AMC 1ACOs Скачать руководство пользователя страница 30

AMC-1ACOs One Channel CO Monitor with DSI 

 

 26  

S1 

Provides a voltage representation of the gas concentration reported on channel 1
Measure between GND (TP4) and S1 (TP2) 
Range: Minimum 0.4V 

No target (0 ppm) gas measured, 4 mA on 4-20 mA input 

Range: Maximum 2V  

High gas concentration measured, 20 ma on 4-20 mA input 

GND  Reference ground, used with VFD (TP1), S1 (TP2) and S2 (TP3) 

 



  On Site Calibration Equipment Required 

  Digital multi-meter with a minimum display range of 0 to 10.0 VDC. 

  Miniature screwdriver or trimmer adjustment tool. 

  Calibration adapter, available from AMC 

  Zero and Span gases (Contact AMC for information) 



 Calibration 

Procedure 

5.2.2.2.1 

On Board Sensors

 

Calibration of the gas sensor involves two steps. First the “zero” must be set and then the 
“span” must be calibrated. 
 

Note: 
The calibration procedure will cause false alarms and or fail signal. Appropriate 
precautions may be required. 

 
Refer to the Figure 10 for DSI Layout, to perform the following calibration procedure: 

1.  Open the front cover on the AMC-1ACOs enclosure. 
2.  Attach the multi-meter as shown in Figure 12. 

  Connect negative (black) lead to TP22 (main board) 

  Connect positive (red) lead to TP4 (main board) 

  To set the zero and span specifically the measurements must be taken on the 

DSI board by connecting negative (black) lead to TP4 (GND) and connecting 
positive (red) lead to TP2 (S1) 

  Refer to Section 5.2.1.2 for trip threshold adjustment  

3.  Apply a Zero gas sample, with a calibration adapter cup firmly and completely 

over the sensor on the AMC-DSI for 2 minutes with a flow rate of .5 liters per 
minute. 

4.  At 2 minutes adjust the Zero trimmer VR5 (DSI board) for a reading of 0.4 V +/- 

5mV.  

5.  Apply the Span gas sample, with a calibration adapter cup firmly and completely 

over the sensor on the AMC-DSI for 2 minutes with a flow rate of .5 liters per 
minute. Since the output range is 0.4 to 2.0 V, a full-scale concentration should 
register 2.0 V after a 2 minute exposure.  Proportionately, a half-scale 
concentration of gas should register 1.2 V, and so on. 
V span adjust = ((Gas used / Full scale) x 1.6VDC) + 0.4 VDC. 

6.  At 2 minutes adjust the Span trimmer VR3 (DSI board) for the appropriate the 

Span voltage reading. 

Содержание 1ACOs

Страница 1: ...llation and operating instructions completely and carefully before starting Filename 3221405B doc Copyright November 2012 AMC The Armstrong Monitoring Corporation 215 Colonnade Road South Ottawa Ontar...

Страница 2: ......

Страница 3: ...TION AND CALIBRATION 15 5 1 OPERATION 15 5 1 1 DIP SWITCH PROGRAMMING 15 5 1 2 ALARM RELAY PROGRAMMING 17 5 1 3 AUDIO ALARMS 17 5 1 4 GAS MONITOR INTERFACE CONFIGURATION 18 5 1 5 DSI INTERFACE CONFIGU...

Страница 4: ...onitor signal input configuration jumpers 18 FIGURE 10 DSI Layout 19 FIGURE 11 AMC 1ACOs Test Points and Trimpots 23 FIGURE 12 AMC 1ACOs Test Points and Trimpots 25 LIST OF TABLES TABLE 1 Building Aut...

Страница 5: ...ease call 1 800 465 5777 1 2 LIABILITY All AMC products must be installed and maintained according to instructions Only qualified personnel should install and maintain the equipment AMC shall have no...

Страница 6: ...77 or through contacts at www armstrongmonitoring com or through email directly at support armstrongmonitoring com 1 5 MODIFICATIONS AND SUBSTITUTIONS Due to an ongoing development program AMC reserve...

Страница 7: ...1A Gas Monitor Gas Concentration Gas Concentration is measured PPM PPM Parts Per Million 1 volume 10 000PPM Span Full range of a sensor i e a CO sensor with a full scale of 0 100 PPM has a 100 PPM sp...

Страница 8: ...ng Pressure Ambient atmospheric pressure Relative Humidity 0 95 non condensing Alarm Trip Points Signal Input Configuration Part No Serial No Type of Gas Warning Alarm Full Scale On board Ch1 91AM CO...

Страница 9: ...arm concentrations are indicated in Section 2 4 POWER TERMINAL BLOCK For line voltage connections of 120 VAC 60 Hz 5 TRANSFORMER A step down transformer powers the internal circuitry and remote sensor...

Страница 10: ...oard CO sensor signal in and a 4 20mA signal out 14 ON BOARD CO SENSOR Sensor allows local detection of CO gas 15 SIGNAL INPUT OUTPUT TERMINAL BLOCK 1 2 3 4 5 6 Allows connection to transmitter input...

Страница 11: ...R PCB 11 PROGRAMMING DIP SWITCHES 8 RELAY SETUP JUMPERS 6 INTERNAL WIRING HEADER 4 POWER TERMINAL 14 ON BOARD CO SENSOR 15 SIGNAL INPUT OUTPUT TERMINAL BLOCK 12 RELAYS BLOCK RV6 RV5 TP6 TP5 TP4 Sensor...

Страница 12: ...or water spray Install in an area where the local concentration of gas is unaffected by the presence of ventilation systems and away from sources of interference gases Mount the monitor where the uni...

Страница 13: ...th the monitor Ice Cube DPDT relays are used Two of the relays are set for different alarm conditions and the optional third relay is a Fault relay The contacts are rated for 10Amps 250VAC resistive F...

Страница 14: ...1ACOs One Channel CO Monitor with DSI 10 AC PRIMARY 120 VAC 60 Hz NEUT HOT CHASSIS GND RV6 RV5 TP6 TP5 TP4 Sensor 1 TP22 GND RV4 CHANNEL 1 SENSOR CHANNEL 1 FIGURE 4 Location of Power Supply Connectio...

Страница 15: ...conduit cable shield must be grounded at the monitor For basic selection of cable size and length between monitor and BAS it is recommended to use 20 16AWG wire on a distance no longer than 2500 4 2 3...

Страница 16: ...installation hold the sensor in such a way that the sensing area is not covered Align the sensor pins with pin sockets on the DSI and lightly push the sensor on to the DSI Sensors need to be calibrate...

Страница 17: ...4 20mA in Positive Not applicable 4 20mA signal input 4 20mA in Not applicable Chassis ground CGND Connect to shield of cable CGND Signal ground Not applicable NOTE MAXIMUM LOAD RESISTANCE IS 500 OHMS...

Страница 18: ...external power is wired through J4 while the optional additional transformer is factory installed through J2 Figure 8 shows a detail description of the VFD connector J4 When the additional transforme...

Страница 19: ...Alarms until Acknowledge Latching Relays ON Once activated warning and alarm relays remain activated latched until activation condition has been removed minimum run timer has expired and the Acknowled...

Страница 20: ...l Alarm relay may be activated as a result of fault detection on either channel see SW2 1 SW1 8 Enable One group of Relays ON Only the first group of relays Warning J2 2 and Alarm J2 3 and Fault J2 4...

Страница 21: ...mally de energized with the jumper straps identified in Table 3 WARNING and ALARM Relay Active State and shown in Figure 2 item 8 Typically the normally de energized position is employed activating th...

Страница 22: ...poses as the jumpers must be strapped as indicated in Table 5 Note V equals 22 volts TABLE 5 Signal input configuration jumper selection SENSOR 1 SENSOR 2 SIGNAL INPUT CONFIGURATION JB 8 TERMINATION J...

Страница 23: ...dip switch settings found in Table 6 Figure 10 illustrates the layout of the DSI board while Table 7 gives detailed descriptions of the dip switch settings found in Table 6 Positions shown in Bold ar...

Страница 24: ...nel This setting is dependant on the selection of an external transmitter and if the input is voltage or current driven When a external 4 20mA transmitter is employed the setting must be set for a 100...

Страница 25: ...arm off for 30 minutes If any WARNING ALARM or FAULT condition remains after 30 minutes the audio alarm will again be activated Any WARNING ALARM or FAULT condition returning to normal and then reacti...

Страница 26: ...rp at 800 465 5777 or service armstrongmonitoring com The monitor should not need re calibration when first installed and powered up but a test for correct operation is recommended after a stabilizati...

Страница 27: ...lds are adjusted to with the trimpots Valarm Calarm Cfull scale IRange Ibase Rtermination KGas Monitor 1A Where Valarm The voltage measured at the alarm test point while adjusting the alarm trimpot Ca...

Страница 28: ...2 2 AMC DSI CALIBRATION Every AMC DSI Sensor is factory calibrated so each unit should be ready for operation after installation and a 30 minute stabilization time Calibration is recommended two times...

Страница 29: ...URE 12 AMC 1ACOs Test Points and Trimpots TABLE 9 DSI board Test points use a voltmeter with greater than 100K input resistance TP Title Usage 1 VFD Provides a voltage representation of the VFD output...

Страница 30: ...Open the front cover on the AMC 1ACOs enclosure 2 Attach the multi meter as shown in Figure 12 Connect negative black lead to TP22 main board Connect positive red lead to TP4 main board To set the ze...

Страница 31: ...adjusted to full scale 10V on a partial channel scale ie 50PPM Refer to Figure 10 for DSI Layout to perform the following calibration procedure 1 Open the front cover on the AMC 1ACOs enclosure 2 Mea...

Страница 32: ...fy the audio and WARNING and ALARM relays are operational 6 3 SENSOR REPLACEMENT The sensor should be replaced when the sensor no longer adequately responds to test gas Refer to the corresponding cali...

Страница 33: ...Ensure that there are no short or open circuits in the sensor cabling Verify that there is no AC or DC voltage present on the sensor cabling prior to connecting the cabling to either the sensor or the...

Отзывы: