7) WIRING DIAGRAMS

• 

HP/CON Option

 = “HP” position (default) is for heat 

pumps, and bridges Y and W1 terminals together.  

When set to “CON” the Y and W1 terminals operate 

independently for conventional systems.

• 

B/O Option

 = “B” setting (default) means the shared 

B/O terminal is energized while in Heat mode and off 

in Cool. “O” setting means the shared B/O terminal is 

energized while in Cool mode and off in Heat.

B (top two)

O (lower two)

HP (right two)

CON (left two)

Back of thermostat circuit board

HP (right two)

CON (left two)

Back of thermostat circuit board

For Heat Pump applications, the options below can be 

left per the factory defaults.

For Conventional (cooling) applications, the option 

below will need to be adjusted or confirmed during the 

install.

B/O

R

Y

W1
W2

GH

GL

C

HP Reversing Valve

Heat Pump Compressor

Blower Fan (High Speed)

Blower Fan (Low Speed)

AMANA PHWT-A150H

THERMOSTAT

24V Power

Auxiliary/Emerg Heat

 *see note 2

 *see note 3

24V Common

NOT USED *

* note 1: WHEN USED FOR

HEAT PUMP, THE Y & W1

TERMINALS ACT AS ONE

B/O

R

Y

W1
W2

GH

GL

C

NOT USED

NOT USED

A/C Cooling

Blower Fan (High Speed)

Blower Fan (Low Speed)

AMANA PHWT-A150H

THERMOSTAT

24V Power

Hea�ng Stage-1

24V Common

**see note 2

**see note 3

UP TO 2H/1C HEAT PUMP APPLICATIONS:

(AMANA PTH & HEH PTAC MODELS):

UP TO 1H/1C CONVENTIONAL APPLICATIONS:

(AMANA PTC PTAC MODELS)  **see note 1

* HEAT PUMP WIRING DIAGRAM NOTES:

•  Note 2: The “W2” terminal is used to call for Electric/

Auxiliary heat. If your Heat Pump PTAC does not have 

Electric heat, then the “W2” terminal should not 

be used and Installer Settings menu 10 (Aux. Stage 

Offset) should be set to “OFF”.

•  Note 3: For PTAC units with only one fan speed 

(single “G” fan wire), add a jumper wire (installer 

provided) to bridge together “GH” and “GL”.  Connect 

your fan wire to either terminal after jumper wire has 

been added.

** CONVENTIONAL WIRING DIAGRAM NOTES:

•  Note 1: For Conventional (cooling) PTAC units, 

Installer Settings menu 06 (System Type) must be set 

to “Con”.

•  Note 2: If connecting to a Conventional PTAC unit 

without electric heat, the W1 and W2 wire terminals 

will not be used and Installer Settings menu 03 

(Available Modes) should be set to “04: Cool Only”

•  Note 3: For PTAC units with only one fan speed 

(single “G” fan wire), add a jumper wire (installer 

provided) to bridge together “GH” and “GL”.  Connect 

your fan wire to either terminal after jumper wire has 

been added.