background image

11

Defrost System

Troubleshooting

WARNING

To avoid electrical shock or death, disconnect the power before changing the defrost time cycle or servicing the
unit.

This unit is equipped with a time/temperature defrost board.  Defrosting of the outdoor coil is determined by both coil
temperature and compressor run time.  Adjustment can be changed as required.  There are 30, 60, and 90 minute settings
available.  Adjust only if geographical conditions, outdoor humidity, or other adverse conditions make it necessary.  The
maximum defrost time is 10 minutes. Most defrost cycles are shorter.

Run Time Adjustment

1. Disconnect power to outdoor unit.
2. Move the defrost time adjustment pin from 30 minutes

to 60 minutes or 90 minutes as required.

3. Reconnect the electrical power.

Rapid Advance

When servicing the unit, it may be necessary to rapidly
advance the system through a defrost cycle.  To perform a
rapid advance:

1. Ensure the 24VAC power is ON.
2. Place

 

the defrost time adjustment pin on “TEST”.

NOTE:  

If the outdoor coil temperature is above 30°F,

place a jumper wire between the “DFS” terminals

(defrost sensor) on the defrost control before placing

defrost time adjustment pin on “TEST”.

3. Reconnect electrical power to outside unit.
4. Place

 

the system into heating operation.

The defrost board function will speed up when the test pins
are connected.  Time between defrosts will be 14 seconds.
Defrost time will be 6.5 seconds.
After servicing is completed, disconnect the power, move
the Defrost Time Select Tab back to 30, 60, or 90, remove
jumper wire on DFS, and reconnect the power.

NOTES:

1.

If the time select tab remains in TEST position for five

(5) minutes, the control will ignore TEST mode and

assume a normal defrost cycle.  To override this,

briefly remove and then replace the select tab.

2.

When the unit starts the defrost cycle, quickly re-

move the time select tab to allow normal defrosting

and defrost termination to proceed.  The select tab

can be reconnected to TEST to repeat the defrost

cycle, or the tab can be placed in the desired time

setting.  (Jumping both test pins with a small insu-

lated screw driver will also work.)

Outdoor Thermostat

An outdoor thermostat is used to prevent full electric heater
operation at varying outdoor ambients (0°F to 45°F).  The
contacts of this thermostat are normally open above its set
points and closed below to permit staging of indoor
supplemental heater operation.
If the outdoor ambient temperature is below 0°F (-18°C)
with 50% or higher relative humidity, an outdoor thermostat
(OT) must be installed and set at (0°) on the dial. Failure to
comply with this requirement may result in damage to the
product which may not be covered by the manufacturer’s
warranty.

(QUALIFIED SERVICER ONLY)

When troubleshooting, the first step should always be to check for clean
coils, clean filter(s), and proper airflow. Indoor airflow should be 350 to
450 CFM per ton of cooling, based on the size of the outdoor unit.
If further information is needed, see the Remote Heat Pump Service
Manual or contact your distributor.

Содержание REMOTE HEAT PUMP

Страница 1: ...than when the unit is in operation Remember it is your responsibility to install the product safely and to know it well enough to be able to instruct a customer in its safe use Safety is a matter of...

Страница 2: ...throughout this manual to indicate immediate or potential safety hazards It is the owner s and installer s responsibility to read and comply with all safety information and instructions accompanying...

Страница 3: ...nce and service If possible discuss unit location with the owner before proceeding This unit is for outdoor installation only It cannot be completely enclosed Refer to Figure 1 for clearances from the...

Страница 4: ...Avoid burying refrigerant lines If you must bury them first dig the trench so it gradually slopes toward the compressor at least 1 inch per 10 feet Then insulate the liquid and suction lines separatel...

Страница 5: ...Never sniff a refrigerant Never purge refrigerant into an enclosed room or space In fact all refrigerants must BY LAW be reclaimed If an indoor leak is suspected thoroughly ventilate the area before...

Страница 6: ...a minimal amount on the line coming from the nitrogen cylinder 4 Open the high pressure valve on the gauge mani fold Pressurize the refrigerant lines and the indoor coil to 150 psig 1034 kPA To reach...

Страница 7: ...ylinder 6 Evacuate the system to about 29 inches Hg as mea sured by the compound low side gauge 7 Open the valve to the thermocouple vacuum gauge Evacuate until the gauge reads 250 microns or less 8 C...

Страница 8: ...e drop to a maxi mum of 2 from the main breaker or fuse panel to the outdoor unit A thermostat is required 1 To connect the unit to the power supply route the power supply and ground wires through the...

Страница 9: ...compressor damage and will void the warranty Most portable machines cannot clean used refrigerant well enough to meet this ARI Standard IMPORTANT If adding additional refrigerant to a system add only...

Страница 10: ...chart shows a superheat of 20 F is ideal for these conditions Since our superheat is 30 20 10 F higher than ideal charge must be added If the system is performing properly reinstall the service port c...

Страница 11: ...fter servicing is completed disconnect the power move the Defrost Time Select Tab back to 30 60 or 90 remove jumper wire on DFS and reconnect the power NOTES 1 If the time select tab remains in TEST p...

Страница 12: ...ITE GREEN TYPICAL H P ROOM THERMOSTAT SYSTEM COMPOSITE DIAGRAM 18 60 ABOVE 10 KW HEAT PUMP B L U E W H I T E C W2 R E D Y O R R Y C O W2 18 GA 7 WIRE R G E R INDOOR UNIT R RED 2 1 OT 1 OT 2 3 EHR 1 2...

Страница 13: ...14 Does the compressor sound normal 15 Check the amperage on the indoor blower motor Is it within the limits shown on the nameplate of the motor 16 Are all access panels installed and secured 17 Do c...

Страница 14: ...14 2003 2004 Goodman Company L P August 2004...

Отзывы: