5
4 www.amana-hac.com
SS-AMVM96
P
roduCt
s
PeCiFiCAtions
P
roduCt
s
PeCiFiCAtions
ACVM96 d
iMensions
Model
W
D
H
A
B
C
D
E
ACMV960604CX
21"
28¾"
40¾"
21"
19½”
16⅛"
18"
19½”
ACVM960805DX
24½"
28¾"
40¾"
24½”
23"
20⅝"
21½"
23"
Notes:
• Installer must supply one or two PVC pipes: one for combustion air (optional) and one for the flue outlet (required). Vent pipe must be either 2”
or 3” in diameter, depending upon furnace input, number of elbows, length of run and installation (1 or 2 pipes). The optional Combustion Air
Pipe is dependent on installation/code requirements and must be 2” or 3” diameter PVC.
• Line voltage wiring can enter through the right or left side of the furnace. Low-voltage wiring can enter through the right or left side of furnace.
• Conversion kits for high-altitude natural gas operation are available. Contact your Goodman distributor or dealer for details.
• Installer must supply following gas line fittings, according to which entrance is used:
Left—Two 90º elbows, one close nipple, straight pipe
Right—Straight pipe to reach gas valve
• For bottom return: Failure to unfold flanges may reduce airflow by up to 18%. This could result in performance and noise issues.
LOW VOLTAGE
ELECTRICAL HOLE
28 3/4
3/4
20 1/4
2 1/2
AIR INTAKE PIPE
2" PVC
LEFT SIDE
DRAIN LINE
HOLES
DRAIN
TRAP
C
L
28 5/16
11 1/2
9 13/16
15 1/2
UNFOLDED FLANGES
1 3/4
18 5/8
2 5/8
HIGH VOLTAGE
ELECTRICAL HOLE
20 5/32
AIR
DISCHARGE
LEFT SIDE
VIEW
3/4
2 1/16
2
UNFOLDED FLANGES
DISCHARGE
CONDENSATE
DRAIN TRAP
w/ 3/4" PVC
DISCHARGE
(RIGHT OR
LEFT SIDE)
40
8 1/4
FOLDED FLANGES
(RETURN)
3/4
HIGH VOLTAGE
ELECTRICAL HOLE
LOW VOLTAGE
ELECTRICAL HOLE
RIGHT SIDE
DRAIN LINE
HOLES
ALTERNATE
VENT/FLUE
LOCATION
VENT/FLUE PIPE
2" PVC
11 5/8
ALTERNATE
AIR INTAKE LOCATION
9 3/4
DRAIN
TRAPC
L
6 1/8
7 3/8
AIR
DISCHARGE
2 5/8
ALTERNATE GAS
SUPPLY HOLE
RIGHT SIDE
VIEW
FRONTVIEW
4 1/8
1 3/4
28 5/16
18 13/16
19 7/8
14
STANDARD GAS
SUPPLY HOLE
FOLDED FLANGES
2 11/16
A
B
C
D
E
FOLDED FLANGES
UNFOLDED FLANGES
UNFOLDED FLANGES
FOLDED FLANGES
M
iniMuM
C
leArAnCes
to
C
oMbustible
M
AteriAls
Position
Sides
Rear
Front
Bottom
Flue
Top
Downflow
0”
0”
3”
NC
0”
1”
Horizontal
6”
0”
3”
C
0”
6”
C = If placed on combustible floor, the floor MUST be wood ONLY.
NC = For installation on non-combustible floors only. A combustible floor sub-base must be used for installations on combustible flooring.
Notes
• For servicing or cleaning, a 24” front clearance is required.
• Unit connections (electrical, flue and drain) may necessitate greater clearances than the minimum clearances listed above.
• In all cases, accessibility clearance must take precedence over clearances from the enclosure where accessibility clearances are greater.