L1 N1 N L
Sensor
Max load 16A (3600W)
Error Codes
This relates to a fault with the internal temperature
sensor, either through damage or disconnection.
This usually requires a replacement thermostat
to correct.
This relates to a fault with the external floor
sensor probe. Contact your electrician, who
can isolate the electricity supply and check the
sensor is connected and working correctly.
Screen Lock
In some situations where your Amber-Pro is
installed into a location where restricted access
is necessary, simply:
Press and hold the button until the
appears on the screen (3 seconds).
To unlock, simply repeat the process until the
disappears.
E1
E2
3 Simple Steps to Factory Reset
1. Having initiated the advanced settings, tap the
menu button continuously until you see 12
2. Use the and buttons to set to 01
3. Press the buttons and switch off at the
mains to complete factory reset
No.
Description
Default
Range
00
Room
temperature
calibration
00
-10~10 C
01
Floor
temperature
calibration
00
-10~10 C
02
Sensor mode
00
00: built-in sensor
01: floor sensor
02: both sensors
03
Max
temperature
setting
35 C
30~60 C
04
Min
temperature
setting
5 C
5~15 C
05
Switching
differential
1 C
0~10 C
06
Frost protection
mode
00
00:yes 01:no
07
Heating
schedule
00
00: 5/2 day mode
01: 6/1 day mode
02: 7 day mode
08
Output delay
00
0~10s
09
Maximum floor
temperature
35 C
5~60 C
10
Holiday
temperature
Not Used
Not Used
11
Temperature
unit
00
00: ˚C 01:˚F
12
Factory reset
00
00:no 01:reset
Advanced Settings Overview
Dimensions
86mm
14mm
30mm
86mm
Installation Guide
STEP 1
Mount the backing plate in the wall socket
with a screwdriver before wiring takes place.
1
2
3
4
5
6
7
16A
L1 N1 N L
Sensor
Max load 16A (3600W)
1
2
3
4
5
6
7
16A
L1 N1 N L
Sensor
Max load 16A (3600W)
STEP 2
Ensure all wiring is undertaken by a qualified
electrician.
STEP 3
After connecting the wires, mount the
thermostat onto the backing plate as per
pictures.