background image

INSPECTION RECORD 
Model No: _____________________ 
Serial No: _____________________ 
Mfg. Date: _____________________ 
Date Installed New: _____________ 

INSPECTION should be performed monthly or 
more frequently if circumstances dictate.  The 
extinguisher should be checked to see that it is 
not damaged, the discharge outlet is not 
blocked, that it is fully charged, the seal is not 
broken and that the operating instructions are 
clearly visible. 

 

ANNUAL MAINTENANCE is a more complete 
inspection of the extinguisher and should be 
done professionally.  It will reveal the need for 
hydrotesting which must be done on Water 
Mist, Water, Wet Chemical, Foam and Carbon 
Dioxide every FIVE YEARS

 

and Dry Chemical, 

Dry Powder, Halotron I and Halon 1211 
extinguishers every TWELVE YEARS. Most 
local authorities require special tags be 
attached to the extinguisher to verify this 
service. 

 

SIX YEAR MAINTENANCE – Every six years 
extinguishers requiring a 12 year hydrotest 
shall be emptied and subject to thorough 
examination of mechanical parts, extinguishing 
agent and expelling means.  When applicable 
maintenance procedures are done during 
periodic recharging or hydrotesting, the six 
year requirement will begin from that date. 

 

RECHARGE should be done professionally 
immediately after any use by your local 
Amerex Distributor who has the trained 
personnel, extinguishing agents and equipment 
to do it properly.  This extinguisher must be 
recharged with the extinguishing agent 
specified on the nameplate. Substitutions could 
cause damage or injury 

and will void the 

warranty. 

DISTRIBUTED BY:  

INSTALLATION & DISTRIBUTION 

Install, inspect, maintain and test your fire extinguisher 
in accordance with the National Fire Protection Assoc. 
Standard 10 “‘Portable Fire Extinguishers”. 
Your fire extinguisher should be mounted in a clean dry 
area, accessible to possible fire hazards and preferably 
near an exit.  Mount it so that the top is from 3 ½ to 5 
feet above the floor and out of the reach of small 
children. 
Use the mounting bracket furnished with the 
extinguisher or an approved Amerex vehicle bracket if 
required.  Fasten to a solid surface using strong screws 
or fasteners (not included). 

Follow the Mounting Instructions below, 
particularly in public areas where the 
extinguisher might be accidentally dislodged 
from the bracket or have objects placed on it.

MOUNTING INSTRUCTIONS 

UL specifies that a hanging device must withstand a 
vertical force of five times the weight of the charged 
extinguisher but not less than 100 pounds.  The  
extinguisher bracket should be mounted as follows: 

Walls where 2"x4" studs can be found – ALL 
SIZES

:  Mount wall hanger bracket securely to stud 

using two #10 x 1¼" long wood screws through the 
diagonal smaller holes in the bracket. 

Sheetrock – ALL SIZES

:  Mount a ¾" thick board to 

the wall using 3/16" toggle bolts – height and width of 
the board is dependent on extinguisher size.  The 
board should extend a minimum of two inches beyond 
all sides of the extinguisher profile (excluding hose 
and horn).  Mount wall hanger bracket to board using 
two #10 x 1" long wood screws as above. 

Cinderblock or Cement – ALL SIZES

:  Mount wall 

hanger bracket using one ¼" toggle bolt or masonry 
lead screw expansion anchor through center hole in 
the bracket.  Mount vehicle/marine strap type brackets 
using two 3/16" toggle bolts or #10 lead screw  
expansion anchors. 

Concrete or Tile Wall

 – ALL SIZES – Mount wall 

hanger bracket using one ¼" masonry lead screw 
expansion anchor through center hole in wall bracket.  
Mount vehicle/marine strap type brackets using two 
No. 10 masonry lead screw expansion anchors. 

Steel Posts or Beams – ALL SIZES

:  Special tools 

and fasteners are required – have extinguisher  
mounted by a professional fire extinguisher service 
company. 

Tile Walls

:  Locate in joint.

 

INSPECTION 

Your extinguisher should be inspected monthly, 
checking for any possible damage, corrosion,  
leakage or obstructions in the discharge outlet. The 
tamper seal should be unbroken.  The extinguisher 
should be cleaned so that the instructions on the 
label are always clearly visible. 

Carbon Dioxide

 extinguishers should be weighed 

and the weight verified to be within the tolerances 
specified on the nameplate (label). 

Water Mist, Water, Wet Chemical, Foam, Dry 
Chemical, 

Dry Powder,

 Halotron I and Halon 1211

 

extinguisher pressure gauges should be checked.  
The indicator will vary slightly due to temperature, but 
should always be in the GREEN area if it is fully 
pressurized.  Heft or weigh the extinguisher to  
determine fullness. 

IN CASE OF FIRE 

1. Have everyone evacuate the area immediately.
2. Call the Fire Department even if the fire appears to 
be small (small fires quickly become LARGE fires).
The Fire Dept. phone number should be posted at
every phone. 
3. Use your extinguisher properly, according to the
instructions on the nameplate and in this manual.  A
large fire should be fought by professionals. Be pre-
pared to leave the area if the fire cannot be 
immediately controlled. 

HOW TO USE 

NOTE:  The following instructions are of a 
general nature, intended to familiarize the 
user with the basic operating techniques of 
Amerex hand portable extinguishers.  

All 

operate by removing the ring (safety) 
pin and squeezing the handles together.

  

Since extinguishers differ, the extinguisher 
nameplate must be consulted for specific 
procedures and starting distances. 
1.

Hold the extinguisher upright and pull
the ring (safety) pin breaking the plas-
tic seal.

2.

Stand back from the fire (the minimum
distance stated on the nameplate) and
aim at the base of the fire nearest you.

3.

Keeping the extinguisher upright,
squeeze the handles together to dis-
charge and sweep from side to side.
Move closer as the fire is extinguished
but not so close as to scatter the burn-
ing material or liquid.

4.

When the fire is out, back away while
watching for possible re-ignition.

5.

Evacuate and ventilate the area im-
mediately after use.  The fumes and
smoke from any fire may be hazard-
ous and can be deadly.

NOTE: Whenever possible, protective 
clothing and breathing equipment 
should be used while fighting a fire. 

OWNER'S MANUAL 

for 

HAND PORTABLE 

Water & Water Mist 

Wet Chemical (Class K) 

AFFF & FFFP Foam 

Dry Chemical 

Dry Powder (Class D) 

Carbon Dioxide 

Halotron I 

Halon 1211 

FIRE EXTINGUISHERS 

AMEREX LIMITED WARRANTY 

Amerex warrants its fire extinguishers to be free from defects 
in material and workmanship from the date of purchase for a 
period of 6 (six) years for Dry Chemical, Dry Powder, & 
Halotron, 12 (twelve) years for High Performance, 1 (one) 
year for Halon, and 5 (five) years for CO2 and Water/Water 
Based.  During the warranty period, any such defects will be 
repaired or the defective extinguisher replaced IF ONLY 
FACTORY REPLACEMENT PARTS HAVE BEEN USED TO 
SERVICE THE EXTINGUISHER.  This warranty does not 
cover defects resulting from modification, alteration, misuse, 
exposure to corrosive conditions, improper installation or 
maintenance. 
ALL IMPLIED WARRANTIES, INCLUDING BUT NOT LIM-
ITED TO, WARRANTIES OF FITNESS FOR PURPOSE 
AND MERCHANTABILITY, ARE LIMITED TO THE TIME 
PERIODS STATED ABOVE.  IN NO EVENT SHALL 
AMEREX CORP. BE LIABLE TO INCIDENTAL OR CONSE-
QUENTIAL DAMAGES. 
Some states do not allow limitations on how long an implied 
warranty lasts or the exclusion or limitation of incidental or 
consequential damages, so the above limitations or exclu-
sions may not apply to you.  Amerex Corp. neither assumes 
nor authorizes any representative or other person to assume 
for it, any obligation or liability other than expressly set forth 
herein.  This warranty gives you specific legal right and you 
may have other rights, which vary from state to state.  To 
obtain performance of the obligation of this warranty, write to 
Amerex Corp.,P. O. Box 81, Trussville, AL  35173-0081 for 
instructions. 

AMEREX CORPORATION 

P.O. BOX 81 

TRUSSVILLE, AL,  35173-0081 

Phone:  (205) 655-3271  Fax:  1-800-654-5980 

e-mail:  

[email protected]

 

web page:  

www.amerex-fire.com

 

Printed in U.S.A.

     P.N. 00914A’ REV 12/15 

1. HOLD EXTINGUISHER UPRIGHT AND 
PULL THE RING (SAFETY) PIN 

2.  STAND BACK FROM THE FIRE AND AIM 
AT THE BASE OF THE FIRE NEAREST YOU 

3.  SQUEEZE HANDLES TOGETHER & 
SWEEP THE EXTINGUISHER STREAM SIDE 
TO SIDE 

REMEMBER THIS SIMPLE WORD – 

P A S S 

P

ULL     

A

IM    

S

QUEEZE    

S

WEEP

Отзывы: