A.1 TECHNICAL DATA  
 

(a) 

General Information:  

 

Model & Heat Input  

 

See Chart Pg (2) for units available 

 
Information all units:  
Gas Supply Connection 

1/2” NPT Male  

Electrical Supply 

 

120V, 1 Phase,  

 

 

 

 

60Hz  

Current Rating 

 

1.2 AMP MAX  

    0.3 

Burner 

 

    0.9 

Fan 

 

Ignition   Electronic 

Program 

 

    Start 

up 

with 

Spark 

 

    Ignition 
 

OPTIONS: 

  1.  

Ambi-Rad Black Bulb 

   Thermostat. 

 

 

 

2.  

Control Panel with multi- 

   zone 

capabilities 

(not 

   AGA/CSA 

certified). 

 

 

 

3.  

Individual Heater Vent to 

 

 

 

Exterior. 

 

NOTES:  
 

A. 

Heater is intended for heating non-
residential indoor spaces and should 
only be installed where flammable gases 
or vapors are not generally present. 

B. 

Heaters may be suspended either hori-
zontal or at an angle, or may be wall 
mounted. See section A3 for clearance 
dimensions.  

 
C. 

The installation must conform with local 
building codes or, in the absence of local 
codes, with the 

National Fuel Gas Code, 

ANSI Z223.1/NFPA 54 

or the 

Natural 

Gas and Propane Installation Code, CSA 
B149.1.

 

 
D. 

The unit shall be electrically grounded 

 

accordance with National Electric Code 

 ANSJJNFPA 

70-1987. 

 

 
E. 

The heater may be installed in aircraft 
hangars when conforming with ANSI/
NFPA 409-1985 and in automotive ga-
rages when conforming with ANSIIN-
FPA 88A (latest edition) for Parking 
Structures and ANSIJNFPA 88B (latest 
edition) for repair garages. In Canada, 
installation code for natural gas burning 
appliances and equipment. CAN1-B 
149.1 and propane CANIB149.2. 

 
Ensure that minimum clearances will be 
maintained to vehicles parked below the 
heater.  

   

 

 

Y

WARNING: 

 

Minimum clearance from the heater must be maintained from vehicles parked 
below heater. In all situations, clearances to combustibles must be maintained. 
Signs should be posted in storage areas to specify maximum stacking height to 
maintain required clearance to combustibles. Refer to mounting clearance tables. 

   

 

 

Y

WARNING:

 

Improper installation, adjust-

ment, alteration, service or maintenance can cause 
property damage, injury or death. Read the instruc-
tions thoroughly before installing or servicing this 
equipment

 

A. INSTALLATION INSTRUCTIONS 

Содержание VPlus100

Страница 1: ...ion manual before perform ing Installation Servicing and Maintenance procedures Follow all warnings or cautions included in this literature and attached to the unit Consult local building codes and Na...

Страница 2: ...nits b Vented Vent c Horizontal Vent 9 FRESH AIR DUCTED INTAKE a Vertical Thro Roof b Horizontal Thro Wall 10 INSTALLATION CHECK OUT AND START UP 11 COMMISSIONING B SERVICE AND MAINTENANCE INSTRUCTION...

Страница 3: ...Code CSA B149 1 D The unit shall be electrically grounded accordance with National Electric Code ANSJJNFPA 70 1987 E The heater may be installed in aircraft hangars when conforming with ANSI NFPA 409...

Страница 4: ...t Above Floor Minimum Recommended in Feet C2 C1 A B1 B B A E D2 0 to 55 D1 Ensure that there is adequate provision in the building for combustion and ventilation air supply Installation must meet mini...

Страница 5: ...olor marked with yellow paint The remaining tubes are mild steel marked with blue paint Exception 175 000 through 225 000 Btu units require a sec ond section of Calcoat 20ft total steel tube connected...

Страница 6: ...40 to 150 000 btu Page 6 170 to 225 000 btu...

Страница 7: ...it controlling the heater or group of heaters include thermostats and if re quired manual control switches All such controls and switch gear must be rated to handle the total inductive load of the cir...

Страница 8: ...Page 8...

Страница 9: ...4 Page 9...

Страница 10: ...tely 10 to 20 seconds the fan will purge the system then re ignition will be attempted After 2 further attempts at igni tion the control unit will lock out the power on lamp will remain illuminated an...

Страница 11: ...ermostat is set to maximum and is calling for heat Close control housing Switch on electrical supply The red mains on lamp should now be illuminated If restarting heater a delay of 15s should be allow...

Страница 12: ...xible hose from the burner Step 5 Remove the burner and position the burner in a safe area to prevent the burner or components attached to the burner from falling to the ground 1 3 Burner Gas Injector...

Страница 13: ...r pot burner head can be re placed ensuring the 5 holes on the outer ring are aligned alongside the probes Step 3 The condition of the igniter assembly can be checked for deterioration However we advi...

Страница 14: ...ner tubes visually If the tubes appear clean skip to servicing the reflector Step 3 If required the interior of the tubes can then be cleaned using an industrial vacuum cleaner or by using long poles...

Страница 15: ...ing harness plugs 2 Operation of vacuum switch operation 3 Replace fan Is the burner sparking Does the gas valve open Check 1 Ignition controller 2 Replace gas valve Check 1 Vacuum switch tubes 2 Emit...

Страница 16: ...Refit leads Step 7 Test product and close access doors 3 2 Air Pressure Switch Replacement Step 1 Open the left hand door and disconnect the two silicone impulse tubes and the 3 cables Step 2 Remove t...

Страница 17: ...head can now be detached by disconnecting the impulse tube and the burner head wiring Step 6 Detach the two screws holding the front of the gas valve Step 7 Remove the four screws holding the rear bu...

Страница 18: ...ee table A F BURNER BODY 200358 G BURNER HEAD See table A H IGNITOR ASSEMBLY 201284 I JET CARRIER 40 50 200420 170 225 201630 J COMBUSTION FAN 201687 K VACUUM PRESSURE SWITCH See table A L GASKET SET...

Страница 19: ...VPLUS BURNER BREAKDOWN Page 19...

Страница 20: ...0 80 50 80 VPLUS150 150 000 201063 25 201007 30 4 2 201637 40 60 40 70 VPLUS125 123 500 201063 26 201007 24 4 1 L200262 40 60 40 60 VPLUS100 100 000 201063 23 201007 21 3 5 L200281 40 40 30 50 VPLUS80...

Страница 21: ...S200 200 000 0 0 0 0 0 0 0 0 TUBE 1 2 REMAINDER 30 VPLUS225 222 500 0 0 0 0 0 0 0 0 TUBE 1 2 REMAINDER 30 OPTIONS 1 All standard units fitted with unvented flue natural gas aluminum reflectors and duc...

Страница 22: ...REFLECTORS SC 4 ALUMINISED STL 4 MILD STEEL ALUMINIUM ER 4 ALUMINISED STL 4 MILD STEEL STAINLESS STEEL 11 6 NOMINAL OVERALL ASSEMBLED LENGTH FIXED JOINT DETAIL SLIDING JOINT DETAIL REFLECTOR OVERLAP...

Страница 23: ...G TUBES REFLECTORS SC 4 ALUMINISED STL 4 MILD STEEL ALUMINIUM ER 4 ALUMINISED STL 4 MILD STEEL STAINLESS STEEL REFLECTOR OVERLAP 2 50 MINIMUM C L S20 BURNER INSERT DETAIL NOTE FOR VPLUS80 ONLY BURNER...

Страница 24: ...ORS SC 4 ALUMINISED STL 4 MILD STEEL ALUMINIUM ER 4 ALUMINISED STL 4 MILD STEEL STAINLESS STEEL REFLECTOR OVERLAP 2 50 MINIMUM C L S30 BURNER INSERT DETAIL NOTE FOR VPLUS80 VPLUS100 ONLY BURNER INSERT...

Страница 25: ...COMBUSTION TUBE REMAINING TUBES REFLECTORS SC 4 ALUMINISED STL 4 MILD STEEL ALUMINIUM ER 4 ALUMINISED STL 4 MILD STEEL STAINLESS STEEL REFLECTOR OVERLAP 2 50 MINIMUM C L BURNER INSERT SEE DETAIL MODEL...

Страница 26: ...INSERT SEE DETAIL MODEL NUMBER BTU HR VPLUS100 S50 100 000 VPLUS125 S50 123 500 VPLUS150 S50 150 000 VPLUS170 S50 169 000 VPLUS200 S50 200 000 VPLUS225 S50 222 500 REFLECTOR OVERLAP 2 50 MINIMUM C L...

Страница 27: ...NISED STL 4 MILD STEEL STAINLESS STEEL S60 REFLECTOR OVERLAP 2 50 MINIMUM C L MODEL NUMBER BTU HR VPLUS125 S60 123 500 VPLUS150 S60 150 000 VPLUS170 S60 169 000 VPLUS200 S60 200 000 VPLUS225 S60 222 5...

Страница 28: ...ER 4 ALUMINISED STL 4 MILD STEEL STAINLESS STEEL REFLECTOR OVERLAP 2 50 MINIMUM C L NOTE 20 MINIMUM OF ALUMINISED STEEL COMBUSTION TUBES CONNECTED BY HIGH TEMPERATURE STAINLESS STEEL COUPLING AS SHOW...

Страница 29: ...MINIUM ER 4 ALUMINISED STL 4 MILD STEEL STAINLESS STEEL REFLECTOR OVERLAP 2 50 MINIMUM C L NOTE 20 MINIMUM OF ALUMINISED STEEL COMBUSTION TUBES CONNECTED BY HIGH TEMPERATURE STAINLESS STEEL COUPLING A...

Страница 30: ...G TUBES REFLECTORS SC 4 ALUMINISED STL 4 MILD STEEL ALUMINIUM ER 4 ALUMINISED STL 4 MILD STEEL STAINLESS STEEL REFLECTOR OVERLAP 2 50 MINIMUM C L MODEL NUMBER BTU HR VPLUS40 U20 41 500 VPLUS80 U20 80...

Страница 31: ...NISED STL 4 MILD STEEL ALUMINIUM ER 4 ALUMINISED STL 4 MILD STEEL STAINLESS STEEL REFLECTOR OVERLAP 2 50 MINIMUM C L U40 BURNER INSERT DETAIL NOTE FOR VPLUS80 AND VSPLUS100 ONLY MODEL NUMBER BTU HR VP...

Страница 32: ...D STL 4 MILD STEEL STAINLESS STEEL U60 REFLECTOR OVERLAP 2 50 MINIMUM C L MODEL NUMBER BTU HR VPLUS125 U60 123 500 VPLUS150 U60 150 000 VPLUS170 U60 169 000 VPLUS200 U60 200 000 VPLUS225 U60 222 500 N...

Страница 33: ...MINIUM ER 4 ALUMINISED STL 4 MILD STEEL STAINLESS STEEL U80 REFLECTOR OVERLAP 2 50 MINIMUM C L NOTE 20 MINIMUM OF ALUMINISED STEEL COMBUSTION TUBES CONNECTED BY HIGH TEMPERATURE STAINLESS STEEL COUPLI...

Страница 34: ...GAS VALVE C BURNER ON AMBER NEON D MAINS ON RED NEON E GAS INJECTOR F BURNER BODY G BURNER HEAD H IGNITOR ASSEMBLY I JET CARRIER J COMBUSTION FAN K VACUUM PRESSURE SWITCH L GASKET SET M BURNER HEAD W...

Страница 35: ...Page 35...

Страница 36: ...317 577 0337 Facsimile 317 842 3989 Website www ambi radusa com For the Distributor Nearest to you call 1 888 330 4878 is the registered Trademark of Ambi Rad Limited Due to continuous product innovat...

Отзывы: