background image

7

CONSTANT TORQUE (EEM) MOTORS

ACNF25 and ACNF31 models utilize constant torque (EEM) mo-
tors.  These motors come with a separate control box which is
mounted on the side of the unit as shown in Figure 8.  The har-
ness from the motor is inserted into the control box which has
another harness leading into the control panel of the unit.

Control Box

Figure 8

The high voltage wiring is the same as the other ACNF models.

The low voltage wiring connections for the ACNF25 and ACNF31
models are shown in Figure 9.  The wire from the motor, T2 (purple,)
T3 (pink) or T4 (yellow), connects to “Y” from the thermostat/con-
denser depending on the application.  The rest of the connections
are similar to the other ACNF models.

Thermostat 

Air Handler 

Condensing Unit 

#18 Gauge 
24 VAC 

#18 Gauge 

24 VAC 

Note: Connect T2,T3 or T4 to the Y 
terminal to the outdoor unit.

 

T1

T5

CONFIRM SPEED TAP SELECTED (T2, T3, OR T4)

IS APPROPRIATE FOR THE APPLICATION BASED ON THIS TABLE.

WIRE COLOR
PURPLE
PINK
YELLOW

BTU
18000
24000

h

HIGH CFM OPTION

Figure 9

MAINTENANCE

Room Thermostat

The room thermostat controls the operation of your heating and/
or cooling unit. It senses the indoor temperature and signals the
equipment to start or stop maintaining the temperature you have
selected for your comfort. The room thermostat should be in a
central, draft free inside wall location for best operation. Do not
place any heat producing apparatus such as lights, radio, etc.,
near the thermostat as this will cause erratic operation of the
comfort system.

Air Filter(s)

All central air moving comfort systems must include air filter(s).
Locate these filters in either the equipment or return air duct sys-
tem upstream of the equipment. The filter(s) removes dust and
debris from the air thus helping to keep your conditioned space
clean. More important, the filter keeps dust and debris from col-
lecting on heat transfer surfaces thus maintaining optimum equip-
ment efficiency and performance. Inspect and clean or replace
filters every month. This routine maintenance procedure will pay
big dividends in reduced operating cost and reduced service ex-
pense. Never operate comfort equipment without filter(s).

Fuses and/or Circuit breakers

This comfort equipment should be connected to the building elec-
tric service in accordance with local and National Electric codes.
This electrical connection will include over current protection in
the form of fuses or circuit breakers. Have your contractor iden-
tify the circuits and the location of over current protection so that
you may be in a position to make inspections or replacements in
the event the equipment fails to operate. Keep replacement fuses
of the proper size on hand.

Periodic Checkup and Service

This unit is designed to provide many years of dependable, trouble-
free comfort when properly maintained. Proper maintenance will
consist of annual checkups and cleaning of the internal electrical
and heat transfer components by a qualified service technician.
Failure to provide periodic checkup and cleaning can result in
excessive operating cost and/or equipment malfunction.

Aluminum Indoor Coil Cleaning (Qualified Servicer Only)

This unit is equipped with an aluminum tube evaporator coil.
The safest way to clean the evaporator coil is to simply flush the
coil with water. This cleaning practice remains as the recom-
mended cleaning method for both copper tube and aluminum
tube residential evaporator coils.
It has been determined that many coil cleaners and drain pan
tablets contain corrosive chemicals that can be harmful to alu-
minum tube and fin evaporator coils. Even a one-time applica-
tion of these corrosive chemicals can cause premature alumi-
num evaporator coil failure. Any cleaners that contain corrosive
chemicals including, but not limited to, chlorine and hydroxides,
should not be used.
An alternate cleaning method is to use one of the products listed
in TP-109* to clean the coils. The cleaners listed are the only
agents deemed safe and approved for use to clean round tube
aluminum coils. TP-109 is also available on the web site in Part-
ner Link > Service Toolkit.

NOTE: Ensure coils are rinsed well after use of any chemical clean-
ers.

Содержание ACNF180 Series

Страница 1: ... DAMAGE ARISING FROM IMPROPER SERVICE OR SERVICE PROCEDURES IF YOU SERVICE THIS UNIT YOU ASSUME RESPONSIBILITY FOR ANY INJURY OR PROPERTY DAMAGE WHICH MAY RESULT IN ADDITION IN JURISDICTIONS THAT REQUIRE ONE OR MORE LICENSES TO SERVICE THE EQUIPMENT SPECIFIED IN THIS MANUAL ONLY LICENSED PERSONNEL SHOULD SERVICE THE EQUIPMENT IMPROPER INSTALLATION ADJUSTMENT SERVICING OR REPAIR OF THE EQUIPMENT SP...

Страница 2: ...lable in cooling capacities of 1 5 2 and 2 5 nominal tons of cooling with a PSC motor ACNF18 ACNF24 and ACNF30 and 2 and 2 5 nominal tons of cooing with a constant torque EEM motor ACNF25 and ACNF31 Electric heat models are available in capacities of 0 5 6 8 and 10 kW The unit is designed to be installed in a horizontal position above a dropped ceiling Do NOT install this unit outside the structur...

Страница 3: ...e A drain trap in a draw through application prevents air from being drawn back through the drain line during fan operation thus preventing condensate from draining and if connected to a sewer line to prevent sewer gases from being drawn into the air stream during blower operation In a blow through application the drain trap prevents conditioned air from escaping It is per missible in this applica...

Страница 4: ... 1 Before locating the unit on the dropped ceiling ensure the strength of the ceiling and beams is adequate to support the weight involved This is an important step and the installers responsibility See the table below for approximate weight of unit MODEL WEIGHT lb 1 5 TON 57 2 TON 64 2 5 TON 68 Table 2 2 Mount the unit in a horizontal position above a dropped ceiling of adequate strength Refer to...

Страница 5: ...ing the serial plate or the finish on the unit Heat trap or wet rags should be used to protect heat sensitive components such as service valves and TXV valves TO PREVENT FEEDER TUBE DAMAGE HOLD THE DISTRIBUTOR BODY WITH A 3 4 OPEN END WRENCH WHEN REMOVING OR REPLACING THE 13 16 FLARE NUT CAUTION 1 Remove the valve core to allow high pressure tracer gas to escape No gas indicates a possible leak 2 ...

Страница 6: ...08 volt wiring For 208V operation move the red wire lead from 240V to 208V tap THERMOSTAT HEAT ANTICIPATOR SETTING ALL MODELS 0 2 MODEL Table 4 Make the following high and low voltage connections at either location to wire units High Voltage Wiring This unit is designed for Single phase 208 230 Volt only Connect the two leads to terminals L1 and L2 on the disconnect in the electrical control secti...

Страница 7: ...ters every month This routine maintenance procedure will pay big dividends in reduced operating cost and reduced service ex pense Never operate comfort equipment without filter s Fuses and or Circuit breakers This comfort equipment should be connected to the building elec tric service in accordance with local and National Electric codes This electrical connection will include over current protecti...

Страница 8: ...fg com or www amana hac com for information on Products Warranties Customer Services Parts Contractor Program and Training Financing Options is a registered trademark of Maytag Corporation or its related companies and is used under license All rights reserved BLOWER CHART FOR ACNF 0 1 0 2 0 3 0 4 0 5 High 710 660 590 515 435 Low 650 595 540 480 390 High 955 880 820 740 675 Low 885 840 775 725 620 ...

Отзывы: