Ambient Weather WH117L Скачать руководство пользователя страница 18

 

Version 2.1  

©Copyright 2015,   

 

 

 

Page 18 

There are dashes (--) on the display 
console. 

 

will turn on. Wait several minutes for the remote 
sensor to report in, or the search icon to turn off.
 
If the synchronization fails, reset the console by 
removing one battery from the display console, 
wait 10 seconds, and reinsert the battery. 
Do not press any buttons while in the search 
mode. 
 

2.

 

Check the remote sensor is powered up and 
displaying the temperature and humidity on the 
LCD display. 

3.

 

Install a fresh set of batteries in the remote 
thermo-hygrometer. For cold weather 
environments, install lithium batteries. 

4.

 

The maximum line of sight communication 
range is 300’. Move the sensor assembly closer 
to the display console. 

5.

 

If the sensor assembly is too close (less than 
5-10’), move the sensor assembly away from the 
display console. 

6.

 

Make sure the remote sensors are not 
transmitting through solid metal (acts as an RF 
shield), or earth barrier (down a hill). 

7.

 

Move the display console around electrical noise 
generating devices, such as computers, TVs and 
other wireless transmitters or receivers. 

8.

 

Move the remote sensor to a higher location. 
Move the remote sensor to a closer location. 

9.

 

Radio Frequency (RF) Sensors cannot transmit 
through metal barriers (example, aluminum 
siding) or multiple, thick walls. 

Temperature sensor reads too high in the 
day time. 

Make sure the thermo-hygrometer is mounted in a 
shaded area on the north facing wall.   

Indoor and Outdoor Temperature do not 
agree 

1.

 

Allow up to one hour for the sensors to stabilize 
due to signal filtering. The indoor and outdoor 
temperature sensors should agree within 4 °F 
(the sensor accuracy is ± 2 °F). 

2.

 

Perform a temperature calibration (reference 
Section 4.2.5)

Indoor and Outdoor Humidity do not 
agree 

1.

 

Allow up to one hour for the sensors to stabilize 
due to signal filtering. The indoor and outdoor 
humidity sensors should agree within 10 % (the 
sensor accuracy is ± 5 %) 

2.

 

Perform a humidity calibration (reference 
Section 4.2.4) 

Console outdoor humidity and remote 
humidity do not agree. 

The console displays the calibrated humidity. The remote 
displays the measured humidity only.    Refer to 4.2.4 to 
set and reset the humidity calibration. 

Relative pressure does not agree with 
official reporting station 

1.

 

You may be viewing the relative pressure, not 
the absolute pressure. 

2.

 

Make sure you properly calibrate the barometer 

Содержание WH117L

Страница 1: ...eration 8 4 2 3 Setting Barometric Pressure 10 4 2 4 Setting Calibrated Humidity 11 4 2 5 Setting Calibrated Temperature 11 4 3 Alarm Mode 12 4 3 1 Alarm Display 12 4 3 2 Alarm Programming 12 4 3 3 Ca...

Страница 2: ...r WH2F The following user guide provides step by step instructions for installation operation and troubleshooting Product Features Figure 1 No Description No Description 1 Radio Controlled Clock with...

Страница 3: ...Display Console Frame Dimensions LxWxH 7 25 x 4 x 1 25 in LCD Dimensions LxW 4 25 x 2 50 1 Thermo hygrometer transmitter WH2F with mounting bracket Dimensions LxWxH 3 5 x 2 5 x 0 9 2 2 Recommend Tools...

Страница 4: ...ree AA alkaline or lithium avoid rechargeable batteries in the back of the display console Looking at the back of the unit left to right the polarity is for the top battery for the middle battery and...

Страница 5: ...oid interference If the signal reception is not successful normally during the day due to solar interference the sensor search will be cancelled the outdoor temperature and humidity will update as nor...

Страница 6: ...ze key is on the top of the display console 2 4 3 Sensor Operation Verification Verify the indoor and outdoor humidity match closely with the console and sensor array in the same location about 10 apa...

Страница 7: ...key and key There are four program modes Quick Display Mode Set Mode Alarm Mode and Min Max Mode Any program mode can be exited at any time by either pressing the SNOOZE LIGHT key on the top of the d...

Страница 8: ...Pressure Calibration Press to increase MIN MAX to decrease SET Pressure Threshold for Forecast Press to increase MIN MAX to decrease SET Storm Threshold for Forecast Press to increase MIN MAX to decr...

Страница 9: ...ndard Tokyo 10 GST Guam Standard Sydney 11 Magadan 12 IDLE International Date Line East NZST New Zealand Standard Wellington New Zealand 3 12 24 Hour Format Press the SET key again to adjust the 12 24...

Страница 10: ...re details on this feature 13 Outdoor Humidity Calibration default is measured outdoor humidity Press the SET key to adjust the outdoor humidity Press the key or MIN MAX key to adjust the relative hum...

Страница 11: ...ch the official reporting station 4 2 4 Setting Calibrated Humidity Note This is a continuation of the previous section To enter this mode you must start at the beginning of this section The display c...

Страница 12: ...play the measured temperature level and not the calibrated temperature level Only the console will show the calibrated value Note The dew point calculation is based on the calibrated temperature level...

Страница 13: ...h for 120 seconds Press any key to cancel the alarm When an alarm condition is activated again within 10 minutes the alarm will not sound but will continue to flash until the weather condition is stab...

Страница 14: ...ess the SNOOZE key or wait 30 seconds for the programming mode to timeout and the Min Max mode will return to Normal Mode 4 5 Other Console Features The following section describes additional console...

Страница 15: ...right indicates that the air pressure is increasing and the weather is expected to improve The arrow pointing the left indicates that the air pressure is decreasing and the weather is expected to det...

Страница 16: ...24 hours Each bar represents three hours The vertical scale of the graph is auto scaled There is not fixed pressure level for each bar and is intended for visualizing trends only 4 5 8 Restoring Lost...

Страница 17: ...smission in open air 300 feet Frequency 433 92 MHz Update Rate 48 seconds 6 2 Measurement Specifications The following table provides specifications for the measured parameters Measurement Range Accur...

Страница 18: ...Move the remote sensor to a higher location Move the remote sensor to a closer location 9 Radio Frequency RF Sensors cannot transmit through metal barriers example aluminum siding or multiple thick w...

Страница 19: ...Lithium Battery 2 pack Batteries for Long Life and Cold Climates AA lithium batteries for cold weather climates Ambient Weather SRS100LX Temperature and Humidity Solar Radiation Shield Solar Radiatio...

Страница 20: ...void the user s authority to operate the equipment Statement according to FCC part 15 105 NOTE This equipment has been tested and found to comply with the limits for a Class B digital device pursuant...

Отзывы: