Amerex A384T Скачать руководство пользователя страница 2

 

PN 14425

 

04/2020

 

All  fire  extinguishers  shall  be  installed,  inspected,  and  maintained  in  accordance  with  the  National  Fire 

Protection  Association  standard  titled  "Portable  Fire  Extinguishers",  NFPA  10,  or  the  National  Fire  Code  of 

Canada and the requirements of local authorities having jurisdiction.

 

When  maintenance  is  indicated,  it  shall  be  performed  by  trained  persons  having  proper  equipment.  Fire 

extinguishers  are  pressure  vessels  and  must  be  treated  with  respect  and  handled  with  care.  They  are 

mechanical devices and require periodic maintenance to be sure that they are ready to operate properly and 

safely. Amerex strongly recommends that the maintenance of portable fire extinguishers be done by a trained 

professional –

 

your local authorized Amerex Distributor.

 

Amerex  Corporation  original  factory  parts  available  to  insure  proper  maintenance  –

 

USE  OF  SUBSTITUTE 

PARTS   RELEASES AMEREX OF ITS WARRANTY OBLIGATIONS. Amerex parts have machined surfaces 

and  threads,  which  are  manufactured  to  exacting  tolerances.  All  parts  meet  precise  specifications  and  are 

subjected  to  multiple  in

-

house  inspections  and  tests  for  acceptability.  There  are  substitute  parts  available, 

which  are  incorrectly  labeled  as  U/L  component  parts,  some  are  advertised  as  Amerex  type.  None  of  these 

meet  U/L  requirements,  and  all  of  them  void  the  Amerex  extinguisher  warranty  and  U/L  listing. 

DO  NOT 

SUBSTITUTE.

 

OWNER

S SERVICE MANUAL

 

INSTALLATION, OPERATING & SERVICING INSTRUCTIONS

 

MANUAL PN 14425

 

HALOTRON PORTABLE EXTINGUISHERS

 

MODELS A384T, B385TS, B386T, B394TS, 397 & 398

 

AMEREX  CORPORATION  DOES  NOT  SERVICE,  MAINTAIN,  OR  RECHARGE  FIRE  EXTINGUISHERS. 

THIS  MANUAL  IS  PUBLISHED  AS  A  GUIDE  TO  ASSIST  QUALIFIED  SERVICE  PERSONNEL  IN  THE 

INSPECTION,  MAINTENANCE,  AND  RECHARGE  OF  AMEREX  FIRE  EXTINGUISHERS  ONLY.  NO 

INSTRUCTION  MANUAL  CAN  ANTICIPATE  ALL  POSSIBLE  MALFUNCTIONS  THAT  MAY  BE 

ENCOUNTERED IN THE SERVICE OF FIRE EXTINGUISHERS. DUE TO THE POSSIBILITY THAT PRIOR 

SERVICE  PERFORMED  ON  THIS  EQUIPMENT  MAY  HAVE  BEEN  IMPROPERLY  DONE,  IT  IS 

EXTREMELY  IMPORTANT  THAT  ALL  WARNINGS,  CAUTIONS,  AND  NOTES  IN  THIS  MANUAL  BE 

CAREFULLY  OBSERVED.  FAILURE  TO  HEED THESE  INSTRUCTIONS  COULD  RESULT  IN  SERIOUS 

INJURY. AMEREX ASSUMES NO LIABILITY FOR SERVICE, MAINTENANCE, OR RECHARGE OF FIRE 

EXTINGUISHERS BY PUBLISHING THIS MANUAL.

 

RECHARGE FIRE EXTINGUISHERS IMMEDIATELY AFTER ANY USE

 

REFERENCES IN THIS MAUNUAL:                                                        

NFPA 10 

Portable Fire Extinguishers  

JJJJJJJJJJJJJJJJJJJJJJJJJJJJJJJJJJJJJJJJJJJJ            

                                                          

 

CGA C

-

Methods for Pressure Testing Compressed Gas 

Cylinders

 

CGA C

-

Standard for Visual Inspection of Steel 

Compressed Gas Cylinders. 

 

National Fire Code of Canada

 

AVAILABLE FROM:                                                                             

National Fire Protection Association, 1 Batterymarch Park, 

Quincy, MA 02169

-

7471 

 

Compressed Gas Association, 14501 George Carter Way, 

Chantilly, VA 20151

-

2923

 

Compressed Gas Association, 14501 George Carter Way, 

Chantilly, VA 20151

-

2923

 

National Research Council Canada, 1200 Montreal Road, 

Building M

-

58 Ottawa, ON K1A 0R6 Canada

 

Содержание A384T

Страница 1: ... 20 COVER SHEET DO NOT PRINT THIS PAGE FOR ACTUAL MANUAL INTERNAL USE ONLY NOTES 1 THIS COVERSHEET FOR INFORMATIONAL PURPOSES ONLY DO NOT PRINT THIS PAGE IN MANUAL 2 DESCRIPTION MANUAL OWNER S SERVICE FOR HALOTRON PORTABLE EXTINGUISHERS 3 ACTUAL PRINTED MATERIAL TO CONSIST OF ATTACHED 4 OVERALL SIZE OF PRINTED DOCUMENT PAGES 8 1 2 X 11 ON 20 LB PAPER 5 PRINTED MATERIAL TO MATCH ATTACHED IN SADDLE ...

Страница 2: ...T SUBSTITUTE OWNER S SERVICE MANUAL INSTALLATION OPERATING SERVICING INSTRUCTIONS MANUAL PN 14425 HALOTRON PORTABLE EXTINGUISHERS MODELS A384T B385TS B386T B394TS 397 398 AMEREX CORPORATION DOES NOT SERVICE MAINTAIN OR RECHARGE FIRE EXTINGUISHERS THIS MANUAL IS PUBLISHED AS A GUIDE TO ASSIST QUALIFIED SERVICE PERSONNEL IN THE INSPECTION MAINTENANCE AND RECHARGE OF AMEREX FIRE EXTINGUISHERS ONLY NO...

Страница 3: ... not more than 5 feet 1 53 m above the floor Extinguishers having a gross weight greater than 40 lbs 18 14 kg shall be installed so that the top of the extinguisher is not more than 3 feet 1 07 m above the floor All extinguishers shall be in an accessible location and near an exit Never install the extinguisher in a location where a potential hazard would prevent easy access The operational temper...

Страница 4: ...ous and can be deadly WARNING SYMPTOMS OF OVER EXPOSURE TO PURE Halotron I MAY CAUSE CENTRAL NERVOUS SYSTEM EFFECTS SUCH AS DIZZINESS DROWSINESS ANESTHESIA OR UNCONSCIOUSNESS PERSONS SUFFERING FROM OVER EXPOSURE SHALL BE IMMEDIATELY REMOVED TO AREA WITH FRESH AIR APPLY ARTIFICAL RESPIRATION IF NECESSARY CONTACT A PHYSICIAN INSPECTING THE EXTINGUISHER Extinguishers shall be INSPECTED when initially...

Страница 5: ...her for damaged missing or substitute parts Only factory replacement parts are approved for use on Amerex fire extinguishers 3 Weigh extinguisher and compare with weight printed in the Maintenance section on the nameplate Recharge extinguisher if weight is not within indicated allowable tolerances 4 Check the date of manufacture on the extinguisher nameplate Cylinder must be hydrostatically proof ...

Страница 6: ...u are recharging an extinguisher which has been partially discharged with agent remaining in the cylinder or has been recharged and the pressure leaked follow the instructions contained in the Recharging Instructions packaged with the Amerex Recharge Kit PN 14538 or with Getz Halotron recovery equipment 1 Complete items 1 through 9 in Maintenance Service Procedure above 2 Verify that there is no p...

Страница 7: ...es indicated in the maintenance section of the extinguisher nameplate 12 Install nozzle or hose and nozzle assembly 13 Install pull pin with ring facing front of the extinguisher Install new tamper seal Record recharge date and attached new recharge tag TROUBLE SHOOTING GUIDE WARNING DETERMINE THE SOURCE OF A LEAK BEFORE THE EXTINGUISHER IS DEPRESSURIZED THE EXTINGUISHER MUST BE COMPLETELY DEPRESS...

Отзывы: