Ambirad HCHE 120 Скачать руководство пользователя страница 13

 
 

 13/30 

4.0 Installation

 

 
4.1 

Location

 

 
4.1.1 

Ensure the structural elements of the building are 

adequate to carry the weight of the appliance and 
its ancillary components, i.e. the flue system, and 
that the surface on which the heater is located is 
level in all plains and non-combustible. 

  

4.1.2 

Sufficient space must be maintained around the 
heater for servicing and the appliance should not 
be sited where it may suffer damage, e.g. forklift 
trucks or traffic. 

 
4.1.3 

The location must also allow for fitting an 
effective flue system and for adequate clearance 
for the air supply, return air, circulation, gas and 
electrical supplies whilst providing good and safe 
working access. 

 
4.1.4 

When moving the heater it is strongly advised 
that the lifting eyes are used.  Adequate 
clearance from combustible materials must be 
maintained between the appliance and its flue 
system. 
 

 

4.1.5 

The horizontal cabinet heater (HCHE) must be 

suspended as illustrated in figure 5.  When 
suspending the horizontal units, ensure the 
structural elements of the building are adequate 
to carry the weight of the appliance and its 
ancillary components (e.g. : flue system, duct 
system, ...).  Unit may only be suspended by 
means of a frame on which the unit must be 
installed. It is strictly forbidden to make use of the 
fixation eyes to suspend the unit! 

 

When unit is installed as a ducted heater, the 
duct connections must be installed as described 
in § 4.5.3. Ensure the dimensions of inlet & outlet 
duct are the same.  
When the air intake is installed without a grille at 
the backside of the unit, ensure that a protection 
grille IP20 is installed to avoid the penetration of 
objects into the blower compartment. 

 

Figure 5

 : 

 

 

4.2 

Heater clearances

 

 
4.2.1 

The following minimum clearances must be 
observed when installing the heater to enable 
easy access to the heater: 

 

Minimum clearance around a vertical heater  
(table 6) 

VCHE  

Frame 

Front *  

LHS 

RHS 

Rear 

Top**  

30 

800 500 500 500 1200 

40 

800 500 500 500 1200 

50 

800 500 500 500 1500 

60 

800 500 500 500 1500 

75 

II 

800 500 500 500 1500 

90 

900 600 600 600 1500 

120 

III 

900 600 600 600 1500 

140 

1000 800 800 600 1750 

150 

1000 800 800 600 1750 

180 

IV 

1000 800 800 600 1750 

215 

1000 1000 1000 2000 2000 

250 

1000 1000 1000 2000 2000 

*   

Measured from front panel. 

** 

Measured from top of outlet nozzle 

All dimensions in mm.  Front is when looking at the burner. 

 
 
Minimum clearance around a horizontal heater  
(table 7) 

HCHE 

Frame 

front* 

Rear 

side 

Bottom  

Top 

30 

800 500 500 500 

40 

800 500 500 500 

50 

800 500 500 500 

60 

800 500 500 500 

75 

II 

800 500 500 500 

90 

900 600 600 600 

120 

III 

900 600 600 600 

140 1000 

600 

800 

800 

150 1000 

600 

800 

800 

180 

IV 

1000 600  800  800 

215 

1000 2000 1000 1000 

250 

1000 2000 1000 1000 

* Measured from front panel 

Содержание HCHE 120

Страница 1: ...Leave it with the user or attached to the appliance or gas service meter after installation WARNING Improper installation adjustment alteration service or maintenance can cause property damage injury...

Страница 2: ...ectrical Connection 3 3 Ventilation Requirement 4 0 Installation 4 1 Location 4 2 Heater Clearances 4 3 Flue 4 4 Nozzled Heaters 4 5 Ducted Heaters 4 6 Filters 4 7 Controls 5 0 Commissioning 5 1 Pre C...

Страница 3: ...ered gas installers 1 1 7 Warning Unauthorised modification of this appliance or departure from use in the manner for which it was intended by the manufacturer or installation in a manner contrary to...

Страница 4: ...cations Each heater must have its own individual open flue 1 4 2 All cabinet heaters are fitted with a pre tested and set forced draught burner A sequential control box is fitted to each burner to pro...

Страница 5: ...0 GS20 GS20 GS20 Minimum gas inlet mbar 17 5 20 17 5 20 17 5 20 17 5 20 17 5 20 17 5 20 17 5 20 17 5 20 17 5 20 17 5 20 17 5 20 17 5 20 pressure ins WG 7 8 7 8 7 8 7 8 7 8 7 8 7 8 7 8 7 8 7 8 7 8 7 8...

Страница 6: ...0 39 39 41 45 42 heater nominal F 65 90 52 65 76 67 72 70 70 74 81 76 Sound level 2 for guidance only Flue spigot outside diameter Total absorbed electrical power VCHE HCHE Model FRAME size I II III I...

Страница 7: ...7 30 2 2 Dimensions Vertical heater range Figure 1a unit with discharge nozzle Front view Figure 1b unit with discharge plenum Front view...

Страница 8: ...8 30 Figure 1c Side view Figure 1d Figure 1e Figure 1f burner mounting flange air inlet air inlet...

Страница 9: ...e Figure 2a Side view Figure 2b Front view Remark The fixation eyes 4x dia 22 5 may only be used to put the unit into horizontal position after delivery It is strictly forbidden to use the fixation ey...

Страница 10: ...3 2073 2012 2012 inside dia 1 burner inlet 110 110 120 120 140 140 155 155 155 155 H1 2088 2088 2168 2168 2376 2378 2477 2477 2466 2466 H2 2164 2164 2114 2114 2400 2400 2395 2395 2334 2334 K1 K2 35 5...

Страница 11: ...appliance and in view when facing the service compartment The isolator must have a contact separation of at least 3 0mm on all poles 3 2 5 The cabinet heaters are foreseen with a control unit supplied...

Страница 12: ...re in the zone as this will lead to a hazardous situation whereby the air heater flue will act as a pressure relief 3 3 6 Normally cabinet air heaters which are used in the free blowing mode i e witho...

Страница 13: ...ake use of the fixation eyes to suspend the unit When unit is installed as a ducted heater the duct connections must be installed as described in 4 5 3 Ensure the dimensions of inlet outlet duct are t...

Страница 14: ...sized in accordance with the diameter appropriate to the appliance flue connection socket Flues must be terminated with an approved terminal fitting Attention ensure that the connection of the flue t...

Страница 15: ...for the sizes 140 150 180 and qty 18 for the sizes 215 250 see fig 8 The horizontal louvers may be adjusted to obtain proper deflection and air pattern For safety reasons it is recommended to wear glo...

Страница 16: ...16 30 Figure 8 Nozzle plenum DB1 DA1 D A 2 D B 2 Figure 9 Vertical louvres...

Страница 17: ...g Duct outlets must be adjusted when necessary to meet the values mentioned in table 9 Table 9 Frame Model Nominal airflow Available outlet static pressure Motor load maximum Motor current normal use...

Страница 18: ...be adjusted when necessary to meet the values mentioned in table 9 4 5 5 Ducted air inlet on VCHE HCHE units The unit is designed so that it can be installed with inlet air ducts Vertical units Option...

Страница 19: ...556 III 90 120 541 4 end 691 1054 651 1014 541 5 top 541 7 bottom 1201 707 1161 667 541 6 rear 1082 707 1042 667 IV 140 150 180 541 4 end 1082 1201 1042 1161 541 5 top 541 7 bottom 1400 596 1360 556 5...

Страница 20: ...ails Filters must be inspected on a regular basis as dirty filters can affect the safe working of the unit For safety reasons it is recommended to wear gloves glasses when inspecting the filters Dirty...

Страница 21: ...end 1 standard 2 duct left 3 duct right 4 duct rear Figure 13a Overview of the VCHE options Note When filters option 502 1 are required then the standard air intake panels must be replaced by the pane...

Страница 22: ...before commencing then proceed with the following checks a Ensure electrical supply has been switched off b Ensure the gas supply is switched off c Check that the heater has been installed on a suita...

Страница 23: ...Then check the following Fan limit stat settings are correct The bi metal strip has not been damaged The bi metal strip casing is not in contact with the heat exchanger body l Adjust temperatures and...

Страница 24: ...Same as after 6 months b Heat exchanger inspection and cleaning c Burner maintenance d Main fan and motor e Pulley and belts f Flue system g Control panel and electrical connections h Gas supply conn...

Страница 25: ...ave worn excessively then change the whole set immediately DO NOT MIX BELTS OF DIFFERENT AGES OR BATCHES As the belts stretch at a different rate according the batch curing number and age premature fa...

Страница 26: ...sure switch Check gas pressure switch Check burner motor Burner starts but goes to lockout Check gas supply Bad earth Main gas cock open Air in gas line Flame probe failure Air pressure switch failure...

Страница 27: ...ting Check control box Signal Check main gas actuator Burner lights but will not hold on main flame Insufficient air High inlet Pressure Fan limit stat Air inlets blocked Outlet nozzles closed Duct re...

Страница 28: ...ustion chamber CC air deflector 10 fixation plate HE 11 sliding bracket HE 12 over pressure relief panel 13 heat exchanger combustion chamber 14 side air deflectors 15 side inner skins 16 top side pan...

Страница 29: ...0 60 75 Contactor 60 61679 D910M5 sizes 90 120 140 150 180 215 Contactor 60 61679 D1210M size 250 60 61703 02 04 size 90 60 61703 04 06 size 120 60 61703 05 09 size 140 60 61703 07010 sizes 150 180 21...

Страница 30: ...bility BSEN 50165 Safety of Electrical Equipment BS 5991 Indirect Gas Fired Heaters less than 2MW BS 5440 Part 1 Specification Installation of Flues Part2 Ventilation Requirements of Gas Appliances BS...

Отзывы: