background image

8

E.  EXHAUST REQUIREMENTS

Exhaust ductwork 

should be

 designed and installed by a competent technician.  Improperly sized ductwork will

create excessive back pressure which results in slow drying, increased use of energy, overheating of the dryer, and
shutdown of the burner by the airflow (sail) switches, burner hi-limits, or basket (tumbler) hi-heat protector
thermostats.  The dryer 

must be 

installed with a proper exhaust duct connection to the outside.

CAUTION:

This dryer produces combustible lint and 

must be 

exhausted to the outdoors.

CAUTION: IMPROPERLY SIZED OR INSTALLED EXHAUST DUCTWORK CAN

CREATE A POTENTIAL FIRE HAZARD

.

Where possible, it is suggested to provide a separate exhaust duct for each dryer.  The exhaust ductwork 

should

be

 laid out in such a way that the ductwork travels as directly as possible to the outdoors, with as few turns as

possible.  It is suggested that the use of right angle turns in the ducting be avoided; use 30º or 45º angles instead.
The shape of the exhaust ductwork is not critical, so long as the minimum cross section area is provided.

If the exhaust ductwork is unusually long (over 20 feet [6.1 meters]) or has numerous elbows, the cross section
area of the ductwork 

must be

 increased in proportion to its length or the number of elbows in it.  In calculating

duct size, the cross section area of a square rectangle duct 

must be

 increased 20 percent (20%) for each additional

20 feet (6.1 meters).  The diameter of a round exhaust 

should be

 increased 10 percent (10%) for each additional

20 feet (6.1 meters).  Each 90º elbow is equivalent to an additional 15 feet (4.57 meters), and each 45º elbow, an
additional 10 feet (3.05 meters).

The ductwork 

should be

 smooth inside with no projections from sheet metal screws or other obstructions, which

will collect lint.  When adding ducts, the duct to be added should overlap the duct to which it is to be connected.
Also, inspection doors 

should be

 installed at strategic points in the exhaust ductwork for periodic inspection and

cleaning.

To protect the outside end of the horizontal ductwork from the weather, a 90º elbow bent downward 

should be

installed where the exhaust exits the building.  (Refer to the 

illustration 

on the following page.)  If the exhaust

ductwork travels vertically up through the roof, it 

should be

 protected from the weather by using a 180º turn to

point the opening downward.  (Refer to the 

illustration 

on the following page.)  In either case, allow at least twice

the diameter of the duct between the duct opening and nearest obstruction.

IMPORTANT:

DO NOT

 use screens, louvers, or caps on the outside opening of the exhaust

ductwork.

1. Multiple Dryer Venting

If it is not feasible to provide separate exhaust ducts for each dryer, ducts from individual dryers may be
channeled into a “common main duct.”  (Refer to the 

illustration 

on the following page.)  The individual

ducts should enter the bottom or side of the main duct at an angle not more than 45º in the direction of
airflow.  The main duct 

should be

 tapered, with the diameter increasing before each individual duct is

added.  The cross section area 

should be

 60 square inches (387.10 square centimeters) for each 8-inch

(20.32 cm) duct added.

Содержание ADG-215

Страница 1: ...annot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier AVERTISSEMENT Assurez vous de bien suivre les instructions données dans cette notice pour réduire au minimum le risque d incendie ou d explosion ou pour éviter tout dommage matériel toute blessure ou la mort Ne pas entreposer ni utiliser d es...

Страница 2: ...nual as complete as possible and hope you will find it useful ADC reserves the right to make changes from time to time without notice or obligation in prices specifications colors and material and to change or discontinue models The illustrations included in this manual may not depict your particular dryer exactly Important For your convenience log the following information DATE OF PURCHASE_______...

Страница 3: ...IN OPERATION CAUTION DRYERS SHOULD NEVER BE LEFT UNATTENDED WHILE IN OPERATION FOR YOUR SAFETY DO NOT DRY MOP HEADS IN THE DRYER DO NOT USE DRYER IN THE PRESENCE OF DRY CLEANING FUMES WARNING UNDER NO CIRCUMSTANCES should the dryer door switch or heat circuit safety devices ever be disabled Caution Label all wires prior to disconnection when servicing controls Wiring errors can cause improper oper...

Страница 4: ...layed on the equipment and or specified in the installation manual included with the dryer WARNING DRYER MUST NEVER BE OPERATED WITHOUT THE LINT FILTER SCREEN IN PLACE EVEN IF AN EXTERNAL LINT COLLECTION SYSTEM IS USED Dryer must not beinstalled or stored in an area where itwill be exposed to water or weather The wiring diagram for the dryer is located in the front electrical control box area ...

Страница 5: ...INSTALLATION PROCEDURES 5 A Unpacking Set Up 5 B Location of the Dryer 5 C Dryer Enclosure Requirements 6 D Fresh Air Supply Requirements 7 E Exhaust Requirements 8 F Electrical Information 10 G Gas Information 13 H Preparation for Operation 16 I Preoperational Tests 17 SECTION IV MAINTENANCE 18 A Cleaning 18 B Adjustments 19 C Lubrication 19 ...

Страница 6: ...uest an inspection and freight claim form The freight company considers this concealed damage This type of freight claim is very difficult to get paid and becomes extremely difficult when more than a day or two passes after the freight was delivered 5 If you need assistance in handling the situation please call American Dryer Corporation IMPORTANT The dryer should be transported and handled in an ...

Страница 7: ...nd exhaust ductwork The frequency of inspection and cleaning can best be determined from experience at each location WARNING The collection of lint in the burner area and exhaust ductwork can create a potential fire hazard 6 For personal safety the dryer must be electrically grounded in accordance with local codes and or the National Electrical Code ANSI NFPA NO 70 LATEST EDITION or in Canada the ...

Страница 8: ...4 SECTION II SPECIFICATIONS NOTE ADC reserves the right to make changes in specifications at any time without notice or obligation ...

Страница 9: ...he wooden skid Two 2 are located at the rear of the base and two 2 are located in front Once the bolts are removed slide the dryer off the skid With the skid removed to make it easier to slide the dryer into its final position slightly lower ALL four 4 leveling legs so that the dryer will slide on the legs instead of the base frame The dryer is equipped with four 4 leveling legs one 1 at each corn...

Страница 10: ... of 6 inches 15 24 cm above the dryer outer top except along the front of the dryer which may be closed in if desired LEAVE 18 24 AT REAR OF DRYER FOR MAINTENANCE SERVICE Dryers may be positioned sidewall to sidewall However allowancesshould be made for the opening and closing of the control and lint doors It is suggested that the dryer be positioned about 2 feet 0 61 meters away from the nearest ...

Страница 11: ... the make up air is distributed equally to the dryers The dryer must be installed with provisions for adequate combustion and make up air supply EXAMPLE For a bank of eight 8 dryers a total make up air opening of 12 square feet 1 11 square meters is required Two 2 openings measuring 2 feet x 3 feet 0 61 meters x 0 91 meters 6 square feet 0 56 square meters are acceptable Allowances must be made fo...

Страница 12: ...ent 10 for each additional 20 feet 6 1 meters Each 90º elbow is equivalent to an additional 15 feet 4 57 meters and each 45º elbow an additional 10 feet 3 05 meters The ductwork should be smooth inside with no projections from sheet metal screws or other obstructions which will collect lint When adding ducts the duct to be added should overlap the duct to which it is to be connected Also inspectio...

Страница 13: ...eet 6 1 meters The diameter of a round exhaust should be increased 10 percent 10 for each additional 20 feet 6 1 meters Each 90º elbow is equivalent to an additional 15 feet 4 57 meters and each 45º elbow an additional 10 feet 3 05 meters NOTE It is recommended that no more than four 4 dryers be connected to the same exhaust duct It is suggested that the use of 90º turns be avoided use 30º or 45º ...

Страница 14: ...Electrical Service for Gas Dryers AWG Stranded Wire Type size wire as per National Electrical Code or local codes 2 Pole circuit breaker is required IMPORTANT The dryer must be connected to the electrical supply shown on the data label located on the inside of the control door In the case of 208 or 230 volts the supply voltage must match the electrical service specifications of the data label exac...

Страница 15: ...applicable Canada Standards Canadian Electrical Codes Parts 1 2 CSA C22 1 1990 or LATEST EDITION The ground connection may be to a proven earth ground at the location service panel For added personal safety when possible it is suggested that a separate ground wire sized per local codes be connected from the ground connection of the dryer to a grounded cold water pipe DO NOT ground to a gas pipe Th...

Страница 16: ...it servicing each dryer be provided b 3 Phase 3ø Gas Dryers For dryers manufactured for operation at 3 phase 3ø the electrical connections are made at the top rear Providing local codes permit power to the dryer can be made by the use of a flexible U L listed cord pigtail wire size must conform to the rating of the dryer or the dryer can be hard wired directly to the service breaker The power supp...

Страница 17: ...pply The gas dryer installation must meet the American National Standard National Fuel Gas Code ANSI Z223 1 LATEST EDITION or in Canada the Canadian Installation Codes CAN CGA B149 1 M91 Natural Gas or CAN CGA B149 2 M91 Liquid Propane L P Gas or LATEST EDITION as well as local codes and ordinances and must be done by a qualified professional NOTE Undersized gas piping will result in ignition prob...

Страница 18: ...ignition system Consistent gas pressure is essential atALL gas connections It is recommendedthat a 3 4 inch 19 05 mm pipe gas loop be installed in the supply line servicing the bank of dryers An in line pressure regulatormust be installed in the gas supply line header if the natural gas line pressure exceeds 12 0 inches 29 9 mb water column pressure IMPORTANT For natural gas a water column pressur...

Страница 19: ...ure regulator or means of regulation built into the dryer Regulation must be provided at the gas supply L P tank or in the case where another gas appliance of a higher required gas pressure is on the same supply line separate regulators vented to the outdoors servicing each dryershould be provided ...

Страница 20: ...PARATION FOR OPERATION The following items should be checked before attempting to operate the dryer 1 Read and follow ALL CAUTION W ARNING and DIRECTION labels attached to the dryer 2 Check incoming supply voltage to be sure that it is the same as indicated on the dryer data label located on the rear side of the control door NOTE 208 volts is not the same as 230 volts 3 Check to assure that the dr...

Страница 21: ...as valve pressure tap of ALL dryers to assure that water column W C pressure is correct and consistent NOTE Water column pressure requirements measured at the gas valve pressure tap Natural Gas 4 0 inches 9 9 mb water column 3 1 2 manifold Liquid Propane L P Gas 11 0 inches 27 4 mb water column 10 manifold 8 If computer program changes are required refer to the computer programming manual which wa...

Страница 22: ...mined from experience at each location Maximum operating efficiency is dependent upon proper air circulation The accumulation of lint can restrict this airflow If the guidelines in this section are met an ADC dryer will provide many years of efficient trouble free and most importantly safe operation WARNING LINT FROM MOST FABRICS IS HIGHLY COMBUSTIBLE THE ACCUMULATION OF LINT CAN CREATE A POTENTIA...

Страница 23: ...exhaust ductwork can create a potential fire hazard NOTE A back draft damper that is sticking partially closed can result in slow drying and shutdown of the heat circuit safety switches or thermostats B ADJUSTMENTS 7 DAYSAFTER INSTALLATIONAND EVERY 6 MONTHS Inspect bolts nuts screws nonpermanent gas connections unions orifices etc electrical terminals and grounding connections 6 MONTHS Motor and d...

Страница 24: ...ADC 112115 1 1 90 2500 2 06 27 95 100 3 9 28 00 25 4 01 15 02 25 ...

Отзывы: