American Standard 4A6H5 Скачать руководство пользователя страница 1

11-BC26D1-11-EN

ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES

IMPORTANT — This Document is customer property and is to remain with this unit.  Please return to service informa-
tion pack upon completion of work.

Heat Pumps

These instructions do not cover all variations in systems or provide for every possible contingency to be met in connection with 
the installation. Should further information be desired or should particular problems arise which are not covered sufficiently for the 
purchaser’s purposes, the matter should be referred to your installing dealer or local distributor.

Note:

 The manufacturer recommends installing only approved matched indoor and outdoor systems. All of the manufacture’s split 

systems are AHRI rated only with TXV/EEV indoor systems. Some of the benefits of installing approved matched indoor and out-

door split systems are maximum efficiency, optimum performance and the best overall system reliability.

4A6H5

Installer’s Guide

Table of Contents

Section 1. Safety

 ..................................................................................... 2

Section 2. Unit Location Considerations

.............................................. 3

Section 3. Unit Preparation

 .................................................................... 5

Section 4. Setting the Unit

 ..................................................................... 5

Section 5. Refrigerant Line Considerations

 ......................................... 6

Section 6. Refrigerant Line Routing

 ..................................................... 7

Section 7. Refrigerant Line Brazing

 ...................................................... 8

Section 8. Refrigerant Line Leak Check

 ............................................. 10

Section 9. Evacuation

 ........................................................................... 11

Section 10. Service Valves

 ................................................................... 11

Section 11. Electrical - Low Voltage

 .................................................... 12

Section 12. Electrical - High Voltage

 ................................................... 14

Section 13. Start Up

 .............................................................................. 15

Section 14. System Charge Adjustment

 ............................................. 16

Section 15. Checkout Procedures and Troubleshooting

 ................... 23

Содержание 4A6H5

Страница 1: ...pproved matched indoor and outdoor systems All of the manufacture s split systems are AHRI rated only with TXV EEV indoor systems Some of the benefits of installing approved matched indoor and out doo...

Страница 2: ...ponent replacement For specific handling concerns with R 410A and POE oil reference Retrofit Bulletins SS APG006 EN and APP APG011 EN or APP APG012 EN Extreme caution should be exercised when opening...

Страница 3: ...or other line lengths Refer to Refriger ant Piping Application Guide SS APG006 EN or Refrigerant Piping Software Program 32 3312 03 or latest revision When mounting the outdoor unit on a roof be sure...

Страница 4: ...w drift barrier should be installed around the unit to prevent a build up of snow on the sides of the unit Min 12 Snow Barrier 3 12 Elevation Snow Legs Pad Ensure the top discharge area is unrestricte...

Страница 5: ...ing the unit on a support pad such as a concrete slab consider the following The pad should be at least 1 larger than the unit on all sides The pad must be separate from any structure The pad must be...

Страница 6: ...h the system charge required for the outdoor condensing unit fifteen 15 feet of tested connecting line and the smallest indoor evaporative coil match If connecting line length exceeds fifteen 15 feet...

Страница 7: ...re due to vibration transmission from the refrigerant lines For Example When the refrigerant lines have to be fastened to floor joists or other framing in a structure use isolation type hangers Isolat...

Страница 8: ...e or other appropriate method every 8 ft 8 Feet Maximum Isolation Through Wall DO NOT hang line sets from ductwork Sealant Insulation Vapor Line Wall Ductwork Isolator Line Set Section 7 Refrigerant L...

Страница 9: ...er check liquid line filter drier s directional flow arrow to confirm correct direction of refrigeration flow away from outdoor unit and toward evapo rator coil as illustrated Braze the filter drier t...

Страница 10: ...2 Check for leaks by using a soapy solu tion or bubbles at each brazed location Remove nitrogren pressure and repair any leaks before continuing Section 8 Refrigerant Line Leak Check 8 1 Check For Le...

Страница 11: ...ete blank off the vacuum pump and micron gauge and close the valves on the manifold gauge set 1 MIN Section 10 Service Valves 10 1 Open the Gas Service Valve 0350 Microns ON OFF CAP 1 4 TURN ONLY COUN...

Страница 12: ...ve System Service Port 3 16 Hex Wrench Unit Side of Service Valve Extreme caution should be exercised when opening the Liquid Line Service Valve Turn counterclockwise until the valve stem just touches...

Страница 13: ...frost will terminate at 47 F For a higher termination temperature cut Jumper J2 to achieve 70 F See Service Facts shipped in the outdoor unit for more information Pin Identification on J5 See Illustra...

Страница 14: ...gh Voltage Ground Ground the outdoor unit per national state and local code requirements LIVE ELECTRICAL COMPONENTS During installation testing servicing and troubleshooting of this product it may be...

Страница 15: ...s to apply power to the indoor and outdoor units STEP 5 Set system thermostat to ON OFF DONE CANCEL ON OFF STEP 4 Wait one 1 hour before starting the unit if compressor crankcase heater acces sory is...

Страница 16: ...ent tempera ture is above 55 F For best results the indoor temperature should be kept between 70 F to 80 F STEP 1 Use the refrigerant line total length and lift measurements from Section 5 3 Total Lin...

Страница 17: ...RISE Add 2 REFRIGERANT LINE LIFT FT 50 1 40 30 25 Use Design Subcooling 15 1 10 0 20 30 40 50 60 70 80 90 100 110 120 130 140 150 Add 1 REFRIGERANT LINE LIFT FT SUBCOOL CHARGING CHART CORRECTIONS TABL...

Страница 18: ...essure should be ap proximately 327 PSIG This is the shown as the intersection of the Final Subcooling column and the Liquid Temperature row Table 14 2 8 9 10 11 12 13 14 179 182 185 188 191 195 198 1...

Страница 19: ...F SUCTION PRESSURE PSIG OUTDOOR TEMPERATURE Degree F COOLING PERFORMANCE CAN BE CHECKED WHEN THE OUTDOOR TEMP IS ABOVE 65 DEG F TO CHECK COOLING PERFORMANCE SELECT THE PROPER INDOOR CFM ALLOW PRESSUR...

Страница 20: ...___ F Liquid Gage Pressure __________ PSIG Suction Gage Pressure __________ PSIG Calculating Charge Using the Weigh In Method STEP 1 Measure in feet the distance between the outdoor unit and the indoo...

Страница 21: ...btained with the namplate charge plus additional charge previously added STEP 5 Return to site for adjustment Important Return in the spring or summer to accurately charge the system in the cooling mo...

Страница 22: ...gainst the following list Final phases of this installation are the unit Operational and Checkout Procedures To obtain proper performance all units must be operated and charge adjustments made Importa...

Страница 23: ...A C T O R C O I L L O W V O L T A G E F U S E S T U C K C O M P R E S S O R I N E F F I C I E N T C O M P R E F U N D E R C H A R G E R E F O V E R C H A R G E E X C E S S I V E E V A P L O A D N O N...

Страница 24: ...com 2016 American Standard Heating Air Conditioning 10 17 The manufacturer has a policy of continuous product and product data improvement and it reserves the right to change design and specification...

Отзывы: