background image

SYSTEM OPERATION

15

COOLING

The refrigerant used in the system is R-22. It is a clear,
colorless, non-toxic, non-irritating, and non-explosive liquid.
The chemical formula is CHCLF

2

. The boiling point, at

atmospheric pressure is -41.4°F.

A few of the important principles that make the refrigeration
cycle possible are: heat always flows from a warmer to a
cooler body, under lower pressure a refrigerant will absorb
heat and vaporize at a low temperature, the vapors may be
drawn off and condensed at a higher pressure and tempera-
ture to be used again.

The indoor evaporator coil functions to cool and dehumidify
the air conditioned spaces through the evaporative process
taking place within the coil tubes.

NOTE: 

 The pressures and temperatures shown in the

refrigerant cycle illustrations on the following pages are for
demonstration purposes only. Actual temperatures and pres-
sures are to be obtained from the "Expanded Performance
Chart."

Liquid refrigerant at condensing pressure and temperatures,
(270 psig and 122°F), leaves the outdoor condensing coil
through the drier and is metered into the indoor coil through
the metering device. As the cool, low pressure, saturated
refrigerant enters the tubes of the indoor coil, a portion of the
liquid immediately vaporizes. It continues to soak up heat and
vaporizes as it proceeds through the coil, cooling the indoor
coil down to about 48°F.

Heat is continually being transferred to the cool fins and tubes
of the indoor evaporator coil by the warm system air. This
warming process causes the refrigerant to boil. The heat
removed from the air is carried off by the vapor.

As the vapor passes through the last tubes of the coil, it
becomes superheated, that is, it absorbs more heat than is
necessary to vaporize it. This is assurance that only dry gas
will reach the compressor. Liquid reaching the compressor
can weaken or break compressor valves.

The compressor increases the pressure of the gas, thus
adding more heat, and discharges hot, high pressure super-
heated gas into the outdoor condenser coil.

In the condenser coil, the hot refrigerant gas, being warmer
than the outdoor air, first loses its superheat by heat trans-
ferred from the gas through the tubes and fins of the coil. The
refrigerant now becomes saturated, part liquid, part vapor and
then continues to give up heat until it condenses to a liquid
alone. Once the vapor is fully liquefied, it continues to give up
heat which subcools the liquid, and it is ready to repeat the
cycle.

HEATING

The heating portion of the refrigeration cycle is similar to the
cooling cycle. By energizing the reversing valve solenoid coil,
the flow of the refrigerant is reversed. The indoor coil now
becomes the condenser coil, and the outdoor coil becomes
the evaporator coil.

The check valve at the indoor coil will open by the flow of
refrigerant letting the now condensed liquid refrigerant by-
pass the indoor expansion device. The check valve at the
outdoor coil will be forced closed by the refrigerant flow,
thereby utilizing the outdoor expansion device.

The restrictor orifice used with the CA*F, CHPF coils  and the
AR*F air handler  will be forced onto a seat when running in
the cooling cycle, only allowing liquid refrigerant to pass
through the orifice opening. In the heating cycle it will be
forced off the seat allowing liquid to flow around the restrictor.
A check valve is not required in this circuit.

COOLING CYCLE

When the contacts of the room thermostat close making
terminals R to Y & G, the low voltage circuit of the transformer
is completed. Current now flows through the magnetic hold-
ing coils of the compressor contactor (CC) and fan relay
(RFC).

This draws in the normally open contact CC, starting the
compressor and condenser fan motors. At the same time
contacts RFC close starting the indoor fan motor.

When the thermostat is satisfied, it opens its contacts,
breaking the low voltage circuit, causing the compressor
contactor and indoor fan relay to open, shutting down the
system.

If the room thermostat fan selector switch should be set on
the "on" position, then the indoor blower would run continuous
rather than cycling with the compressor.

Heat pumps energize the reversing valve thorough the "O"
circuit in the room thermostat. Therefore the reversing valve
remains energized as long as the thermostat subbase is in
the cooling position. The only exception to this is during
defrost.

DEFROST CYCLE

The defrosting of the outdoor coil is jointly controlled by the
defrost timing board,  defrost (30/60) control, and compressor
run time.

HEATING CYCLE

The reversing valve on the heat pump models is energized in
the cooling cycle through the "O" terminal on the room
thermostat.

These models have a 24 volt reversing valve coil. When the
thermostat selector switch is set in the cooling position, the
"O" terminal on the thermostat is energized all the time.

Care must be taken when selecting a room thermostat. Refer
to the installation instructions shipped with the product for
approved thermostats.

Содержание ASC13018

Страница 1: ...ps with R 22 Refrigerant Blowers Coils Accessories This manual is to be used by qualified professionally trained HVAC technicians only Goodman does not assume any responsibility for property damage or...

Страница 2: ...you assume responsibility for any personal injury or property damage which may result WARNING This unit should not be connected to or used in conjunction with any devices that are not design certifie...

Страница 3: ...s Ensure the pressure rating meets or exceeds 400 lbs When in doubt do not use cylinder WARNING In either of these instances an electrical short between the terminal and the compressor housing may res...

Страница 4: ...ons G S C 13 036 1 A A Brand Name G Goodman Brand Amana Brand Distinctions S Goodman Brand High Feature Set Models A Amana Brand Product Category S Split System Unit Type C Condenser R 22 H Heat Pump...

Страница 5: ...5 tons 024 2 tons 030 2 5 tons 036 3 tons 042 3 5 tons 048 4 tons 060 5 tons 070 5 tons 090 7 5 tons 120 10 tons C KL 036 2 A Electrical Supply Unit Type E CommercialAirConditioner K AirConditioner P...

Страница 6: ...ner K AirConditioner P Heat Pump Product Category C Split System 1 208 230V 60Hz 1ph 2 220 240V 50Hz 1ph 3 208 230V 60Hz 3ph 4 308 415V 50Hz 3ph Revision NominalCapacity 018 1 5 tons 024 2 tons 030 2...

Страница 7: ...n A Initial Release THIS NOMENCLATURE IS TO BE USED AFTER JULY 2006 THIS NOMENCLATURE IS TO BE USED TRHOUGH JULY 2006 A W U F 3642 1 6 A A Electrical Supply Expansion Device Application C Ceiling Moun...

Страница 8: ...21 Furnace Cabinet D Fits 24 1 2 Furnace Cabinet N Does Not Apply Horizontal Slab Coils Expansion Device F Flowrator Revision A Initial Release Nominal Capacity Range 13 SEER 1824 1 1 2 2 tons 3030 2...

Страница 9: ...X X X X X CSR U 1 Hard Start Kit X X X X CSR U 2 Hard Start Kit X X X X CSR U 3 Hard Start Kit X X Model Description ASC13018 ASC13024 ASC13030 ASC13036 ASC13042 ASC13048 ASC13060 OT18 60A Outdoor The...

Страница 10: ...Kit x x OT18 60A Outdoor Lockout Stat OT EHR18 60 Emergency Heat relay kit CSR U 1 Hard Start Kit x x CSR U 2 Hard Start Kit x x x CSR U 3 Hard Start Kit x x Model Description CKL18 CKL24 CKL30 CKL36...

Страница 11: ...ORATOR COIL 1 4 FLARE CONNECTION BULB SUCTION LINE EXPANSION VALVE REMOVE BEFORE INSTALLING EXPANSION VALVE SEAL SUPPLIED W KIT SEAL SUPPLIED W KIT BULB TO BE LOCATED AT 10 OR 2 O CLOCK TAILPIECE 3 8...

Страница 12: ...HERMOSTAT WIRE SHORT CYCLE PROTECTOR YELLOW 1 BLACK 1 Y1 Y2 R1 R2 Y C UNIT TERMINAL BOARD CONTACTOR ASC01A ANTI SHORT CYCLECONTROLKIT Install Line Thermostat Here Install Line Thermostat Here Wire Nut...

Страница 13: ...X X CHPF30306 X X CHPF36426 X X CSCF1824N6 X X CSCF303N6 X X CSCF3642N6 X X X NO HEAT KIT HKR 03 HKR05 C HKR 06 HKR 08 C HKR 10 C HKR 15C HKR 20C HKR 21C HKR3 15 HKR3 20 MBR0800AA 1AA X X X X X MBR12...

Страница 14: ...t the compressorcenter COILS AND BLOWER COILS MBR MBEblowercabinetsaredesignedtobeusedasatwo piece blower and coil combination MBR MBE blower sec tions can be attached to cased evaporator coil This tw...

Страница 15: ...d itcontinuestogiveup heat which subcools the liquid and it is ready to repeat the cycle HEATING The heating portion of the refrigeration cycle is similar to the coolingcycle Byenergizingthereversingv...

Страница 16: ...door Coil Accumulator Bi Flow Filter Dryer Outdoor Coil Thermostatic Expansion Valve Check Valve Reversing Valve De Energized Indoor Coil Accumulator Bi Flow Filter Dryer Outdoor Coil Thermostatic Exp...

Страница 17: ...ng mode the orifice moves back off its seat allowingrefrigeranttoflowunmeteredaround the outside of the orifice EXPANSIONVALVE CHECKVALVEASSEMBLY INCOOLINGOPERATION EXPANSIONVALVE CHECKVALVEASSEMBLY I...

Страница 18: ...ndoor Coil Outdoor Coil Thermostatic Expansion Valve COOLING CYCLE CONDENSING UNIT In the cooling mode the orifice is pushed into its seat forcing refrigerant to flow through the metered hole in the c...

Страница 19: ...elow a specific ambient temperature setting i e break even temperature during heating When used in this manner the Y heat demand is switched to the W1 input to the furnace by the outdoor thermostat an...

Страница 20: ...est Motor Windings S 16 Improper Cooling Anticipator Check Resistance of Anticipator S 3B Shortage of Refrigerant Test For Leaks Add Refrigerant S 101 103 Restricted Liquid Line Remove Restriction Rep...

Страница 21: ...CM Motor Windings 33 S 16D ECM CFM Adjustments 33 S 16E Checking GE X13 Motors 34 S 17 CheckingCompressorWindings 35 S 17A Resistance Test 35 S 17B GroundTest 35 S 17D OperationTest 36 S 18 Testing Cr...

Страница 22: ...nsofundersized wirecancauselowvoltage Ifwiresizeisadequate notify the local power company in regard to either low or high voltage REMOTE CONDENSING UNITS BLOWER COILS VOLTAGE MIN MAX 208 230 198 253 1...

Страница 23: ...TS OPTIONS Troubleshooting Encoded Two Stage Cooling Thermostats Options TEST FUNCTION SIGNAL OUT SIGNAL FAN S T E T S1 S1 S1 S2 S2 S2 S3 S3 S3 R COM LOW SPEED COOL LO SPEED COOL HI SPEED COOL LO SPEE...

Страница 24: ...pproximatelythree minutes before resetting 1 Remove wire from Y1 terminal 2 Wait for approximately four 4 minutes if machine was running With power ON WARNING Line Voltage nowpresent 1 Apply 24 VAC to...

Страница 25: ...relay or contactor S 8 CHECKING CONTACTOR CONTACTS DISCONNECTELECTRICALPOWERSUPPLY WARNING Disconnect Electrical Power Supply 1 Disconnectthewireleadsfromtheterminal T sideofthe contactor 2 With powe...

Страница 26: ...electrical box of any residential condensing unit that has a Copeland Scroll compressor inside Once attached Comfort Alert provides around the clock monitoring for common electrical problems compress...

Страница 27: ...formation Yellow ALERT Locked Rotor 1 Run capacitor has failed Flash Code 4 2 Low line voltage contact utility if voltage at disconnect is low 3 Excessive liquid refrigerant in compressor 4 Compressor...

Страница 28: ...ight dimming within the home Only hard start kits approved by Amana brand or Copeland should be used Kick Start and or Super Boost kits are not approved start assist devices Thedischargecheckvalveclos...

Страница 29: ...o and slowly returnstoinfinity Startcapacitorwithbleedresistorwill not return to infinity It will still read the resistance of the resistor B Shorted indicator swings to zero and stops there replace C...

Страница 30: ...5 at the power connector If no voltage is present 3 Check the unit for incoming power See section S 1 4 Check the control board See section S 40 5 Iflinevoltageispresent reinsertthe5 pinconnectorand...

Страница 31: ...R G Turn power OFF prior to repair Wait 5 minutes after disconnecting power before opening motor Handle electronic motor control with care Motor rocks but won t start Loose motor mount Blower wheel n...

Страница 32: ...wer OFF prior to repair Wait 5 minutes after disconnecting power before opening motor Handle electronic motor control with care Blower won t shut off Current leakage from controls into G Y or W Check...

Страница 33: ...E product uses a General Electric ECMTM motor This motor provides many features not available on the traditional PSC motor These features include ImprovedEfficiency Constant CFM Soft Start and Stop Im...

Страница 34: ...ged electric heat cut jumper PJ4 on the control board S 16E CHECKING GE X13TM MOTORS The GE X13TM Motor is a one piece fully encapsulated 3 phasebrushlessDC singlephaseACinput motorwithball bearing co...

Страница 35: ...otoramperage andwindingtemperature Highmotortemperatureoramper age heats the disc causing it to open breaking the common circuit within the compressor on single phase units Heat generated within the c...

Страница 36: ...thecause for failure is somewhere else in the system B If the compressor fails to start replace COPELAND COMPRESSOR 03 A 12345 L YEAR MONTH SERIAL NUMBER PLANT S 18 TESTING CRANKCASE HEATER OPTIONAL I...

Страница 37: ...he EBTDR board These terminals are used to connect the unused leadsfromtheblowermotorandhavenoaffectontheboard s operation SEQUENCE OF OPERATION This document covers the basic sequence of operation fo...

Страница 38: ...r the first stage heat demand Note If more than two heater elements are on the heater assembly it will contain a second heat sequencer HR2 which will control the 3rd and 4th heater elements if availab...

Страница 39: ...tion 2 1 On a demand for heat the room thermostat energizes W1 and 24Vac is supplied to terminal E W1 of the VSTBinsidetheMBEandAEP units TheVSTBwillturn on the blower motor and the motor will ramp up...

Страница 40: ...contains a second heater element HR1 will contain a second set of contacts M3 and M4 which will close to turn on heater element 2 Note If more than two heater elements are on the heater assembly it w...

Страница 41: ...ion manual suppliedwiththeblowercoil ortheblowerperformancetable in the service manual shows the CFM for the static mea sured Alternately the system CFM can be determined by operat ingtheelectricheate...

Страница 42: ...er test the element for continuity no reading indicates the element is open Replace as necessary S 100 REFRIGERATION REPAIR PRACTICE DANGER Always remove the refrigerant charge in a proper manner befo...

Страница 43: ...e s with the compressor open with the suction line of the comprssor closed or severely restricted WARNING 1 Connect the vacuum pump vacuum tight manifold set with high vacuum hoses thermocouple vacuum...

Страница 44: ...suction valve core remove hose and reinstall both valve core caps 6 Check system for leaks NOTE Thischargingprocedurecanonlybedoneinthe cooling mode of operation Early production a mod els only All mo...

Страница 45: ...needforanexternalcheckvalveandbypassloop Thethreeforceswhichgoverntheoperationofthevalveare 1 the pressure created in the power assembly by the feeler bulb 2 evaporatorpressure and 3 theequivalentpres...

Страница 46: ...le superheat SUPERHEAT ADJUSTMENT The expansion valves used on Amana brand coils are factory set and are not field adjustable If the superheat setting becomes disturbed replace the valve On systems us...

Страница 47: ...flow into an evaporator coil The amount of refrigerant that flows through the capillary tube restrictororificeisregulatedbythepressuredifference between the high and low sides of the system In the coo...

Страница 48: ...OTICE Violation of EPA regulations may result in fines or other penalties Now determine if a burn out has actually occurred Confirm byanalyzinganoilsampleusingaSporlanAcidTestKit AK 3 or its equivalen...

Страница 49: ...line size to 3 8 is critical since an increased refrigerant charge level from having a larger liquidlinecouldpossiblyshortenacompressor slifespan 3 Single Stage Condensing Unit The maximum length of...

Страница 50: ...le 9 Installation Requirements 1 In a completely horizontal installation with a long line set wheretheevaporatorisatthesamealtitudeas orslightly below the condenser the line set should be sloped towar...

Страница 51: ...0 F at any time Wrap the reversing valve with a large rag saturated with water Re wet the rag and thoroughly cool the valve after eachbrazingoperationofthefourjointsinvolved Thewetrag around the rever...

Страница 52: ...oilandthenegativeprobe above the coil 2 A direct reading can be taken of the static pressure drop across the coil 3 Consult proper table for quantity of air STATIC PRESSURE DROP Ifthetotalexternalstat...

Страница 53: ...P2 4 K1 OT NO Y P2 9 CALL FOR 2ND STAGE COMPRESSOR Y2 1 0K G FURN P2 1 C OT C C SECOND STAGE COMPRESSOR OUTPUT G CALL FOR EMERGENCY HEAT W1 FURN W2 HP F1 3A OT NC 24VAC 2ND STAGE COMPRESSOR DEMAND OUT...

Страница 54: ...age Electric Heat RED EMERGENCY HEAT RELAY 1 4 2 BLUE WHITE BLACK BROWN THERMOSTAT OT EHR18 60 2 1 From Air Handler C G W2 R C R W2 O Y From Outdoor Unit C G W2 E R O Y Indoor Thermostat W3 B L U E G...

Страница 55: ...or Unit C G W2 E R O Y Indoor Thermostat W3 W3 B L U E G R E E N W H I T E R E D B R O W N B L U E R E D W H I T E O R A N G E Y E L L O W 15kw and Above with Two OT EHR18 60 s Two Stage Electric Heat...

Страница 56: ...ATOR MOTOR ELECTRONIC BLOWER TIME RUN CAPACITOR SR EM EBTDR RC BK RD BL YL BLUE BLACK RED YELLOW COMPONENT CODE BROWN PURPLE GREEN PU BR GR FEMALE PLUG CONNECTOR MALE PLUG CONNECTOR NOTE 2 TRANSFORMER...

Страница 57: ...G NO K1 USE COPPER OR ALUMINUM WIRE EQUIPMENT GROUND 3 5 2 1 4 TR PC PU L1 L2 BL W BR SR PK G W BR BL PU R BK R R R BK BL BL R 208 240 24V BL R M6 M5 RS2 W BR BL BL L1 L2 BK BK R R Y Y Y M8 M7 BL BL B...

Страница 58: ...ATIONS CONNECT THERMOSTAT TO Y Y2 ONLY TAPE OR REMOVE Y1 CONNECTION CONNECT CONDENSING UNIT TO YCON C 6 RED WIRES TO BE ON TRANSFORMER TERMINAL 3 FOR 240 VOLTS AND ON TERMINAL 2 FOR 208 VOLTS 1 FOR HE...

Страница 59: ...DENSER COM W2 O ED W1 OUTDOOR HEATPUMP W W2 R W BL OTC OT1 C OT2 O E W1 BR BL Y BL Y YCON TO CONDENSER C PL2 3 1 2 BR Y W BL BR R PK G Y1 C W2 R TO Y Y2 G EM BK R G BL 4 5 6 7 8 9 W R R BL COM BL 5 TR...

Страница 60: ...r 240 volts and on terminal 2 for 208 volts 2 See composite wiring diagrams in installationinstructions for proper low voltage wiring connections Notes DELAY RELAY RELAY EVAPORATOR MOTOR ELECTRONIC BL...

Отзывы: