Use the panel installation guide to verify proper system setup.

The Home Disaster 

is an integrated environmental sensor

that detects flood and extreme temperature conditions.  

Features

Titanium probes for unmatched corrosion immunity

Detects flood, freeze, and heat conditions

Secure encrypted wireless transmissions

5-year warranty

Enroll

 the flood sensor (ID ending in 0) by placing the

panel into wireless enrollment mode and then sending an 

enrollment signal from the sensor. 

Options for Sending an Enrollment Signal

Remove the battery tab and cover to trip tamper

Freeze & heat inputs must be enabled as additional 

zones to function. Activate only the zones needed in 

order to extend battery life. 

To activate and enroll a freeze input (ID ending in 1):

Remove magnet from reed switch

Hold down tamper and install battery

To activate and enroll a heat input (ID ending in 2):

Have magnet next to reed switch

Hold down tamper and install battery

Install 

by placing the remote flood probe in the location

requiring flood or leak detection.  If desired, the flood 

probe can be screwed to the floor or baseboard.  Next, 

mount the sensor to the wall using the mounting screw 

locations.  Finally, connect the flood probe wires to the 

sensor’s terminal blocks.  

Detects

 

water pooled under the sensor and reports extreme

temperature conditions.

Default Temperature Trip Points

Heat alarms when over 100°F (38°C)

Heat restores when under 97°F (36°C)

Freeze alarms when under 45°F (7°C)

Freeze restores when over 48°F (9°C)

RE319 Home Disaster

DSC

®

 Compatible

IN

ST

A

LL

G

U

I

D E

I

Mounting

Screw

Holes

Wire

Entry

Hole