Calculating Vent System Length

To calculate the length of the system you need, add the 
equivalent feet (meters) for each vent piece used in the system. 

7" (17.8 cm) Round Vent System

Example vent system

3¹⁄₄

" x 10" (8.3 cm x 25.4 cm) Vent System

Example vent system

Electrical Requirements

Observe all governing codes and ordinances. 

Ensure that the electrical installation is adequate and in 
conformance with National Electrical Code, ANSI/NFPA 70 (latest 
edition), or CSA Standards C22.1-94, Canadian Electrical Code, 
Part 1 and C22.2 No. 0-M91 (latest edition) and all local codes 
and ordinances.

If codes permit and a separate ground wire is used, it is 
recommended that a qualified electrician determine that the 
ground path is adequate.

A copy of the above code standards can be obtained from:

National Fire Protection Association

One Batterymarch Park

Quincy, MA 02269

CSA International

8501 East Pleasant Valley Road

Cleveland, OH 44131-5575

A 120 volt, 60 Hz., AC only, 15-amp, fused electrical circuit is 
required.

If the house has aluminum wiring, follow the procedure 
below:

1. Connect a section of solid copper wire to the pigtail 

leads.

2. Connect the aluminum wiring to the added section of 

copper wire using special connectors and/or tools 
designed and UL listed for joining copper to aluminum.

Follow the electrical connector manufacturer's recommended 
procedure. Aluminum/copper connection must conform with 
local codes and industry accepted wiring practices.

Wire sizes and connections must conform with the rating of 
the appliance as specified on the model/serial rating plate. 
The model/serial plate is located behind the filter on the rear 
wall of the range hood.

Wire sizes must conform to the requirements of the National 
Electrical Code, ANSI/NFPA 70 (latest edition), or CSA 
Standards C22. 1-94, Canadian Electrical Code, Part 1 and 
C22.2 No. 0-M91 (latest edition) and all local codes and 
ordinances.

Vent Piece

Round

45° elbow

2.5 ft
(0.8 m) 

90° elbow

5.0 ft
(1.5 m)

7" (17.8 cm) wall cap

0.0 ft
(0.0 m)

3

¹⁄₄

" x 10" (8.3 cm x 25.4 cm) 

to 7" (17.8 cm)

4.5 ft
(1.4 m)

3

¹⁄₄

" x 10" (8.3 cm x 25.4 cm) 

to 7" (17.8 cm) 90° elbow

5.0 ft
(1.5 m)

Maximum Recommended Length

= 50 ft (15.2 m)

1 - 90° elbow

= 5.0 ft (1.5 m)

1 - wall cap

= 0.0 ft (0.0 m)

8 ft (2.4 m) straight

= 8.0 ft (2.4 m)

Length of 7" (17.8 cm) system

= 13.0 ft (3.9 m)

Vent Piece

3

¹⁄₄

" x 10" (8.3 cm x 25.4 cm)

90° elbow

5.0 ft
(1.5 m) 

3

¹⁄₄

" x 10" (8.3 cm x 25.4 cm) 

flat elbow

12.0 ft
(3.7 m)

3

¹⁄₄

" x 10" (8.3 cm x 25.4 cm) 

wall cap

0.0 ft
(0.0 m)

Wall cap

 

 

 

 

7" (17.8 cm) round

90˚ elbow

2 ft (0.6 m)

6 ft (1.8 m)

Maximum Recommended Length

= 35 ft (10.7 m)

1 - 90° elbow

= 5.0 ft (1.5 m)

8 ft (2.4 m) straight

= 8.0 ft (2.4 m)

1 - wall cap

= 0.0 ft (0.0 m)

Length of 3

¹⁄₄

" x 10" (8.3 cm x 25.4 cm) 

system

= 13.0 ft (3.9 m)

Wall cap

 

   

3

¹⁄₄

" x 10"

(8.3 x 25.4 cm) 

elbow

2 ft

(0.6 m)

6 ft (1.8 m)

Содержание UXT5230AYB

Страница 1: ...lpool ca HOTTE D ASPIRATION DE 30 76 2 CM ET 36 91 4 CM Instructionsd installationetGuided utilisationetd entretien Au Canada pour assistance installation ou service composer le 1 800 807 6777 ou visi...

Страница 2: ...installation 27 UTILISATION DE LA HOTTE 28 Commandes de la hotte de cuisini re 28 ENTRETIEN DE LA HOTTE 28 Nettoyage 28 SCH MA DE C BLAGE 30 ASSISTANCE OU SERVICE 31 Au Canada 31 Accessoires 31 GARAN...

Страница 3: ...ardous or explosive materials and vapors CAUTION To reduce risk of fire and to properly exhaust air be sure to duct air outside do not vent exhaust air into spaces within walls or ceilings attics or i...

Страница 4: ...crews with washers and nuts to attach filler strips LocationRequirements IMPORTANT Observe all governing codes and ordinances It is the installer s responsibility to comply with installation clearance...

Страница 5: ...the vent system enters the heated portion of the house Makeup Air Local building codes may require the use of makeup air systems when using ventilation systems greater than specified CFM of air moveme...

Страница 6: ...for joining copper to aluminum Follow the electrical connector manufacturer s recommended procedure Aluminum copper connection must conform with local codes and industry accepted wiring practices Wire...

Страница 7: ...ne on the underside of the cabinet Mark the point on this line that is 2 2 cm from back wall Drill a 1 3 2 cm diameter hole through the cabinet at this point To wire through wall 1 Mark a line distanc...

Страница 8: ...ide of the top of cabinet 3 Use a compass or a circle template to draw a circle with a diameter that is 0 64 cm larger than the vent 4 Use saber or keyhole saw to cut the circular vent opening Style 3...

Страница 9: ...into place 7 Remove vent knockouts depending on your installation requirements Round vent system installations Remove top rectangular and round vent knockouts Rectangular vent system installations Fo...

Страница 10: ...n on ordering NOTE Do not reconnect power until the installation is complete 2 Remove the screw from the terminal box cover Remove terminal box cover and set aside 3 Remove the power supply knockout f...

Страница 11: ...2 Replace grease filter See the Range Hood Care section 3 Check the operation of the range hood fan and light See Range Hood Use section If range hood does not operate check to see whether a circuit...

Страница 12: ...paper towels To avoid damage to the stainless steel do not use cleaners that contain chlorine Cleaning Method Rub in direction of grain to avoid scratching or damaging the surface For stainless steal...

Страница 13: ...rew into the filter retainer Replacing the Halogen Lamp Turn off the range hood and allow the halogen lamp to cool To avoid damage or decreasing the life of the new lamp do not touch lamp with bare fi...

Страница 14: ...A 110 Watts 27 5 10 Ohms 55 7 10 Ohms Motor Characteristics Power Supply 120 VAC Frequency 60 Hz Amperage Wattage Rating Motor Resistance Red Brown Red Black Red Gray 86 8 10 Ohms W Common BK Line BK...

Страница 15: ...company in your area you can also look in your telephone directory Yellow Pages For further assistance If you need further assistance you can write to Whirlpool Corporation with any questions or conce...

Страница 16: ...ce by an authorized Whirlpool servicer is not available 10 The removal and reinstallation of your major appliance if it is installed in an inaccessible location or is not installed in accordance with...

Страница 17: ...n cas de non respect des instructions Votre s curit et celle des autres est tr s importante Nous donnons de nombreux messages de s curit importants dans ce manuel et sur votre appareil m nager Assurez...

Страница 18: ...que d incendie et vacuer ad quatement les gaz veiller acheminer l air aspir par un conduit jusqu l ext rieur ne pas d charger l air aspir dans un espace vide du b timent comme une cavit murale un plaf...

Страница 19: ...ion des tringles d appui Exigencesd emplacement IMPORTANT Observer les dispositions de tous les codes et r glements en vigueur C est l installateur qu incombe la responsabilit de respecter les distanc...

Страница 20: ...ment d isolation thermique pour minimiser la conduction de chaleur par l interm diaire du conduit d vacuation de l int rieur de la maison l ext rieur Le clapet anti retour doit tre plac du c t air fr...

Страница 21: ...u le sommet achat s par B Bouche de d charge murale avec clapet achat s par C Entre 24 61 cm min et 30 76 2 cm max au dessus de la surface de cuisson Composant Rond Coude 45 2 5 pi 0 8 m Coude 90 5 0...

Страница 22: ...vec la demande de courant de l appareil sp cifi e sur la plaque signal tique La plaque signal tique de l appareil est situ e derri re le filtre sur la paroi arri re de la hotte Le calibre des conducte...

Страница 23: ...r la face inf rieure du sommet du placard vacuation par le mur D coupage d une ouverture rectangulaire de 3 x 10 8 9 cm x 26 7 cm dans le mur 1 Mesurer 2 lignes de 0 9 cm et 3 9 8 cm en descendant par...

Страница 24: ...er l ouverture circulaire pour le passage du conduit d vacuation Installation du conduit d vacuation 1 Installer le conduit d vacuation travers l ouverture d coup e dans le placard mural ou le mur Ach...

Страница 25: ...8 3 x 25 4 cm selon la configuration de votre installation La fixer la hotte l aide des vis de 3 5 x 5 mm fournies et retirer le ruban adh sif de l obturateur registre REMARQUE La plaque de montage de...

Страница 26: ...on avant d avoir compl tement termin l installation 2 ter la vis du couvercle du bo tier de connexion Retirer le couvercle du bo tier de connexion et le mettre de c t 3 ter l opercule pour le passage...

Страница 27: ...graisse Voir la section Entretien de la hotte 3 Contr ler le fonctionnement du ventilateur de la hotte et de la lampe Voir la section Utilisation de la hotte Si la hotte ne fonctionne pas d terminer...

Страница 28: ...ment la hotte et les filtres graisse en suivant les instructions suivantes R installer le filtre graisse avant de faire fonctionner la hotte Surfaces externes IMPORTANT Ne pas utiliser de tampons de r...

Страница 29: ...cher la patte de retenue du filtre Elle reviendra alors en place et fixera le filtre 4 R installer la vis dans la patte de retenue du filtre Remplacement de la lampe halog ne Interrompre l alimentati...

Страница 30: ...e 3 Vitesse 2 Vitesse 1 MAR BL GRIS N Fonctionnement du commutateur L 1 Lampes 120 V 1 5 Ohms L 2 Vitesse 1 120 V 1 5 Ohms L 3 Vitesse 2 120 V 2 0 Ohms 2 5 Ohms 120 V Vitesse 3 L 4 Rouge Gris 86 8 10...

Страница 31: ...ue ce gros appareil m nager est utilis et entretenu conform ment aux instructions jointes ou fournies avec le produit Whirlpool Corporation ou Whirlpool Canada LP ci apr s d sign es Whirlpool paiera p...

Страница 32: ...ATIONS PEUVENT NE PAS S APPLIQUER DANS VOTRE CAS CETTE GARANTIE VOUS CONF RE DES DROITS JURIDIQUES SP CIFIQUES ET VOUS POUVEZ GALEMENT JOUIR D AUTRES DROITS QUI PEUVENT VARIER D UNE JURIDICTION UNE AU...

Отзывы: