Amana MBVC Series Скачать руководство пользователя страница 4

www.amana-hac.com 

SS-AMBVC

p

roduCt

 S

peCifiCatioNS

MBVC B

lower

 p

erforMaNCe

 d

ata

 — d

ipSwitCh

 S

uMMary

Dipswitch #

Function

Default Setting

S1 - S2*

Cooling / HP Airflow 

A/B/C/D

Airflow D

S3 - S4*

Cooling / HP / Aux Trim 

(-10%, 0, +10%)

No Trim

S5 - S6*

Cooling Profile 

A,B,C,D

Profile 1

S7*

Dehum 

(on/off)

Off

S8

Unused

On

S9 - S11

Heater Kit Kw

Off/Off/Off

*   Valid only if the system is wired in legacy mode. If system is wired in the 4-wire communicating mode, 

these functions are selected via the user menu in the CTK01AA T-STAT. 

C

ooliNg

 / hp a

irflow

S1

S2

Speed Tap

MBVC1200 

Airflow (SCFM)

MBVC1600 

Airflow (SCFM)

MBVC2000 

Airflow (SCFM)

off

off

A

600

1000

1200

on

off

B

800

1200

1600

off

on

C

1000

1400

1800

on

on

D

1200

1600

2000

Cooling / HP / Aux Trim

Cooling Profile

S3

S4

Trim Value

S5

S6

off

off

0

off

off

A

on

off

10%

on

off

B

off

on

-10%

off

on

C

on

on

0

on

on

D

h

eater

 K

it

 

K

w a

irflow

S9

S10

S11

Heater KW

MBVC1200 

Airflow (SCFM)

MBVC1600 

Airflow (SCFM)

MBVC2000 

Airflow (SCFM)

off

off

off

21

NA

NA

NA

off

off

on

20

NA

NA

2000

off

on

off

15

1400

1500

1500

off

on

on

10

1000

1000

1200

on

off

off

8

740

1000

1000

on

off

on

6

635

800

800

on

on

off

5

600

800

800

on

on

on

3

600

800

800

Содержание MBVC Series

Страница 1: ...ghts Storage of six prior fault codes Programmable heat strip settings Color coded terminal strip for non communicating set up Cooling and heat pump applications AHRI Certified ETL Listed Cabinet Feat...

Страница 2: ...ower 1 208 230 60 1 Motor Speed Revisions V Variable Speed A First Series C ComfortNet Compatible Circuit Breaker Airflow Delivered A No Circuit Breaker 08 800 CFM B Circuit Breaker 12 1200 CFM 16 160...

Страница 3: ...208 230 1 4 3 15 10 8 73 MBVC1600AA 1 1 600 to 1 000 208 230 1 6 3 15 10 8 83 MBVC2000AA 1 2 000 to 1 200 208 230 1 5 8 15 11 10 95 Minimum Circuit Ampacity MCA and Maximum Overcurrent Protection MOP...

Страница 4: ...menu in the CTK01AA T STAT Cooling HP Airflow S1 S2 Speed Tap MBVC1200 Airflow SCFM MBVC1600 Airflow SCFM MBVC2000 Airflow SCFM off off A 600 1000 1200 on off B 800 1200 1600 off on C 1000 1400 1800 o...

Страница 5: ...6 500 11 029 11 209 20 021 13 178 11 209 23 464 813 16 103 16 16 133 16 11 23 17 21 24 11 11 201 16 Side and Front Views W H 3 KNOCKOUTS 1 125 1 375 1 750 875 KNOCKOUT 2 PLACES C 6 1 2 5 5 1 8 3 1 4 D...

Страница 6: ...Typical Two Stage Cool Two Stage Heat Thermostat Dehumidistat Optional G W1 W2 Y1 Y2 O Y2 W1 W2 Y1 Y2 Remote Condensing Unit Two Stage AC NEU HOT DEHUM C R G R Y1 1 2 R C C Modular Blower Integrated...

Страница 7: ...AGE INTEGRATED CONTROL MODULE TX 3 DEHUM C W1 1 5 FIELD SPLICE W1 CFM LED R Y1 NOTES LOW VOLTAGE 24V 4 GND W1 24 V 3 A 4 RX 2 COLOR CODES Y2 TH STATUS LED 5 TO RECALL THE LAST 6 FAULTS MOST RECENT TO...

Страница 8: ...f Maytag Corporation or its related companies and used under license to Goodman Company L P All rights reserved Our continuing commit ment to quality products may mean a change in specifications witho...

Отзывы: