P
roduct
S
PecificationS
SS-ASZ16
www.amana-hac.com
3
S
PecificationS
ASZ16
0241A
ASZ16
0361A
ASZ16
0481A
ASZ16
0601A
C
ApACitieS
And
R
AtingS
Nominal Cooling (BTU/h)
24,000
36,000
48,000
60,000
Nominal Heating (BTU/h)
24,000
36,000
48,000
60,000
Decibels
72
73
74
75
C
ompReSSoR
RLA
10.3
16.7
21.2
25.6
LRA
52
82.0
96.0
118.0
C
ondenSeR
F
An
m
otoR
Horsepower
1/6
1/6
1/6
1/6
FLA
1
1
1
1
R
eFRigeRAtion
S
yStem
Refrigerant Line Size¹
Liquid Line Size (“O.D.)
⅜”
⅜”
⅜”
⅜”
Suction Line Size (“O.D.)
¾”
⅞”
1⅛”
1⅛”
Refrigerant Connection Size
Liquid Valve Size (“O.D.)
⅜”
⅜”
⅜”
⅜”
Suction Valve Size (“O.D.)
¾”
⅞”
⅞”
⅞”
Valve Connection Type
Sweat
Sweat
Sweat
Sweat
Refrigerant Charge
153
203
263
273
Shipped with Orifice Size
NA
NA
NA
NA
e
leCtRiCAl
d
AtA
Volts / Hz / Phase
208/230-60-1
208/230-60-1
208/230-60-1
208/230-60-1
Minimum Circuit Ampacity ²
13.9
21.9
27.5
33
Max. Overcurrent Protection ³
20
30
40
50
Min / Max Volts
197/253
197/253
197/253
197/253
Power Supply Conduit Size
½” or ¾”
½” or ¾”
½” or ¾”
½” or ¾”
S
hip
W
eight
(
lbS
)
282
282
282
296
¹ Tested and rated in accordance with AHRI Standard 210/240
² Wire size should be determined in accordance with National Electrical Codes; extensive wire runs will require larger wire
sizes
³ Must use time-delay fuses or HACR-type circuit breakers of the same size as noted.
n
oteS
• Always check the S&R plate for electrical data on the unit being installed.
• Installer will need to supply ⅞” to 1⅛” adapters for suction line connections.
• Unit is charged with refrigerant for 15’ of ⅜” liquid line. System charge must be adjusted per Installation Instructions Final
Charge Procedure.
• Installation of these units requires the specified TXV Kit to be installed on the indoor coil. THE SPECIFIED TXV IS DETER-
MINED BY THE OUTDOOR UNIT NOT THE INDOOR COIL.