button (C) — damper can now be 

 

 

 

 

 

 

adjusted manually. 

3. 

Rotate damper spindle until low fire end 
vent suction of between 0.5” to 1” WG is 
achieved. Release the manual override   
button (C). 

4. 

Using a phillips screwdriver, reposition 
the mechanical end stop (A) to final 
bracket  position. 

5. 

Reconnect power to damper. Recheck    
correct direction of rotation (i.e. when 
4mA from controller = damper fully open.) 
If this is not correct, use a flat head 
screwdriver and change the direction 
switch (B). 

The high/low fire end vent suction adjustment is 
made using the fan damper. 
 

Setting Maximum Fire End Vent Suction.            

 
1.  Isolate supply from the motorised 

damper. 

2. 

Press and hold the manual override 

 

 

 

button  (C)  —  damper  can  now  be        
adjusted manually. 

3. 

Rotate damper spindle until end vent suc-
tion of between 2.5” to 3” WG is 
achieved. Release the manual override 
button. 

4. 

Using a phillips screwdriver, reposition 
the  mechanical end stop (A) to final 
bracket  position. 

5. 

Reconnect power to damper. Recheck    
correct direction of rotation (i.e. when 
4mA from controller = damper fully open.) 
If this is not correct, use a flat head 
screwdriver and change the direction 
switch (B). 

 

Setting Minimum Fire End Vent Suction. 

 

1.  Isolate supply from the motorised 

damper. 

2. 

Press and hold the manual override 

 

 

 

10 Modulation End Vent Suction Setting Procedure. 

Nb 
Please contact an AmbiRad representative for installations over 4000’ elevation 

11 Modulation Technical Information. 

  

Heater Model

 

 

 

ARC18LR(M)

 

ARC24LR(M)

 

ARC32LR(M)

 

ARC38LR(M)

 

Minimum Fire BTU 

30,000 

39,000 

52,000 

63,000 

Maximum Fire BTU 

74,000 

98,000 

130,000 

155,000 

  

  

  

  

  

Jet Size 

LPG 

L100535
(3.5mm) 

L100540
(4.0mm) 

L100544
(4.4mm) 

L100548
(4.8mm) 

  

Nat Gas 

L100544 
(4.4mm) 

L100549 
(4.9mm) 

L100554 
(5.4mm) 

L100558 
(5.8mm) 

  

  

  

  

  

Shutter Plate 

L100321 
(17mm) 

L100320 
(19.5mm) 

L100314 
(22mm) 

L100316 
(24mm) 

  

  

  

  

  

End Vent 
Orifice Plate 

L104102 
(16mm) 

L104101 
(24mm) 

L104100 
(27mm) 

L104103 
(28mm) 

End Vent Suction (All Models) 

Minimum Fire  

0.5” to 1” WG 

Maximum Fire  

2.5” to 3” WG 

Содержание SmartCom3

Страница 1: ......

Страница 2: ...losed circuit to enable Connect to B0 B1 for remote ON ie BMS time control REMOTE SENSOR s may be placed at a max distance of 325ft from the control unit using shielded 18 Awg cable Wiring should be k...

Страница 3: ...and ONE slave configuration Wire further slaves in parallel REMOTE SWITCH INPUTS should be connected by 18 Awg cable Max length is 325ft Low voltage switching inputs to be normally open closed circuit...

Страница 4: ...able Connect to B0 B1 for remote ON ie BMS time control REMOTE SENSOR s may be placed at a max distance of 325ft from the control unit using shielded 18 Awg cable Wiring should be kept separate from m...

Страница 5: ...5ft from the control unit using shielded 18 Awg cable Wiring should be kept separate from mains wiring to minimize noise pick up Set within Engineers functions for any remote sensors SmartCom Mulitizo...

Страница 6: ...ster and ONE slave configuration Wire further slaves in parallel REMOTE SWITCH INPUTS should be connected by 18 Awg cable Max length is 325ft Low voltage switching inputs to be normally open closed ci...

Страница 7: ...a master and ONE slave configuration Wire further slaves in parallel REMOTE SWITCH INPUTS should be connected by 18 Awg cable Max length is 325ft Low voltage switching inputs to be normally open close...

Страница 8: ...to enable Connect to B0 B1 for remote ON ie BMS time control REMOTE SENSOR s may be placed at a max distance of 325ft from the control unit using shielded 18 Awg cable Wiring should be kept separate...

Страница 9: ...plug and remove the cap via two screws Connect the incoming 24V cable from the Control panel onto terminals L3 and GND ensuring correct orientation Connect the incoming 4 20mA cable from the modulati...

Страница 10: ...nt Module In line Burner Branch Zone 2 18 Awg Shielded Cable Sensor Zone 2 In line Burner In line Burner In line Burner 2nd Branch Zone 1 End Vent Module End Vent Burner 1 phase 115V Pump 115V 60Hz Ma...

Страница 11: ...driver reposition the mechanical end stop A to final bracket position 5 Reconnect power to damper Recheck correct direction of rotation i e when 4mA from controller damper fully open If this is not co...

Страница 12: ...to default settings as described in the SmartCom Installation and User Manual ref US SCOM 29 The controllers will therefore operate immediately with standard Infrared Radiant heaters To alter the cont...

Страница 13: ...the entire system on whereas making this connection on a slave unit will only bring on that zone 1 BMS Controlling Time only Ensure all the programmed ON times in the SmartCom are turned off i e They...

Страница 14: ...0337 Facsimile 317 842 3989 Website www ambirad com us For the Distributor Nearest please call 1 888 330 4878 AmbiRad is a registered trademark of AmbiRad Limited Because of continuous product innova...

Отзывы: