Amana PHWT-A100C Скачать руководство пользователя страница 1

AMANA PHWT-A100C THERMOSTAT

1) DESCRIPTION AND COMPATIBILITY

The Amana PHWT-A100C is a non-programmable 

electronic thermostat, which can be used with the 

following heating/cooling applications:
• Cooling/ Conventional PTAC Units (PTC) with or

without Electric Heat

2) SPECIFICATIONS

• Input Voltage: 19 to 30 VAC

• Output Rating: Max. 1.5A per terminal (3A total)

• Temperature Control: 45°F to 90°F (7°C to 32°C)

• Temperature Accuracy: ± 1°F (± 0.5°C)

• Wire Terminals:

24 VAC Common

GL 

Fan LOW Speed

GH 

Fan HIGH Speed

Heating Signal

Cooling Signal

24 VAC Hot

B/O 

Reversing Valve

3) SAFETY INFORMATION

• This thermostat is for LOW voltage applications only.

• Turn OFF electricity to all heating and cooling

components.

• All wiring must conform to applicable local

and national building and electrical codes and

ordinances.

4) TO REMOVE EXISTING THERMOSTAT

1. Write down the letters printed near each wire

terminal that is used, and the color of each wire it

is connected to; self-adhesive wire labels are also

enclosed.

2. Carefully remove wires from existing thermostat

and bend so they cannot fall back into wall or

touch each other.

3. Remove existing thermostat base from the wall.

5) TO INSTALL NEW THERMOSTAT

1. Mount the thermostat on an inside wall about

five feet above the floor in an area that has good

circulation, but is not directly affected by a vent

or duct.

2. If painting or construction is still ongoing, cover

the thermostat completely or wait until work is

complete before mounting thermostat.

3. If new mounting holes are needed, mark the

placement of the new mounting holes through

the thermostat base. Using a 3/16” drill bit,

drill the holes you have marked and insert the

supplied wall anchors.

4. Feed the wires through the wire opening in the

base and use supplied screws to mount base to

the wall.

5. Using Section 7) WIRING DIAGRAMS, wire each

terminal on the new thermostat base. Ensure that

the bare end is fully seated into the connector,

then tighten securely. Pull gently on wires to

ensure they are secure.

6. Place thermostat front back onto the base.

7. Restore power back to heating and cooling

components and thermostat.

8. See Section 8) INSTALLER SETTINGS MENU, to

adjust the required settings needed for each

system type.

PTAC DIRECT SALES, INC.

185 S. Kimball Avenue., Suite 130

Southlake, TX 76092

877.454.7822