AMALGAMATED INSTRUMENT PM4-SSI Скачать руководство пользователя страница 28

5.36

Clear user scale operation

Display:

CLr U.SCL

Range:

n/a

Default Value:

n/a

The display scaling via the

U.SCL

function operation can be cleared at this function. Pressing the

^

and

v

buttons simultaneously will clear the user scaling and will cause the scaling to revert

to a 1:1 equivalent i.e. equivalent to

INPt

function set to

1

and

SCLE

function set to

1

. Note

that clearing the user scale will not clear any zero or preset operations, the

CLR ZERO

function

must be used to clear any zero offsets. If necessary the preset value can be changed at the

P.SEt

function and the

P

button or remote input used to activate the preset operation to return the

display to the required scaling.

5.37

Two point live input scaling

Display:

USER SCLE

Range:

on

or

OFF

Default Value:

OFF

Allows selection of two point live input calibration to be used when this function is set to

on

.

This method allows scaling without the need to calculate the required scaling from the SSI en-
coder/sensor data.

The

CAL1

and

CAL2

functions described below can then be used to scale the display. If required

the

CAL OFSt

function can be used to make an adjustment to add or subtract an offset value

across the display range. The

CAL1

,

CAL2

and

CAL OFSt

functions will only be seen when

the

USER SCLE

function is set to

on

. Note: the

U.SCL

function must be set to

OFF

when the

USER SCLE

function is used.

5.38

First calibration scaling point

Display:

CAL1

Range:

Any display value

Default Value:

n/a

This method of display scaling is used only when the

USER SCLE

function is set to

on

.

CAL1

and

CAL2

are used together to scale the instruments display, values for both must be set when

using this scaling method.

The

CAL1

function sets the first calibration point for live input calibration. When using this

method a “live” signal input must be present at the input terminals. Note:

CAL1

and

CAL2

can

be set independently i.e. it is not necessary to perform a

CAL2

operation directly after a

CAL1

.

Note that some display rounding may occur if the scaling values entered are larger than the normal
binary or Gray code values.

The procedure for entering the first scaling point is:

1. Ensure that an input signal of a know value from an encoder etc. is present at the input

terminals, this will normally be at the low end of the range.

28 of

36

PM4SSIMAN-2.2-0

Содержание PM4-SSI

Страница 1: ...t Display Controller Operation and Instruction Manual AMALGAMATED INSTRUMENT CO ABN 80 619 963 692 Unit 5 28 Leighton Place Hornsby Telephone 61 2 9476 2244 e mail sales aicpl com au NSW 2077 Australi...

Страница 2: ...Mechanical Installation 4 3 Electrical installation 5 4 Function tables summary of setup functions 8 5 Explanation of functions 12 6 BCD Converter Input Functions 33 7 Specifications 35 8 Guarantee an...

Страница 3: ...BCD input is converted to an SSI output which is then inter preted by the PM4 SSI The SEt OPER setup function is used to select the input type required If the input from a general SSI output device t...

Страница 4: ...option for panel mount instruments Prepare a panel cut out of 45mm x 92mm 1 mm 0 mm see diagram below Insert the instrument into the cut out from the front of the panel From the rear of the instrumen...

Страница 5: ...chapter to confirm proper selection of voltage polarity and input type before applying power to the instrument When power is applied the instrument will cycle through a display sequence indicating the...

Страница 6: ...d by the device being connected to the PM4 Consult the handbook for the SSI device used for details of maximum cable length Notes Twisted pair cable must be used for clock and data refer to the SSI RA...

Страница 7: ...ping screws from the back cover then remove the back cover by pulling it away from the instrument 3 Remove the earth screw which passes through the underside of the case then slide out the board or bo...

Страница 8: ...e delay for the designated alarm relay x 0 to 9999 0 See 4 1 5 4 15 Axrt Reset time delay for the designated alarm relay x 0 to 9999 0 See 4 1 5 5 16 Axn o or Axn c Alarm relay x action to normally op...

Страница 9: ...n low display value Optional Any display value 0 5 19 21 REC Analog output option high display value Optional Any display value 1000 5 20 21 drnd Display rounding 1 to 5000 1 5 21 21 dCPt Decimal poin...

Страница 10: ...input calibration scaling point Any display value n a 5 39 29 CAL OFSt Calibration offset Any display value n a 5 40 29 SEt OPER Set display operation SSI bc8 or bc24 SSI 5 41 30 SSI RAtE SSI clock fr...

Страница 11: ...Record your relay settings in the table below Display Relay 1 Relay 2 Relay 3 Relay 4 Relay 5 Relay 6 Relay 7 AxLo AxHi AxHY Axtt Axrt Axn o or Axn c AxSP or Axt1 etc n a Ax rt Ax tL or Ax PS PM4SSIMA...

Страница 12: ...move power from the instrument Hold in the button and reapply power The display will briefly indicate as part of the wake up messages when the message is seen you can release the button Move to step 2...

Страница 13: ...e on to the next setpoint Note this easy access also functions in the same manner for the PI control setpoint relay and or analog PI output if PI control is available The instrument must be set in the...

Страница 14: ...s Display Value Time A Lo x A HY x value A Lo A HY x x plus Relay activates at this value or below Relay resets above this value Alarm low operation with hysteresis 5 2 Alarm relay high setpoint Displ...

Страница 15: ...t around the setpoint value The hysteresis setting operates as follows In the high alarm mode once the alarm is activated the input must fall below the setpoint value minus the hysteresis value to res...

Страница 16: ...ull time delay will be restored The reset time is selectable over 0 to 9999 seconds To set a reset time value go to the Axrt function and use the or v push buttons to set the value required then press...

Страница 17: ...Display P SEt Range Any display value Default Value 0 Displays and sets the preset value this function will not be seen unless either the R INP or P SEt function is set to P SEt The preset value can...

Страница 18: ...ay scaled differently to the 7 segment display For example the bargraph scale may be indicating percentage fill of a tank whilst the 7 segment display is indicating actual process units To set bargrap...

Страница 19: ...g bAr_ 0 and bAr 100 will give a bargraph with all the bottom half segments lit at a 7 segment display reading of 100 and all the top segments lit with a 7 segment display reading of 100 r dot modulu...

Страница 20: ...ft most digits will be output if set to 0 then the four right most digits will be output 5 17 Digital output option low value Display diG_ Range Any display value Default Value 0 Seen only with the 16...

Страница 21: ...ied when this option is fitted for wiring details and link settings Displays and sets the analog retransmission 4 20mA 0 1V or 0 10V link selectable output high display value 20mA 1V or 10V in display...

Страница 22: ...d Note that the higher the filter setting the longer the display may take to reach its final value when the input is changed similarly the relay operation and any output options will be slowed down wh...

Страница 23: ...manner as the Hi function described above HiLo toggle between Hi and Lo displays This function allows the remote input to be used to toggle between peak and valley memory displays The first operation...

Страница 24: ...access to any functions via FUNC mode entry via CAL mode must be made to gain access to alarm and calibration functions If set to ALL then access to all functions including calibration functions can...

Страница 25: ...e SCLE value to 1500 The display value is calculated in the following manner Display value Value sent from encoder SCLE INPt Example A 12 bit SSI encoder will give an output in the range 0 to 4095 if...

Страница 26: ...the SIGN setting on the values displayed for a given number of input bits 5 32 SSI code type Display SSI CodE Range bin or GRAY Default Value bin The input type can be set to bin for binary or to GRAY...

Страница 27: ...its zero position and a ZERO operation carried out via the remote input or P button The sensor is then moved a known distance and the U SCL operation is carried out via the F button Notes Easy access...

Страница 28: ...he display If required the CAL OFSt function can be used to make an adjustment to add or subtract an offset value across the display range The CAL1 CAL2 and CAL OFSt functions will only be seen when t...

Страница 29: ...mally be at the high end of the range 2 At the CAL2 function press and v simultaneously then release them The display will indicate the live input value Do not be concerned at this stage if the live i...

Страница 30: ...encies The normal setting is Hi Use Lo only if communications difficulties are experienced due to long cable runs 5 43 Baud rate for optional serial communications Display bAUd RAtE Range 300 600 1200...

Страница 31: ...it address for polled POLL or M buS mode 0 to 31 seen only with serial output option Refer to the separate PM4 Panel Meter Optional Output Addendum booklet supplied when optional outputs are fitted Al...

Страница 32: ...Error this message means that an error occurred whilst attempting to scale the display Check that the sensor is connected correctly and that the scaling method was followed correctly 32 of 36 PM4SSIMA...

Страница 33: ...gured through a push button sequence Refer to the diagram on page 10 for details on accessing setup functions Explanation of functions SEt bcd select input mode This function is used to select the inp...

Страница 34: ...llow a 2 digit display SEt OPER set operation mode Allows selection of one of the three main operation mode Select SSI if the input is an SSI signal binary or Gray code from encoder etc The remaining...

Страница 35: ...LED display and no optional outputs Typically 50mA at 12VDC and 35mA at 24VDC for PM4 with LCD display and no optional outputs actual current drawn depends on display type and options fitted Output st...

Страница 36: ...the manu facturer freight paid and if accepted for free repair will be returned to the customers address in Australia free of charge When returning the product for service or repair a full description...

Отзывы: