(Primary Heating for PTC Models; Auxiliary Heating for PTH Models; See below for Power Cord Configuration)
P
roduCT
s
PeCifiCATions
: PTC / PTH m
odels
— e
leCTriC
H
eAT
P
erformAnCe
Voltage
Electric
Heater
Size (kW)
No. of
Stages
Nominal Heating (BTU/h)
Total
Watts ⁶
Total
Amps
Min. Circuit
Ampacity²
MOD ⁴
(amps)
Power
Cord
@ 230V
@ 208V
@ 265V
230/208V
2.5
1
8,500
6,800
- -
2,570 / 2,115
11.2 / 10.1
14.1
15
6-15 P
230/208V
3.5
1
12,000
9,900
- -
3,570 / 2,935
15.5 / 14.1
19.5
20
6-20 P
230/208V
5
1
17,100
14,000
- -
5,070 / 4,160
22.1 / 20.0
27.6
30
6-30 P
265V
2.5
1
- -
- -
8,500
2,570
9.7
12.2
15
7-20 P
265V
3.7
1
- -
- -
12,600
3,770
14.2
17.9
20
7-20 P
265V
5
1
- -
- -
17,100
5,070
19.2
23.9
25
7-30 P
Notes
¹ All 265-volt models must use an Amana® brand sub-base (PTSB4**E) or an Amana® brand hard-wire kit (PTPWHWK4).
² Minimum branch circuit ampacity ratings conform to the National Electric Code; however, local codes should apply.
³ Minimum voltage on 230/208-volt models is 197 volts; maximum is 253 volts. Minimum voltage on 265-volt models is 239 volts; maximum is 292 volts.
⁴ Overcurrent protection for all units without electric heaters is 15 amps. Overcurrent protection on 265-volt models must be cartridge-style time-delay
fuses (included and factory-installed on all Amana® brand 265-volt chassis).
⁵ Heating capacity and efficiency based on unit operation without condensate pump; unit automatically switches to electric heat at approximately 24°F
outdoor ambient.
⁶ Total watts for 15,000 BTU/h models; subtract 20 watts for PT07/09/12
⁷ Specify two-digit heater kW size to complete model number.
⁸ R-410A refrigerant used in all systems.
⁹ All units meet or exceed ASHRAE 90.1 standards.
¹⁰ All units less than 250 volts have a Leak Current Detector Interrupter (LCDI) power cord and meet UL 484 standards.
P
roduCT
s
PeCifiCATions
: PTH m
odels
— r
everse
-C
yCle
H
eATing
P
erformAnCe
Heating
Capacity¹
PTH073G
**AXXX
PTH093G
**AXXX
PTH123G
**AXXX
PTH153G
**AXXX
PTH074G
**AXXX
PTH094G
**AXXX
PTH124G
**AXXX
PTH154G
**AXXX
Voltage ¹, ³
230 / 208
230 / 208
230 / 208
230 / 208
265
265
265
265
BTU/h ⁵
6,800 / 6,800
8,300 / 8,100 11,500 / 11,300 13,800 / 13,600
6,800
8,300
11,400
13,700
Amps ¹⁰
3.9
4.2 / 4.2
5.8 / 5.8
7.0 / 7.0
3.1
3.7
5.0
6.1
Watts ¹⁰
585 / 570
715 / 700
1085 /1035
1350 / 1330
570
715
1080
1340
COP ⁵
3.4 / 3.5
3.4 / 3.4
3.1 / 3.2
3.0 / 3.0
3.5
3.4
3.1
3.0
CFM (Dry)
370
360
370
410
370
360
370
410
COP = Coefficiency of Performance; per AHRI Test Procedures, units are rated for capacities and efficiencies.
Notes
¹ All 265-volt models must use an Amana® brand sub-base (PTSB4**E) or an Amana® brand hard-wire kit (PTPWHWK4).
² Minimum branch circuit ampacity ratings conform to the National Electric Code; however, local codes should apply.
³ Minimum voltage on 230/208-volt models is 197 volts; maximum is 253 volts.
Minimum voltage on 265-volt models is 239 volts; maximum is 292 volts.
⁴ Overcurrent protection for all units without electric heaters is 15 amps. Overcurrent protection on 265-volt models must be cartridge-style time-delay
fuses (included and factory-installed on all Amana® brand 265-volt chassis).
⁵ Heating capacity and efficiency based on unit operation without condensate pump; unit automatically switches to electric heat at approximately 24°F
outdoor ambient.
⁶ Specify two-digit heater kW size to complete model number.
⁷ R-410A refrigerant used in all systems.
⁸ All units meet or exceed ASHRAE 90.1 standards.
⁹ All units less than 250 volts have a Leak Current Detector Interrupter (LCDI) power cord and meet UL 484 standards.
¹⁰ Refer to electric heat performance data for total MCA and recommended overcurrent protection. Amps and Watts notation refers to compressor only.