American Dynamics RJ1SNUD Series Скачать руководство пользователя страница 6

SENSORNET SINGLE-POSITION JUNCTION BOX (J-BOX) 

8000-2573-21, REV. F 

INSTALLATION GUIDE

 

6 of 10 

6.  Run conduit and ac cable to box and clamp 

conduit in place (Figure 7). 

7. Reattach chassis. 

Figure 7. Conduit attachment 

 

8.  Wire ac line to TB1 and jumper primary taps of 

transformer according to ac source (refer back 
to Figure 6). 

120Vac:

 Place a jumper across taps 1 and 3, 

and another jumper across taps 2 and 4. 

240Vac:

 Place a jumper across taps 2 and 3 

only. 

9.  Reattach PC board assembly. 

Changing the Fuse 

To reduce the risk of fire, replace fuses with the 
same type and rating (3:15A type IEC127, sheet III). 
The part number for the fuse is 5111-0017-21. Two 
spare fuses are provided inside the cover.  

To access fuse, use a small slotted screwdriver to 
unscrew the cap of the fuse holder (Figure 7) and 
lift out the fuse. 

 

Connecting Power and  
Data Cables 

Note:

 Incoming and outgoing video cables are 

connected together within the box. No termination 
exists for video cables within the J-Box. 

Power Cable Requirements 

The low-voltage power cable runs between the 
J-Box and the camera dome. The length of this 
cable depends on the ac line voltage. See Table 1 
for cable lengths based on worst case low line 
voltages for Japan (100Vac), North America 
(120vac), and Europe (240vac). 

Table 1. Cable length vs. line voltage 

Worst 
Case Line 
Voltages

 

18AWG 16AWG 14AWG 

90 Vac  

(Japan) 

30m  

(100ft) 

50m  

(160ft) 

80m  

(260ft) 

102 Vac  

(N. Amer.) 

60m  

(200ft) 

100m  

(320ft) 

160m  

(520ft) 

180 Vac 

(Europe) 

30m  

(100ft) 

50m  

(160ft) 

80m  

(260ft) 

204 Vac  

(Europe) 

60m  

(200ft) 

100m  

(320ft) 

160m  

(520ft) 

Data Cable Requirements 

The data cable contains one non-polarized 22AWG, 
unshielded, twisted pair. Up to 1km (3000ft) of data 
cable can be run from the Host to the J-Box, or from 
J-Box to J-Box (see CAUTION below). For more 
information about the SensorNet communication 
protocol and possible cable network configurations, 
see 

Communication Protocols and Cable Networks

8000-2573-19.  

CAUTION:

 The data cable from the J-Box to the 

dome is limited by the length of the power cable. 
See Table 1 above. 

Note: 

Power, data, and video cables can be ordered 

separately or within a composite cable ordered in 
various lengths. Plenum-rated cables must be used 
in indoor ceilings used for environmental air return 
(called “other air space” in the National Electrical 
Code). Order parts through your distribution 
network. If you order cable from an outside source, 
wire colors may be different. 

Conduit 

Fuse holders 

Содержание RJ1SNUD Series

Страница 1: ...einfachen Zugang zum Ger t erlaubt Outside elements To keep outside elements from entering the J Box always mount it vertically with cable exits facing down and tighten the four plastic screws Adding...

Страница 2: ...mensions H x W x D 200 x 200 x 132mm 7 87 x 7 87 x 5 19 in Mounting area H x W 281 x 200mm 11 x 8 in Weight 3 7 kg 8 25 lbs Construction Polycarbonate non metallic enclosure Color Light gray Cover loc...

Страница 3: ...mounting brackets of the box as templates mark mounting hole locations The two center top slots in the upper bracket match the bolt spacing used for older J Boxes CAUTION J Box meets NEMA 4 standard f...

Страница 4: ...s shown in Figure 4c with J Box on ground and its rear facing towards you a Slip one of the two bands through closed slots in lower mounting bracket Pick slots appropriate for the width of the pole b...

Страница 5: ...these parts CAUTION Keep the disconnect device circuit breaker readily accessible when hardwiring J Box Do the following 1 Unplug line cord from ac outlet 2 Loosen two screws then slide and lift PC b...

Страница 6: ...ds on the ac line voltage See Table 1 for cable lengths based on worst case low line voltages for Japan 100Vac North America 120vac and Europe 240vac Table 1 Cable length vs line voltage Worst Case Li...

Страница 7: ...data line Place JW1 across pins 2 3 unterminated if the J Box is to be the hub of a star network For jumpers JW2 and JW3 See Communications Protocols and Cable Networks 8000 2573 19 Figure 8 PCB conne...

Страница 8: ...on page 7 Removing the Circuit Board Follow steps to remove the circuit board Reverse steps to reassemble 1 Loosen four captive screws to release cover 2 Remove six screws to remove circuit board Fig...

Страница 9: ...04 4 Pin Connector 2109 0254 03 Power Transformer 5604 0205 01 Cable Strain Relief 3100 0035 11 Fuse 5111 0017 21 These parts are shown bold in Figure 12 Figure 12 Exploded view of SensorNet J Box St...

Страница 10: ...e party responsible for FCC compliance could void the user s authority to operate the equipment and could create a hazardous condition WARRANTY DISCLAIMER Sensormatic Electronics Corporation makes no...

Отзывы: