Gas Monitor 1ACO One-Channel Monitor
12
Switch Feature Position
Description
SW1-2,
SW2-2
Minimum Run
Timer
See
Description
Warning and alarm relays are maintained in alarm state
for a minimum time interval following alarm activation, as
follows:
SW1-2 SW2-2 Minimum Run Time
OFF
OFF
0 minutes
ON OFF 5 minutes
OFF ON 10 minutes
ON ON 30 minutes
Note that a sensor level falling below the alarm threshold
and then re-occurring during this time resets the alarm
timer for the associated alarm.
SW1-3,
SW1-4
Sensor Type
(Mode
Select)
See
Description
Sensor type (threshold mode) is selected as follows:
SW1-3 SW1-4 Sensor Type (Mode)
OFF
OFF
Increasing
ON OFF Decreasing
OFF ON Reserved
ON ON Reserved
OFF
The Alarm relay is not activated when fault is detected.
SW2-1 Alarm
Relay
Activated
when Fault is
Detected
ON
When fault is detected, the Alarm relay is activated.
OFF
Audio alarm is disabled for Warning conditions.
SW2-3 Audio
Enable
for Warning
ON
Audio alarm is activated in conjunction with Warning.
OFF
Sensor Fault thresholds set at 0.4 mA into 250R or 100
mV.
SW2-4 Sensor
Fault
Threshold
ON
Sensor Fault thresholds set at 1.4 mA into 250R or
350mV.
OFF
No activation delay of Warning conditions.
SW2-5 Activation
Delay,
Warning
ON
Five minute delay on activation of Warning conditions
following sensor exceeding alarm threshold.
OFF
No activation delay of Alarm conditions.
SW2-6 Activation
Delay, Alarm
ON
Delay on activation of Alarm conditions following sensor
exceeding alarm threshold.
OFF
Audio alarm (buzzer) disabled.
SW2-7 Audio
Alarm
Enable
ON
Audio alarm (buzzer) enabled.