Installation Instructions
Duct Length
Maximum allowable duct length is 60 equivalent feet.
• Use
Recommended Standard Fittings in figures below
to calculate duct length.
• Flexible duct is not recommended. However, if it is
used, one foot is equal to two feet of smooth metal
duct.
Recommended Standard Fittings
3¼
x 10 inch to 6 inch
transition = 4½ equivalent
feet
3¼
x 10 inch to 6 inch
transition = 5 equivalent
feet
6 inch to 3¼
x 10 inch
transition = 9 equivalent
feet
6 inch 90 degree elbow
= 5 equivalent feet
6 inch 45 degree elbow =
2½ equivalent feet
6 inch to 3¼
x 10 inch
transition = 1 equivalent
foot
3¼
x 10 inch 90 degree
elbow = 5 equivalent feet
3¼
x 10 inch wall cap
(Unrestricted) =
0 equivalent feet
6 inch wall cap (Unrestricted) = 0 equivalent feet
Anti-tip Bracket Installation
To reduce risk of range tipping, secure range with a
properly installed anti-tip devise packed with range.
1. Measure 5
1
/
8
inches from back wall on right and left
side of cabinet cutout. Mark measurements on floor
and draw a straight line connecting marks.
2. Position anti-tip bracket.
• If range is installed beside cabinet(s), place anti-
tip bracket with inside edge over line drawn on
floor and end of bracket against cabinet.
• If range is not installed beside cabinet(s), position
range where it will be installed. Draw a line along
side of range on floor from front to back. Remove
range. Place anti-tip bracket with inside edge over
line drawn 5
1
/
8
inches from back wall and end of
bracket over line drawn along side of range on
floor.
• Anti-tip bracket can be installed on either right or
left side.
3. Mark 2 hole locations in anti-tip bracket.
4. Drill 2 holes.
• If drilling into wood, use a
3
/
32
inch drill bit.
• If drilling into concrete, use a
3
/
16
inch masonry drill
bit and insert plastic anchors.
5. Secure bracket to floor using screws supplied.