CONNECTIONS

Relay Connections

The 2032 Alarm Responder provides relay closures only;
they are not intended to supply power.  Two groups (GROUP
1 and GROUP 2) of four 12-pin relay connectors are
provided on the rear panel (see Figure 2, page 2).  Each group
provides connections for double pole relays.  The two groups
provide 32 pairs of relay closures.  Figure 3 illustrates the
internal 2032 relay interconnections for Group 1 relays.

The relay connections to the unit must be made with shielded,
2-wire twisted pair (22 AWG or heavier gauge wire or
equivalent). The shield wire is to be connected to the
grounding terminal.

Each set of three pin connections is labeled with a relay
number, from 1 through 32, corresponding to one of the
monitors of the monitor group(s) selected.  Each pin within
one of the numbered sets is also labeled, under the connector,
with an A, a B, and a ground symbol.  The A and B pins on
each connection are the contacts for one side of each double
pole relay.  The contacts for the other side of each relay are
connected to the common Group connectors (next paragraph).
The ground pin is provided for shielding.

One 12-pin connector on the lower right of the 2032 rear
panel contains the common connections for each relay group.
Each set of pins is labeled with the group number G1 IN, G1
OUT, G2 IN, and G2 OUT, and each pin is labeled with an A,
B, and ground.  The A and B pins are common contacts for
the other side of the double pole relays; G1 IN  and OUT are
connected to relays 1-16 (see Figure 3), and G2 IN and OUT
are connected to relays 17-32.  The Group IN connections are
used for determining the function of the associated relays,
such as providing a user-supplied voltage, a short to ground,
or a unique signal on relay activation.  The Group IN pins can
also be used as inputs from cascading 2032 units.  The Group
OUT connections are used to connect the associated relays to
a single responding device, such as a speaker or an indicator
light, or for cascading to additional 2032’s.

For ease of attaching to external equipment, each connector is
supplied with a mating screw terminal connector, shown in
Figure 4.  Insert the signal and shield wires into the slots of
the mating connector and tighten the hold-down screws.
When all lines have been connected, insert the 12-pin
connectors into the rear panel mating terminals.
The relay contact ratings are 0.6 Amps at 24 VAC, or 2 Amps
at 30 VDC, resistive load.  Power through the relays is not
supplied by the 2032.

Data Line Connections (1995 or 1996)

A DATA LINE is connected from the DATA LINE OUT
BNC on a Matrix Bay to the DATA LINE IN BNC on the
rear panel of the Alarm Responder.  (Older 1995 systems
used the term LAN IN/OUT).  Use a good grade RG-59 video
cable (Belden 8241 or equivalent).  The DATA LINE OUT
BNC on the Alarm Responder must be fitted with a 75-ohm
BNC terminator, or if used to loop to other DATA LINE
controlled equipment, it must be terminated at the end of the
run.

The 2032 must be connected to the Data Line which is used
for the group of monitors to be followed.  For 1995 and 1996
systems, Data Line 1 is for monitors 1-64 and Data Line 2 is
for monitors 65-128.

The LED labeled DATA, on the rear panel, will illuminate
when valid code is received on the Data Line.

3

CONNECTIONS  

Figure 4 - Typical 12-Pin Connector

Figure 3 - 2032 Relay Contacts (Group 1) 

HOLD DOWN SCREWS

INSERT CONNECTOR

THIS DIRECTION

A

B

B

A

B

A

B

A

G1 IN

G1 OUT

A

B

A

B

1

2

3

A

B

A

B

A

B

Содержание 2032

Страница 1: ...ed with all American Dynamics Matrix Switching Systems to follow and respond to alarm conditions The 2032 Alarm Responder provides a relay closure when a monitor goes into an alarm condition The relay closures may be used to start a VCR or other such device Other uses include the operation of panel displays showing alarmed monitors Installation and Operating Instructions ...

Страница 2: ... is furnished to the purchaser under a license for use on a single system Information furnished by SENSORMATIC is believed to be accurate and reliable However no responsibility is assumed by SENSORMATIC for its use nor for any infringements of other rights of third parties which may result from its use No license is granted by implications or otherwise under any patent or patent rights of SENSORMA...

Страница 3: ...ved with the packing list with your order Be sure to save 1 The shipping cartons and insert pieces They are the safest material in which to make future shipments of the product 2 The IMPORTANT SAFEGUARDS sheet 3 These Installation and Operating Instructions M M M MA A A AI I I IN N N NT T T TE E E EN N N NA A A AN N N NC C C CE E E E User maintenance of this unit is limited to external cleaning an...

Страница 4: ......

Страница 5: ...ures 1 Installation 2 Setup 2 Monitor Select 2 Connections Relay Connections 3 Data Line Connections 3 Control Code Line Connections 4 Operation 5 Power Sources 5 Powering Up 5 Typical System Connections Appendix Specifications back page ...

Страница 6: ......

Страница 7: ...owed only from 1995 1996 systems on Data Line 2 The 2032 contains 32 addressable normally open relays The 32 relays can be grouped in series or in two groups of 16 Each of the two groups can control 16 relays FEATURES The 2032 Alarm Responder has the following features SCREW TERMINAL WIRE CONNECTORS LED INDICATOR FOR VALID CODE LED POWER INDICATOR DIP SWITCH SELECTION FOR MONITOR GROUP COMPATIBLE ...

Страница 8: ...at the 2032 will respond to The DIP switches and associated relay group connectors are shown in Figure 2 The first DIP switch 1 sets the monitor group for the GROUP 1 relays relays 1 through 16 The third DIP switch 3 sets the monitor group for the GROUP 2 relays relays 17 through 32 The second and fourth DIP switches are not used in the 2032 Switches 1 and 3 can be set either to the same or to two...

Страница 9: ...ion of the associated relays such as providing a user supplied voltage a short to ground or a unique signal on relay activation The Group IN pins can also be used as inputs from cascading 2032 units The Group OUT connections are used to connect the associated relays to a single responding device such as a speaker or an indicator light or for cascading to additional 2032 s For ease of attaching to ...

Страница 10: ... a Star configuration to a Control Code distribution unit 1691 or 2091 See Figure 5 For this connection each 2032 must have a 120 ohm termination A maximum of three 2032s or other Control Control devices may be Daisy chained on a single code line When devices are Daisy Chained intermediate devices must not contain a 120 ohm termination on the Control Code line Only the last unit in a Daisy Chain h...

Страница 11: ...esponder does not contain an On Off Switch The socket outlet shall be located near the equipment and shall be readily accessible The 120V units are supplied with a pendant 3 wire cord and plug for mating to the primary source outlet The 230V units are supplied with a Euro style IEC 320 type inlet A suitable detachable cord should be connected between the IEC 320 inlet and the power source The cord...

Страница 12: ......

Страница 13: ...APPENDIX ...

Страница 14: ......

Страница 15: ...UP 2 A B A B A B A B A B A B A B A B A B A B A B A B A B A B A B A B A B A B A B A B A B A B A B A B A B A B A B A B A B A B A B A B A B A B A B A B B W S 5678 9101112 13141516 21222324 25262728 29303132 17181920 G1 IN G1 OUT G2 IN G2 OUT CONTROL CODE INPUT 1600 1650A Monitor 1 Relay Connections Relay Group 1 Output Connections or Cascading to other 2032 s G1 IN G1 OUT G2 IN G2 OUT A A B B A B A B...

Страница 16: ... R RS S S S 2 2 2 23 3 3 32 2 2 2 1 1 1 1 2 2 2 2 3 3 3 3 J J J J1 1 1 1 O O O OU U U UT T T T M M M MO O O ON N N NI I I IT T T TO O O OR R R R 2 2 2 2 1 1 1 1 O O O O U U U U T T T T O O O O U U U U T T T T A A A A A A A A B B B B B B B B M M M MO O O ON N N NI I I IT T T TO O O OR R R R 4 4 4 4 3 3 3 3 M M M MO O O ON N N NI I I IT T T TO O O OR R R R 6 6 6 6 5 5 5 5 M M M MO O O ON N N NI I I ...

Страница 17: ...41516 21222324 25262728 29303132 17181920 G1 IN G1 OUT G2 IN G2 OUT 1234 B W S B W S 1650 MONITORS 1 8 1650 MONITORS 9 16 2032 MONITORS 9 16 ALARM POWER INPUT OUTPUT C O M 1 2 3 4 5 6 SELECT PRGM 29 28 30 27 26 25 49 50 51 52 53 54 7 8 9 10 11 12 31 32 33 34 35 36 55 56 57 58 59 60 15 13 14 16 17 18 37 38 39 40 41 42 61 62 63 64 19 20 21 22 23 24 43 44 45 4647 48 120V 60Hz A A A A A A A A A A A A ...

Страница 18: ... 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 1024 Bay TERMINATION To 1024 Bays and 2032 for MONITORS 65 128 Additional 1024 Bays DATA LINE IN OUT SYNC 120 VAC 50 60 Hz 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 T E S T E X P A N S I O N 1 GROUP 1 GROUP 2 DATA LINE IN OUT 1 DATA PWR ABCDEF ON OFF ABCDEF ON OFF ABCDEF ON OFF ABCDEF ON OFF SELECT A B A B A B A B B W S G1 IN G1 OUT G2 IN G2 OUT 1 2 3 4 5...

Страница 19: ...ns Safety EN 60950 1992 EMC EN 50130 4 1995 EN 55022 1994 Class B EN 61000 3 2 1995 EN 61000 3 3 1995 EN 61000 4 2 1995 EN 61000 4 3 1996 EN 61000 4 4 1995 EN 61000 4 5 1995 EN 61000 4 6 1996 EN 61000 4 11 1994 Supplementary Information The products herewith comply with the requirements of the Low Voltage Directive 73 23 EEC as amended by 93 68 EEC and the EMC Directive 89 339 EEC as amended by 93...

Страница 20: ...n_A December _2000_________________________________________________________________________Printed_in_USA SPECIFICATIONS Electrical Ratings AD2032 120 VAC 50 60 Hz 15 W AD2032 1 230 VAC 50 60 Hz 125 mA Relay Contact Ratings 0 6 A 24 VAC 2 A 30 VDC Mounting Surface Mount or Rack Mount Weight 7 lbs 1 4 Kg Finish Shadow Gray Dimensions 17 W x 3 5 H x 8 D 432 x 89 x 203 mm ...

Отзывы: