Amerex 570 Скачать руководство пользователя страница 2

 

PN 08220

 

04/2020

 

All  fire  extinguishers  shall  be  installed,  inspected,  and  maintained  in  accordance  with  the  National  Fire 

Protection  Association  standard  titled  "Portable  Fire  Extinguishers",  NFPA  10,  or  the  National  Fire  Code  of 

Canada and the requirements of local authorities having jurisdiction.

 

When  maintenance  is  indicated,  it  shall  be  performed  by  trained  persons  having  proper  equipment.  Fire 

extinguishers  are  pressure  vessels  and  must  be  treated  with  respect  and  handled  with  care.  They  are 

mechanical devices and require periodic maintenance to be sure that they are ready to operate properly and 

safely. Amerex strongly recommends that the maintenance of portable fire extinguishers be done by a trained 

professional –

 

your local authorized Amerex Distributor.

 

Amerex  Corporation  makes  original  factory  parts  available  to  insure  proper  maintenance  –

 

USE  OF 

SUBSTITUTE  PARTS  RELEASES  AMEREX  OF  ITS  WARRANTY  OBLIGATIONS.  Amerex  parts  have 

machined surfaces and threads that are manufactured to exacting tolerances. O

-

rings, hoses, nozzles, horns, 

and all metal parts meet precise specifications and are subjected to multiple in

-

house inspections and tests for 

acceptability.  There  are  substitute  parts  available  that  are  incorrectly  labeled  as  UL  component  parts,  some 

are  advertised  as  Amerex  type.  None  of  these  meet  UL  requirements  and  all  of  them  void  the  Amerex 

extinguisher warranty and UL listing. DO NOT SUBSTITUTE

 

RECHARGE FIRE EXTINGUISHERS IMMEDIATELY AFTER ANY USE

 

OWNER

S SERVICE MANUAL

 

INSTALLATION, OPERATING & SERVICING INSTRUCTIONS

 

MANUAL PN 08220

 

CLASS

-

D PORTABLE EXTINGUISHER 

 

MODEL B570

 

AMEREX  CORPORATION  DOES  NOT  SERVICE,  MAINTAIN,  OR  RECHARGE  FIRE  EXTINGUISHERS. 
THIS  MANUAL  IS  PUBLISHED  AS  A  GUIDE  TO  ASSIST  QUALIFIED  SERVICE  PERSONNEL  IN  THE 
INSPECTION,  MAINTENANCE,  AND  RECHARGE  OF  AMEREX  FIRE  EXTINGUISHERS  ONLY.  NO 
INSTRUCTION  MANUAL  CAN  ANTICIPATE  ALL  POSSIBLE  MALFUNCTIONS  THAT  MAY  BE 
ENCOUNTERED IN THE SERVICE OF FIRE EXTINGUISHERS. DUE TO THE POSSIBILITY THAT PRIOR 
SERVICE  PERFORMED  ON  THIS  EQUIPMENT  MAY  HAVE  BEEN  IMPROPERLY  DONE,  IT  IS 
EXTREMELY  IMPORTANT  THAT  ALL  WARNINGS,  CAUTIONS,  AND  NOTES  IN  THIS  MANUAL  BE 
CAREFULLY  OBSERVED.  FAILURE  TO  HEED  THESE  INSTRUCTIONS  COULD  RESULT  IN  SERIOUS 
INJURY. AMEREX ASSUMES NO LIABILITY FOR SERVICE, MAINTENANCE, OR RECHARGE OF FIRE 
EXTINGUISHERS BY PUBLISHING THIS MANUAL. 

 

AMEREX CORPORATION –

 

P.O. BOX 81 –

 

TRUSSVILLE, ALABAMA  35173

-

0081

 

Phone:  205/655

-

3271     Fax:  800/654

-

5980

 

e

-

mail:  

sales@amerex

-

fire.com

      Web Page:  

http://www.amerex

-

fire.com

 

REFERENCES IN THIS MAUNUAL:                                                        

NFPA 10 

Portable Fire Extinguishers  

JJJJJJJJJJJJJJJJJJJJJJJJJJJJJJJJJJJJJJJJJJJJ            

                                                          

 

CGA C

-

Methods for Pressure Testing Compressed Gas 

Cylinders

 

CGA C

-

Standard for Visual Inspection of Steel 

Compressed Gas Cylinders. 

 

National Fire Code of Canada

 

AVAILABLE FROM:                                                                             

National Fire Protection Association, 1 Batterymarch Park, 

Quincy, MA 02169

-

7471 

 

Compressed Gas Association, 14501 George Carter Way, 

Chantilly, VA 20151

-

2923

 

Compressed Gas Association, 14501 George Carter Way, 

Chantilly, VA 20151

-

2923

 

National Research Council Canada, 1200 Montreal Road, 

Building M

-

58 Ottawa, ON K1A 0R6 Canada

 

Содержание 570

Страница 1: ...EREX CORPORATION IT SHALL NOT BE DUPLICATED USED OR DISCLOSED TO OTHERS WITHOUT THE EXPRESS WRITTEN CONSENT NOTES 1 THIS COVERSHEET FOR INFORMATIONAL PURPOSES ONLY DO NOT PRINT THIS PAGE IN MANUAL 2 DESCRIPTION MANUAL OWNER S SERVICE FOR MODEL B570 PORTABLE EXTINGUISHER 3 ACTUAL PRINTED MATERIAL TO CONSIST OF ATTACHED 4 OVERALL SIZE OF PRINTED DOCUMENT PAGES 8 1 2 X 11 ON 20 LB PAPER 5 PRINTED MAT...

Страница 2: ...EDIATELY AFTER ANY USE OWNER S SERVICE MANUAL INSTALLATION OPERATING SERVICING INSTRUCTIONS MANUAL PN 08220 CLASS D PORTABLE EXTINGUISHER MODEL B570 AMEREX CORPORATION DOES NOT SERVICE MAINTAIN OR RECHARGE FIRE EXTINGUISHERS THIS MANUAL IS PUBLISHED AS A GUIDE TO ASSIST QUALIFIED SERVICE PERSONNEL IN THE INSPECTION MAINTENANCE AND RECHARGE OF AMEREX FIRE EXTINGUISHERS ONLY NO INSTRUCTION MANUAL CA...

Страница 3: ... applicable standards of Factory Mutual to ANSI UL 711 and ANSI UL 299 It also complies with industry standards as presented in the National Fire Protection Association Standard No 10 Standard for Portable Fire Extinguishers WARNINGS USE THIS EXTINGUISHER ONLY ON CLASS D BURNING METALS CLASS D FIRES NORMALLY GENERATE EXTREMELY HIGH HEAT AMEREX RECOMMENDS THE USE OF PROTECTIVE CLOTHING AND SELF CON...

Страница 4: ...ess than 50 feet 15 m from the hazard leaving unobstructed access Avoid placing it in an extremely hot or cold place The operational temperature range is 40 F to 120 F 40 C to 49 C Adequately protect the extinguisher if temperatures outside this range are anticipated Keep the extinguisher clean and free from dirt ice chemicals and any contaminants that may interfere with its proper operation DO NO...

Страница 5: ...ob the chemical onto the fire Be careful not to spread the fire surface when using this technique 4 Reapply powder to visible hot spots 5 To avoid re ignition allow metal to cool before cleanup 6 Evacuate and ventilate the area immediately after use The fumes and smoke from any fire may be hazardous and can be deadly INSPECTION INSPECTION NFPA 10 is a quick check intended to give reasonable assura...

Страница 6: ...late label Recharge extinguisher if weight is not within indicated allowable tolerances see instructions in Recharge Procedure 4 Check the date of manufacture stamped on the bottom of the extinguisher or nameplate for model B570 and on the wall hanger loop for Model 570 Cylinder must be hydrostatically proof pressure tested every 12 years to the test pressure indicated on the nameplate 585 psi 403...

Страница 7: ...available 4 Use a regulated pressurizing source of ARGON ONLY Set the regulator to no more than 220 psi 1520 kPa 5 Check and calibrate regulator gauge at frequent intervals The regulator gauge shall be used to determine when the intended charging pressure has been reached Do not use the extinguisher gauge for this purpose 6 Never leave an extinguisher connected to a regulator of a high pressure so...

Страница 8: ... fluid or a solution of soapy water to the valve discharge orifice around the collar O ring sealing area cylinder welds and gauge Remove leak detecting fluid from valve assembly by blowing out with air or argon Wipe exterior of extinguisher to remove any remaining residue 11 Install the hose assembly to the operating valve Reconnect the female swivel on the extension applicator to the male swivel ...

Страница 9: ...ROBLEM CORRECTIVE ACTION 1 Leak at operating valve col lar O ring Remove valve assemble clean collar thoroughly and install new collar O ring Lubricate with Bluestar V 711 2 Leak through valve Install new valve stem assembly Check valve seat scratches or foreign matter Install new valve stem assembly 3 Leak around gauge thread Remove gauge and reinstall using Teflon tape on the gauge threads 4 Def...

Отзывы: