3
Fig. 1c
Tamper indicating detachment from the wall
Caution! The proper indication of detachment from the wall requires screwing the additional screw to the
mounting base, which will result in closing the tamper switch once the signaling device is mounted on the
wall.
Fig. 2 The printed circuit board of the signaling device
Power supply of the signaling device is supplied to the „+” and „-” terminals.
The signaling device can operate with or without the 12V/2,2Ah battery. The battery should be connected to
the „-BAT+” socket
Caution! During battery operation, the power supply voltage should be between 13V and 13.8V to ensure
proper charging process.
The TAMPER switches are used to connect the device to the tamper circuit of the alarm system. The tamper
circuit indicates outer enclosure opening (tamper 1) and detachment from the wall (tamper 2).