SETUP
Alarm-only Sequencing on Output B
As shipped, MONITOR output B provides a continuous
sequence of the video inputs. To set up the unit such that
output B shows the sequence only during alarms, and is
otherwise blank, Jumper J45 on the main printed circuit board
(PCB) must be removed, as follows:
1. Turn unit off and unplug from power source.
2. Remove screws for top cover, and remove the top
cover.
3. Remove jumper J45, located near the middle of the
main PCB. See Figure 2, page 3, for location of J45.
4. Reattach top cover.
Audio Alarm Beeper
As shipped, the audio alarm beeper is activated during alarms.
To deactivate the beeper, remove Jumper J46, located near the
side of the printed circuit board. See Figure 2, page 3, for the
location of jumper J46. Follow the procedures outlined above
for access to the main PCB for removing this jumper.
Cascading Setup
Two switchers may be cascaded together to provide for a 32
position switcher, as described in Cascading Connections, page
4. As shipped, the first switch position of DIP switch S22 is
set for non-cascaded operation. It must be reset for cascaded
operation, as shown in the following paragraph.
On-Screen Camera Numbers
On-screen camera numbers displayed by the switcher may be
set to provide for any block of 16 camera numbers, from 1 to
512. A six-position DIP switch (S22) located on the main PCB
of the switcher is used to set the 16-camera block of on-screen
camera numbers. As shipped, all units are set for camera block
1-16. Table 1, DIP Switch S22 Camera Block Settings, shows
the correct setting of the DIP switch positions for other camera
number blocks.
Follow the procedures outlined for Alarm-only Sequencing
above for access to the main PCB to set this DIP switch. See
Figure 2, page 3 for location of DIP switch S22.
Table 1 - DIP Switch S22 Camera Block Settings
0 = OFF; 1 = ON
Camera DIP Switch Position
Block
1
2
3
4
5
6
1-16
0
0
0
0
0
*
17-32
1
0
0
0
0
*
33-48
0
1
0
0
0
*
49-64
1
1
0
0
0
*
65-80
0
0
1
0
0
*
81-96
1
0
1
0
0
*
97-112
0
1
1
0
0
*
113-128
1
1
1
0
0
*
129-144
0
0
0
1
0
*
145-160
1
0
0
1
0
*
161-176
0
1
0
1
0
*
177-192
1
1
0
1
0
*
193-208
0
0
1
1
0
*
209-224
1
0
1
1
0
*
225-240
0
1
1
1
0
*
241-256
1
1
1
1
0
*
257-272
0
0
0
0
1
*
273-288
1
0
0
0
1
*
289-304
0
1
0
0
1
*
305-320
1
1
0
0
1
*
321-336
0
0
1
0
1
*
337-352
1
0
1
0
1
*
353-368
0
1
1
0
1
*
369-384
1
1
1
0
1
*
385-400
0
0
0
1
1
*
401-416
1
0
0
1
1
*
417-432
0
1
0
1
1
*
433-448
1
1
0
1
1
*
449-464
0
0
1
1
1
*
465-480
1
0
1
1
1
*
481-496
0
1
1
1
1
*
497-512
1
1
1
1
1
*
*
Cascading Setup: Switch position 6 OFF for single unit
operation (as shipped). For cascading, set switch 6 on first
unit to ON and leave switch 6 on second unit set to OFF.
2
SETUP
AD1416,AD1416L
- CAUTION -
The following internal adjustments expose hazardous-
voltage components and allow access to dangerous
electric shock potentials. They should be made only by
qualified service personnel.