7) WIRING DIAGRAMS
•
HP/CON Option
= “HP” position (default) is for heat
pumps, and bridges Y and W1 terminals together.
When set to “CON” the Y and W1 terminals operate
independently for conventional systems.
•
B/O Option
= “B” setting (default) means the
shared B/O terminal is energized while in Heat
mode and off in Cool. “O” setting means the
shared B/O terminal is energized while in Cool
mode and off in Heat.
Back of thermostat circuit board
Back of thermostat circuit board
WIRING DIAGRAM NOTES:
For systems that only have one fan speed (only a single
“G” fan wire present), add a jumper wire (installer
provided) to bridge together “GH” and “GL”. Connect
your fan wire to either terminal after jumper wire has
been added.
For Conventional (cooling) applications, the options
below can be left per the factory defaults.
WIRING DIAGRAM NOTES:
For systems that only have one fan speed (only a single
“G” fan wire present), add a jumper wire (installer
provided) to bridge together “GH” and “GL”. Connect
your fan wire to either terminal after jumper wire has
been added.
For Heat Pump applications, the options below will
need to be adjusted or confirmed during the install.
B/O
R
Y
W
GH
GL
C
NOT USED
A/C Cooling
Blower Fan (High Speed)
Blower Fan (Low Speed)
AMANA PHWT-A100C
THERMOSTAT
24V Power
He
ating
24V Common
B/O
R
Y
W
GH
GL
C
HP Reversing Valve
Heat Pump Compressor
Blower Fan (High Speed)
Blower Fan (Low Speed)
AMANA PHWT-A100C
THERMOSTAT
24V Power
NOT USED*
WHEN USED FOR
HEAT PUMP, THE Y & W
TERMINALS ACT AS ONE
24V Common
UP TO 1H/1C CONVENTIONAL APPLICATIONS:
(AMANA PTC PTAC MODELS)
UP TO 1H/1C HEAT PUMP APPLICATIONS:
(AMANA PTH & HEH PTAC MODELS):