background image

 

3

 
An optional condensate pump kit may be installed if a 
lift is required to dispose of the condensate. The cond-
ensate pump kit can be ordered direct from the factory. 
See the optional parts list for information on the kit. 

 
2.4 Ducting

 

 

2.4A Installing Duct Collars 

 

The DHV-150H is equipped with 10” and 6” round inlet 
collars and a 10” round exhaust collar. The 10” and 6” 
round inlet collars are designed with tabs that fold 
inside the filter enclosure of the DHV-150H. The 10” 
round exhaust collar is attached to the DHV-150H by 
folding the tabs inside the end panel of the DHV-150H. 
 

2.4B Ducting for Dehumidification 

 

For the ideal installation, draw air from the central part 
of the home and return it to the isolated areas of the 
home like the bedrooms, den, utility room, or family 
room. The ductwork of the existing heating system can 
be used to supply air to the home. If the existing supply 
goes to isolated areas of the home, discharge the 
supply of the DHV-150H into the supply of the existing 
heating system. If the existing heating system 
incorporates a central supply, installation of a separate 
supply duct from the DHV-150H to each isolated area is 
recommended. DO NOT draw air directly from the 
kitchen, laundry, or isolated basement. You may draw 
air from a basement that is open to the home. All 
flexible ducting connected to the DHV-150H should be 
UL listed. 
 
The inlet of the DHV-150H is the 10” diameter hole in 
the filter enclosure of the unit. A 10” round collar is 
supplied with the unit to attach to round duct. The duct 
may be permanently attached to the collar. A 6” round 
collar is provided with the unit to attach to the 6” hole in 
the filter enclosure. The 6” collar should be capped if 
fresh make-up air is not desired. If fresh make-up air is 
desired see section 2.4C. 
 
The outlet of the DHV-150H is located on the end of the 
unit. A second 10” round collar is supplied with the unit. 
Cut and remove the safety grid, then bend the tabs on 
the collar inside the hole in the cabinet end. 
 
A length of 10 feet or more of acoustical flex ducting on 
the outlet of the DHV-150H will reduce air noise from 
the fan. A length of flexible ducting on all DHV-150H 
duct connections is recommended to reduce noise and 
vibration transmitted to rigid ductwork in the structure. 
 

Ducting the DHV-150H as mentioned in sections 2.4A-
2.4G requires consideration of the following points: 
 

Duct Sizing:

 For total duct lengths up to 25', use a 

minimum 10" diameter round or equivalent rectangular. 
For longer lengths, use a minimum 12" diameter or 
equivalent. Grills or diffusers on the duct ends must not 
excessively restrict airflow. 
 

Isolated Areas:

 Effective dehumidification may require 

that ducting be branched to isolated, stagnant areas. Use 
8" or larger diameter branch ducting to each of two or 
three areas, use 6" or larger to each of four or more 
areas. 
 

Connecting to existing HVAC systems:

 An optional 

10" check damper is available from the factory to prevent 
reverse flow through the DHV-150H. If the DHV-150H is 
ducted to the supply of a high static air handler the check 
damper may be placed in the DHV-150H supply duct. 
 

2.4C Ducting for Fresh Air 

 

Fresh air can be brought into the structure by 
connecting a insulated duct from outside to the 6” DHV-
150H inlet and by turning on the fan switch or activating 
the humidity control (on units with the humidity control 
panel). Activate the ventilation timer on units with the 
ventilating & humidity control panel to bring in fresh air. 
Refer to section 3.5 for programming instructions for 
the ventilation timer. Advantages of this form of 
ventilation include: 
 
1.  Outside air is filtered before entering the building. 
2.  Outside air will be dehumidified before entering if 

the DHV-150H is running in dehumidification mode. 

3.  Drawing air from outside and blowing inside aids in 

slightly pressurizing the structure. This helps 
prevent dirty and humid air from entering elsewhere. 
It also reduces the potential for carcinogenic radon 
gas to enter and provides make-up air for open 
combustion and exhaust devices like the clothes 
drier, fireplace, and water heater. 

4.  The need for an alternate ventilation device may be 

eliminated. 

 
In cold climates or areas where the outdoor dew point is 
low at times, ventilation can be used to dehumidify the 
structure.  This approach is often more economical than 
running the dehumidifier to remove excess moisture 
from the structure. For example, in a house that 
experiences condensation on the interior surface of the 
windows during the winter, increasing the amount of 
ventilation will often cure the problem. 
 
An insulated 6" diameter duct is generally sufficient to 
provide up to 150 CFM of outside air. Large quantities 
of outside air will impact DHV-150H performance 

Содержание DHV-150H

Страница 1: ...er 13 5 8 Defrost Thermostat 13 5 9 Electric Ventilation Damper 13 5 10 Low Pressure Control 13 5 11 Condensate Pump Kit 13 6 Electrical Schematic 14 7 Pictorial Electrical Diagram 15 8 Service Parts List 16 9 The DHV 150H 16 10 Optional Parts List 17 11 Accessories 17 12 Warranty Terms 18 Serial No ________________________________ Purchase Date ____________________________ Dealer s Name _________...

Страница 2: ...mmon grounded outlet on a 15 or 20 Amp circuit It draws around 12 Amps under normal operating conditions If used in a wet area pool spa room or basement prone to flooding a ground fault interrupter protected circuit is required Install the remote control panel in a central area of the structure where it will sense the relative humidity of the structure accurately Avoid installing the control panel...

Страница 3: ...tructure Ducting the DHV 150H as mentioned in sections 2 4A 2 4G requires consideration of the following points Duct Sizing For total duct lengths up to 25 use a minimum 10 diameter round or equivalent rectangular For longer lengths use a minimum 12 diameter or equivalent Grills or diffusers on the duct ends must not excessively restrict airflow Isolated Areas Effective dehumidification may requir...

Страница 4: ...0H in a central area of the structure Duct the supply of the DHV 150H to a 10 x 10 x 10 tee damper that is 30 open to the crawl space if desired Duct the other side of the tee to the air supply of the existing HVAC system Connect an insulated duct from outside to the 6 collar of the DHV 150H if you wish to provide optional fresh make up air 2 4F Installation in an Attic with an Existing Forced Air...

Страница 5: ... the support can easily be removed Cut the strips of metal on each end and remove the support section from the cabinet This will prevent the compressor from transmitting vibration to the cabinet Make sure none of the compressor tubes are pressed against the cabinet or access panel Check that the compressor tubes are centered in the holes where they pass through the drain pan A length of 10 feet or...

Страница 6: ...6 Figure 1 DHV 150H in a Basement With a Forced Air System Incorporating a Central Return Figure 2 DHV 150H in an Attic with a Forced Air System Incorporating a Central Return ...

Страница 7: ...r within the living space for accurate humidity sensing 3 3 Humidity Control Adjustment Set the humidity control to the desired humidity level for the home The dehumidifier will run continuously until the relative humidity RH is reduced to the humidity control dial setting Setting the humidity control to lower RH levels will NOT increase the unit s dehumidification rate the unit will simply run lo...

Страница 8: ...lation Now with the ventilation start time set press the I O button The word OFF should appear to the right of the time and the number 1 should remain in the lower right hand corner of the display The 1 and OFF signify the turn off time for the first program Set the turn off time using the 1 7 h and m buttons in the same way as described above and continue on to the second through sixth programs W...

Страница 9: ...times before the high efficiency filter requires replacement Be careful not to damage the fabric media when handling the high efficiency pleated paper filter Do not attempt to clean the high efficiency pleated paper filter It should be replaced when it becomes restrictive See Figure 7 4 3 Optional Fresh Air Return Check and clean the screen on the outdoor fresh air return seasonally The screen may...

Страница 10: ...on prevents fan impeller rotation 3 Defective fan 4 Defective fan relay 5 Defective fan capacitor Fan runs with fan switch ON Fan does not run with ventilation timer activated 1 Ventilation timer set to manual switched OFF 2 Time not correct on ventilation timer 3 Defective ventilation timer 4 Defective fan switch Evaporator coil frosted continuously low dehumidifying capacity 1 Dirty air filter s...

Страница 11: ...110 volts from compressor terminal R to overload terminal 3 using an AC voltmeter If voltage is present go to step 3 If no voltage there may be a loose connection in the compressor circuit Test each component for continuity See the appropriate section if a defect is suspected 3 Unplug the unit and then disconnect the red and yellow wires from compressor terminals R S Using an ohmmeter check contin...

Страница 12: ...l hole from becoming plugged A standing burn out does not require a suction line filter drier 7 Evacuate the system with a good vacuum pump and accurate vacuum gauge Leave the pump on the system for at least an hour 8 Operate the system for a short period of time monitoring the suction pressure to determine that the suction filter is not becoming plugged Replace the suction filter drier if pressur...

Страница 13: ...ventilating the structure when the unit is dehumidifying or recirculating the indoor air The electric ventilation timer operates on 24 Vac from the control circuit DO NOT connect high voltage to the damper motor or damage to the motor may result DO NOT force the blade of the damper by hand or damage to the damper motor may result If the electric ventilation damper fails to operate 1 Check that the...

Страница 14: ...14 Figure 4 Electric Schematics of the DHV 150H ...

Страница 15: ...15 Figure 5 Pictorial Electrical Diagrams of DHV 150H ...

Страница 16: ...r 30 MFD 7 4022563 1 Condenser Coil 8 4021470 1 Defrost Thermostat 4021648 1 Defrost Thermostat Mounting Clip item 8 not shown 9 4022563 1 Evaporator Coil 10 4024270 1 Fan 11 4020924 1 Fan Relay SPDT 24 Vac 15A 12 4024360 1 Fan Run Capacitor 16MFD 13 4022593 1 Filter Drier 14 4021626 1 Hose Drain Pan 56 ID x 8 15 4023875 1 Inlet Collar 10 Galvanized Steel 16 4023928 1 Inlet Collar 6 Galvanized Ste...

Страница 17: ...t Damper 6 Diameter Electrically Actuated not shown 32 4024153 1 Cover for Items 28 29 not shown 33 4021495 1 Knob Black 25 shaft 34 4024150 1 Instructions Humidity Fan not shown 35 4024122 1 Instructions Ventilation Timer Humidity not shown 36 4020554 1 Switch Black SPDT ON OFF 37 4022486 1 Timer 7 Day 24 Vac Programmable 38 AL99982 1 Optional External Insulation Kit not shown 39 AL22023 1 6 Vent...

Страница 18: ...r cause beyond American ALDES Ventilation Corporation s reasonable control Limitations and Exclusions If any American ALDES Dehumifier Dehumidifying Ventilator part is repaired or replaced the new part shall be warranted for only the remainder of the original warranty period applicable thereto All warranty periods shall be extended by the period of time if any that the unit is out of service while...

Страница 19: ...19 Date Service Notes ...

Отзывы: