unrestricte...

Страница 5: ...ing the unit on a support pad such as a concrete slab consider the following The pad should be at least 1 larger than the unit on all sides The pad must be separate from any structure The pad must be...

Страница 6: ...h the system charge required for the outdoor condensing unit fifteen 15 feet of tested connecting line and the smallest indoor evaporative coil match If connecting line length exceeds fifteen 15 feet...

Страница 7: ...re due to vibration transmission from the refrigerant lines For Example When the refrigerant lines have to be fastened to floor joists or other framing in a structure use isolation type hangers Isolat...

Страница 8: ...e or other appropriate method every 8 ft 8 Feet Maximum Isolation Through Wall DO NOT hang line sets from ductwork Sealant Insulation Vapor Line Wall Ductwork Isolator Line Set Section 7 Refrigerant L...

Страница 9: ...er check liquid line filter drier s directional flow arrow to confirm correct direction of refrigeration flow away from outdoor unit and toward evapo rator coil as illustrated Braze the filter drier t...

Страница 10: ...2 Check for leaks by using a soapy solu tion or bubbles at each brazed location Remove nitrogren pressure and repair any leaks before continuing Section 8 Refrigerant Line Leak Check 8 1 Check For Le...

Страница 11: ...ete blank off the vacuum pump and micron gauge and close the valves on the manifold gauge set 1 MIN Section 10 Service Valves 10 1 Open the Gas Service Valve 0350 Microns ON OFF CAP 1 4 TURN ONLY COUN...

Страница 12: ...ve System Service Port 3 16 Hex Wrench Unit Side of Service Valve Extreme caution should be exercised when opening the Liquid Line Service Valve Turn counterclockwise until the valve stem just touches...

Страница 13: ...frost will terminate at 47 F For a higher termination temperature cut Jumper J2 to achieve 70 F See Service Facts shipped in the outdoor unit for more information Pin Identification on J5 See Illustra...

Страница 14: ...gh Voltage Ground Ground the outdoor unit per national state and local code requirements LIVE ELECTRICAL COMPONENTS During installation testing servicing and troubleshooting of this product it may be...

Страница 15: ...s to apply power to the indoor and outdoor units STEP 5 Set system thermostat to ON OFF DONE CANCEL ON OFF STEP 4 Wait one 1 hour before starting the unit if compressor crankcase heater acces sory is...

Страница 16: ...ent tempera ture is above 55 F For best results the indoor temperature should be kept between 70 F to 80 F STEP 1 Use the refrigerant line total length and lift measurements from Section 5 3 Total Lin...

Страница 17: ...RISE Add 2 REFRIGERANT LINE LIFT FT 50 1 40 30 25 Use Design Subcooling 15 1 10 0 20 30 40 50 60 70 80 90 100 110 120 130 140 150 Add 1 REFRIGERANT LINE LIFT FT SUBCOOL CHARGING CHART CORRECTIONS TABL...

Страница 18: ...essure should be ap proximately 327 PSIG This is the shown as the intersection of the Final Subcooling column and the Liquid Temperature row Table 14 2 8 9 10 11 12 13 14 179 182 185 188 191 195 198 1...

Страница 19: ...F SUCTION PRESSURE PSIG OUTDOOR TEMPERATURE Degree F COOLING PERFORMANCE CAN BE CHECKED WHEN THE OUTDOOR TEMP IS ABOVE 65 DEG F TO CHECK COOLING PERFORMANCE SELECT THE PROPER INDOOR CFM ALLOW PRESSUR...

Страница 20: ...___ F Liquid Gage Pressure __________ PSIG Suction Gage Pressure __________ PSIG Calculating Charge Using the Weigh In Method STEP 1 Measure in feet the distance between the outdoor unit and the indoo...

Страница 21: ...btained with the namplate charge plus additional charge previously added STEP 5 Return to site for adjustment Important Return in the spring or summer to accurately charge the system in the cooling mo...

Страница 22: ...gainst the following list Final phases of this installation are the unit Operational and Checkout Procedures To obtain proper performance all units must be operated and charge adjustments made Importa...

Страница 23: ...A C T O R C O I L L O W V O L T A G E F U S E S T U C K C O M P R E S S O R I N E F F I C I E N T C O M P R E F U N D E R C H A R G E R E F O V E R C H A R G E E X C E S S I V E E V A P L O A D N O N...

Страница 24: ...com 2016 American Standard Heating Air Conditioning 10 17 The manufacturer has a policy of continuous product and product data improvement and it reserves the right to change design and specification...

Отзывы: