background image

DC Backup UPS

Application, Maintenance and Installation Manual

Revision 1

6

Installation

Fit this unit in locations where personnel access is restricted. Personnel with access must be trained in 
electrical safety and be familiar with procedures for avoiding electrical shock. 

Allow room in 19 inch rack for airflow around case.

Wiring

AC input

Unit must be connected to mains earth. 
Provide external protection, as 

there is no AC fusing inside unit

DC output

DC output wiring size should comply with wiring codes. 
We recommend 1.5mm up to 17Ah, 2.5mm for 40Ah. (keep wiring short)
Connection of the output is from terminal block,  E  --.
To install as earthed supply connect  or – to earth.
To install as a floating supply, connect two 10k/1/2W resistors external to the 
unit(see diagram). Fit one resistor from ground to + terminal and the other from 
ground to the – terminal. 

Batteries

Units are shipped without batteries. On commissioning, check that the fuse is 
removed and connect the batteries as follows: 
1/ connect RED wire to +ve terminal of battery 1. 
2/ connect BLACK wire to –ve terminal of battery 2. 
3/ Fit fuse.
Replacement of batteries follows the same procedure.

Remote 
monitoring

Remote wiring should be 0.75mm sq.
Wiring plugs into front of unit. The voltage-free contacts are clearly labelled. 

Connections for remote monitoring are given in the table below.

Connector pin 
number

Function - Analog version
Relay contacts

6 connector top

Common 

charger monitor

5

Closed for charger OK, opens on fail

4

Open for OK, closes on fail 

3

Common 

battery low

2

Closed for batt OK, opens on low

Open for OK, closes when low

Mounting dimensions for the 7021 and 7025  range of DCUPS are given in the attached drawing.

7

Maintenance

There is no routine maintenance required on the 7021 and 7025 series DC backup units. However, it is 
recommended that the battery capacity be verified yearly with a non-critical load, to ensure adequate 
performance during power outages.

18/10/06

7021 and 7025_manual1.doc

Page 6 of 7

WARNING

Take care when inserting batteries, as the batteries contain hazardous energy levels 

Do not allow battery terminals to connect in a short circuit.

.

Содержание 7021 Series

Страница 1: ...algen Model 7021 7025 DC Backup UPS Manual Revision 1 Model 7021 and 7025 Series Amalgen Technologies Pty Ltd 43 Anderson road Mortdale NSW 2223 Australia 18 10 06 7021 and 7025_manual1 doc Page 1 of...

Страница 2: ...e of battery when AC returns Amalgen battery management system The above functions are provided in a single unit designed to fit in 19 inch equipment racks Importantly the unit forms a complete soluti...

Страница 3: ...rly in the small price sensitive categories is not straightforward Then there are power spikes and load transients to consider A DC back up system is a good alternative The 7021 and 7025 back up syste...

Страница 4: ...h battery backup An AC rectifier supplies power to the load and doubles as a battery charger There are 3 modes of operation AC power available In this mode the load is supplied from the AC rectifier T...

Страница 5: ...motely via voltage free contacts The following table shows the details CONDITION LOCAL LEDs REMOTE RELAYs Charger OK Green light if OK N O contact closes if OK DC available Green light if Vload over 1...

Страница 6: ...the batteries as follows 1 connect RED wire to ve terminal of battery 1 2 connect BLACK wire to ve terminal of battery 2 3 Fit fuse Replacement of batteries follows the same procedure Remote monitori...

Страница 7: ...Fusing To be provided external to unit IP rating IP20 DC Voltage 12VDC Nominal 9V to 14 Output is floating from earth Current The current ratings of different models given below Charger Type Constant...

Отзывы: