background image

Section III - Minimum Operating Clearances

This section discusses applying a condensing unit / heat pump in installations where there are space
constraints.

These concerns must be addressed:
1. System Operation - Adequate airflow must be provided to the condensing unit / heat pump in order
to enable appropriate heat transfer. If this is accomplished, head pressure will remain within an effective
operating range.
2. System Servicability - Proper space must be allowed for the HVAC service technician to properly
maintain the condensing unit / heat pump. Furthermore, space must be allowed for major
component change out in the event of a failure. Working space is determined by the National Electric
Code
3. Space Maintenance - Appropriate area must be allowed in order maintain the ground area where the
units are positioned to prohibit debris from collecting on the panels, thus further providing unobstructed
airflow to the condensing unit.
4. State, Local Codes, and National Codes shall prevail. Check with the local jurisdiction before
installation to assure compliance.

Numerous projects require reduced clearances between outdoor units and adjacent walls, fences and other
units. The obstruction in question is usually one of the following:

1. One or more walls of an adjacent building.
2. Fences or barriers provided to reduce sound transmission or visually screen the equipment.
3. Other outdoor units in a multi-unit installation.
4. Overhangs
5. A combination of the above.

The prime considerations involved in establishing minimum clearances are:

1. Adequate airflow to the outdoor coil with minimum recirculation.
2. Service access to the equipment.
3. Compliance with the National Electric Code and other applicable codes.
4. Design temperature - Design temperatures greater than 105F require additional consideration.

I. In order to assure that adequate airflow reaches the Allegiance 18

 

condensing unit, size free air passages

at 300 feet per minute maximum velocity (FPM). See condensing unit airflow performance on page 16 of
this document; or, for the most current information, consult the unit’s product data manual.

II. The importance of providing sufficient access for maintenance and service to equipment cannot be
overemphasized. The HVAC service technician’s job may be performed with greater ease and at lower cost
if adequate space is allowed.

III. Knowledge of the National Electric Code and other applicable codes for the job sight location is a
necessity in order to satisfy local inspectors. These codes are in place for service as well as safety.

IV. Be sure to read all provisions and footnotes contained in this document. When ambient temperatures
exceed 105F, more space may be required for minimum operating clearances.

Pg. 7

Содержание 2A6H8030A

Страница 1: ...EN American Standard Allegiance and Heritage 18 dual compressor cooling units and heat pumps Low Outdoor Operating Temperature Unit Mounting Minimum Clearances Refrigerant Piping Limitations American...

Страница 2: ...heAmericanStandard Allegiance Heritage18coolingunitsandheatpumps Thisbulletindiscusses I OffSeasonCoolingOperation II UnitMounting III MinimumOperatingClearances IV RefrigerantPipingLimitations ISSUED...

Страница 3: ...T D O S E I R O S S E C C A D E R I U Q E R l e d o M 5 4 0 F 0 4 0 3 0 F 0 0 F 8 1 e c n a i g e l l A d e p p i h S s A C D E t o N d e v o r p p A 8 1 e g a t i r e H d e p p i h S s A C D E t o N...

Страница 4: ...R Y1 Y2 G W W2 B Red R Y YLow Green G White W1 White W2 White W3 Blue B Orange O R Y2 Y1 G W1 X2 B O EDR 1 EDC EDR Y1 Red R Ylow Green G White W1 White W2 White W3 Blue B EDC Heat Pump Split System an...

Страница 5: ...umps please observe thefollowing 1 Anytimetheunitistobesupportedfromtheedge thesupportingmaterialshallextendminimumtwo inches under the perimeter of the unit s base 2 Themountingholelocationsaremolded...

Страница 6: ...extend 2 from the basepan perimeter If supporting the base pan from the perimeter the support must extend under the base pan at least 2 American Standard recommends supporting the middle of the base p...

Страница 7: ...cent building 2 Fences or barriers provided to reduce sound transmission or visually screen the equipment 3 Otheroutdoorunitsinamulti unitinstallation 4 Overhangs 5 Acombination of the above Theprimec...

Страница 8: ...rand unrestricted top clearance A For locations where the design ambient temperature is below 105F 1 Corner unit shall have1 5 feet clearance from side wall and 1 0 feet clearance from back wall 2 1 f...

Страница 9: ...ional Electric Code for more informationregardingminimumclearancesforworkingspaces Service Panel Service Panel 1 0 min 1 0 m i n 1 0 m i n 1 0 min 1234 1234 1234 1234 12 12 12 12 12 12 12 12 12 12345...

Страница 10: ...shall have 2 0 feet clearance from one wall and 1 5 feet clearance from the other wall 2 2 0 feet clearance in between units 3 NEC requires 3 feet clearance for service This may be reduced to 2 5 feet...

Страница 11: ...et Consult the National Electric Code for more informationregardingminimumclearancesforworkingspaces Service Panel 3 0 min 5 feet minimum unrestricted top clearance shall be provided 3 feet minimum cl...

Страница 12: ...Access Units may be rotated as shown on the following page in order that service access sides face each other provided that 3 feet minimum clearance be maintained between the units In order to comply...

Страница 13: ...ss Service Access Service Access Service Access Service Access Service Access Service Access Units may be rotated as shown on above in order that service access sides face each other provided that 3 f...

Страница 14: ...feet Please consult the 2002 or current Edition of the National Electric Code Article 110 for the most up to date information D Fence construction 1 Height shall not exceed the top of the unit 2 Free...

Страница 15: ...m 3FT 1 M 3 5FT 1 2 mm 4FT Note Where the conditions are as follows Condition 1 Exposed live parts on one side and no live or grounded parts on the other side of the working space or exposed live part...

Страница 16: ...le Given Qty of 2 units in an area surrounded by a fence on two sides and solid walls on the other two sides Units are 2A7A8060A1000A Required Determine free air opening space required in fence Soluti...

Страница 17: ...1 1 4 4 1 7 3 4 1 4 3 1 A 0 3 0 8 H 6 A 2 4 8 1 1 4 4 1 7 3 4 1 4 3 A 6 3 0 8 A 7 A 2 4 8 1 1 4 4 1 7 3 4 1 4 3 1 A 6 3 0 8 H 6 A 2 4 8 1 1 4 4 1 7 3 4 1 4 3 A 8 4 0 8 A 7 A 2 4 8 1 1 4 4 1 7 3 4 1 4...

Страница 18: ...t refrigerant lines are properly sized and do notexceedthelengthsetforthintheunit sinstallationmanual 2 Linelengthlimits A Gas line 80 feet linear length of the linear length 25 feet may be installed...

Страница 19: ...Pg 19 NOTES...

Страница 20: ...persedes New Stocking Location Since American Standard has a policy of continuous product improvement it reserves the right to change design and specifications without notice American Standard Inc 620...

Отзывы: