56
8. User & Operating Instructions.
Document re
feren
c
e number
GB
/VS
/1
18/0711
8.1
To Start the Heater
1. Ensure gas supply is turned on.
2. Electrical supply to the controls is on.
3. Ensure that the controls are correctly set
i.e.;
•
Clock is correctly set.
•
Heater program is correctly set.
•
Required room temp is correctly set
4. Once the heating controller ‘calls for heat’
power will be supplied to the heater(s). The
red neon will then illuminate.
5. After a pre-purge period of 10 seconds the
burner will ignite and the amber neon will
then illuminate.
6. If lockout occurs press the lockout reset
button (if available), or switch off electrical
supply and restart after 15 seconds.
7. If lockout occurs three times consecutively
switch off and isolate the gas and
electricity supplies.
Contact the AmbiRad Service department.
8.2. To Switch Off Heater
1. Switch off electrical supply to the heater.
The burner will stop and the fan will shut
off.
2. If the heater is to be switched off for
periods in excess of one week it is highly
recommended that both the gas and the
electrical supplies are turned off.
8.3. Routine Maintenance between Service
Intervals
After ensuring that the heater is cold and
mains electric isolated, cleaning of the
reflectors with a soft cloth and a mild
detergent (non solvent based cleaners only)
in water can be undertaken.
Additional removal of dust from the radiant
tubes, burner and heat exchanger can be
undertaken.
8.4 Frequency of Servicing
The manufacturer recommends that to
ensure
continued
efficient
and
safe
operation of the appliance, the heater is
serviced annually by a competent person
e.g. every year in normal working conditions
but in exceptional dusty or polluted
conditions more frequent servicing may be
required.
The manufacturer offers a maintenance
service. Details are available on request.
For Service requirements, please contact
AmbiRad.
For further technical and service support
visit our Support Information Database at
www.s-i-d.co.uk
AmbiRad is a registered trademark of AmbiRad Limited. Because of continuous product
innovation, AmbiRad reserve the right to change product specification without due notice
AmbiRad Limited Fens Pool Avenue
Brierley Hill West Midlands DY5 1QA
United Kingdom.
Telephone 01384 489700
Facsimile 01384 489707
Email
Website
www.ambirad.co.uk
Technical Support
www.s-i-d.co.uk
Step 10 The two screws retaining the gas valve
can then be removed.
Step 11 The gas valve can now be replaced.
Step 12 Refit all components in reverse order.
Step 13 Ensure step screw is in the correct
position as indicated in the previous diagram.
(For Natural Gas burners ONLY).
Step 14 Set gas pressures to data badge or as
per section 1.11 and ensure reliable burner
performance.
Step 15 Test product and close access doors.