Installation Instructions:

Unit should be installed in accordance with The National Electrical Code and all applicable Local Regulations.
1.  Remove back plate inside the enclosure by removing four (4) mounting screws (Figs. 2a-7a, pgs. 5-10 ).
2.  Mark and drill desired knockouts on the enclosure to facilitate wiring. For suggested wire entry locations 
 

refer to Fig. 1, pg. 4. Use weather tight NEMA 4 rated connectors, bushings, and cables.

3.  Unit can be wall or pole mounted.
 

Wall Mount:

 

 

- Mark and drill holes to line up with the top and bottom holes of the enclosure flange. 

 

 

- Secure enclosure with appropriate fasteners (Fig. 9 and Fig. 9a, pg. 11).      

 

Pole Mount:

 

 

- Refer to the detailed pole mount instructions (pg. 11).

 

Secure enclosure to earth ground.

4.  Set power switch on power distribution board marked [PD] to OFF position for models WPTV248UL or
 WPTV248ULCB 

(Figs. 2b, 3b, pgs. 5, 6). Set power disconnect circuit breaker to OFF position for all 

 

other models (Figs. 4b-7b, pgs. 7-10).

5.  All units are factory set for 24VAC operation. 
 

For 28VAC operation adjust unit prior to mounting and applying power as follows: 

 

Change the wire position so that the black wire [28V] is connected to the terminal marked [P] and the 

 

yellow wire [24V] is connected to the terminal marked [S].

 

Note: WPTV248ULCB set for 28VAC operation is not Class 2, not power-limited.

6.  Place back plate with all internal parts, using four (4) screws, back into WP enclosure (Figs. 2a-7a, pgs. 5-10).
7.  Connect AC power to the black and white flying leads of the transformer(s) (Figs. 2-7, pgs. 5-10),
 

secure green lead to earth ground. Use 18 AWG or larger for all power connections.

 

Keep power-limited (PTC protected outputs only) wiring separate from non power-limited wiring. 

 

Minimum 0.25” spacing must be provided. Use separate entries.

8.  Set power switch on power distribution board marked [PD] to ON position for models WPTV248UL or
 WPTV248ULCB 

(Figs. 2b, 3b, pgs. 5, 6). Set power disconnect circuit breaker to ON position for all 

 

other models (Figs. 4b-7b, pgs. 7-10).

9.  Measure output voltage before connecting devices. This helps avoiding potential damage.
 

Terminals marked [1P - 8P] are of the same polarity.

 

CAUTION: Determine the maximum operating voltage of the equipment being powered before 

 

adjusting the output voltage.

10.  Set power switch on power distribution board marked [PD] to OFF position for models WPTV248UL or 
 WPTV248ULCB 

(Figs. 2b, 3b, pgs. 5, 6). Set power disconnect circuit breaker to OFF position for all 

 

other models (Figs. 4b-7b, pgs. 7-10).

11.  Connect devices to terminals marked [1P - 1N] through [8P - 8N] on PD8/PD8CB board 
 

(Figs. 2-7, pgs. 5-10), carefully observing polarity.

12.  Set power switch on power distribution board marked [PD] to ON position for models WPTV248UL or    
 WPTV248ULCB 

(Figs. 2b, 3b, pgs. 5, 6). Set power disconnect circuit breaker to ON position for all 

 

other models (Figs. 4b-7b, pgs. 7-10).

13.  Green LED will illuminate when power is present.
14.  Upon completion of wiring, secure enclosure door with the cam lock (supplied).
 

Caution: Equipment to be installed/serviced by authorized/trained personnel only. 

 

Shut branch circuit power before installing/servicing equipment.

WARNING: This installation should be made by qualified service personnel. Unit should be installed in 
accordance with the National Electrical Codes and all local codes. For continued protection against risk 
of fire replace all fuses only with the same type and rating (3.5A/250VAC).

Terminal Identification:

PD8 - Power Distribution Module

Terminal Legend

Function/Description

1P - 8P

AC output.

1N - 8N

AC output.

Содержание WPTV248175UL

Страница 1: ... WPTV248175UL 24VAC 7A 175VA or 28VAC 6 25A 175VA Eight 8 Protected Outputs WPTV248300UL 24VAC 12 5A 300VA or 28VAC 10A 280VA Eight 8 Protected Outputs WPTV248ULCB 24VAC 3 5A 85VA or 28VAC 3A 85VA Eight 8 PTC Protected Outputs WPTV248175ULCB 24VAC 7A 175VA or 28VAC 6 25A 175VA Eight 8 PTC Protected Outputs WPTV248300ULCB 24VAC 12 5A 300VA or 28VAC 10A 280VA Eight 8 PTC Protected Outputs ...

Страница 2: ... 24VAC 3 5A 8 P 2 5A 5A 250V 3 5A 250V 0 9A 28VAC 3A WPTV248175UL 24VAC 7A 8 P 3 5A 3 5A 10A 250V 1 76A 28VAC 6 25A WPTV248175ULCB 24VAC 7A 8 P 2 5A 10A 250V 1 76A 28VAC 6 25A WPTV248300UL 24VAC 12 5A 8 P 3 5A 3 5A 15A 32V 2 7A 28VAC 10A WPTV248300ULCB 24VAC 12 5A 8 P 2 5A 15A 32V 2 7A 28VAC 10A Specifications Agency Listings UL Listed for Commercial CCTV Equipment UL2044 cUL Listed CSA Standard C...

Страница 3: ...utputs only wiring separate from non power limited wiring Minimum 0 25 spacing must be provided Use separate entries 8 Set power switch on power distribution board marked PD to ON position for models WPTV248UL or WPTV248ULCB Figs 2b 3b pgs 5 6 Set power disconnect circuit breaker to ON position for all other models Figs 4b 7b pgs 7 10 9 Measure output voltage before connecting devices This helps a...

Страница 4: ...e exclamation point within an equilateral triangle is intended to alert the user to the presence of important operating and maintenance servicing instructions in the literature accompanying the appliance CAUTION To reduce the risk of electric shock do not open enclosure There are no user serviceable parts inside Refer servicing to qualified service personnel Right Panel Left Panel Suggested Locati...

Страница 5: ...TPUTS N P S 1 2 3 4 5 6 7 8 P N Class 1 Outputs PD8 ON OFF 24VAC or 28VAC Output 1 Follow same procedure using terminals 2P N through 8P N for outputs 2 through 8 Green Ground Wire Input 115VAC 50 60Hz Fig 2a Fig 2b 24VAC or 28VAC fused or PTC protected outputs 1 through 8 Terminal Blocks for Fig 2 ...

Страница 6: ...ough 8P N for outputs 2 through 8 LED INPUT ON OFF MAIN FUSE COMMON POWER OUTPUTS FUSED POWER OUTPUTS N P S 1 2 3 4 5 6 7 8 P N PD8 24VAC Class 2 Not Wet Class 3 Wet 28VAC Class 1 Green Ground Wire Input 115VAC 50 60Hz Fig 3a Fig 3b 24VAC or 28VAC fused or PTC protected outputs 1 through 8 Terminal Blocks for Fig 3 ...

Страница 7: ...2 3 4 5 6 7 8 P N PD8 24VAC or 28VAC Output 1 Follow same procedure using terminals 2P N through 8P N for outputs 2 through 8 Green Ground Wire Input 115VAC 50 60Hz Illuminated Power Disconnect Circuit Breaker with manual reset Fig 4a Fig 4b 24VAC or 28VAC fused or PTC protected outputs 1 through 8 Terminal Blocks for Fig 4 ...

Страница 8: ...h 8 LED INPUT MAIN FUSE COMMON POWER OUTPUTS FUSED POWER OUTPUTS N P S 1 2 3 4 5 6 7 8 P N PD8 24VAC Class 2 Not Wet Class 3 Wet 28VAC Class 1 Green Ground Wire Input 115VAC 50 60Hz Illuminated Power Disconnect Circuit Breaker with manual reset Fig 5a Fig 5b 24VAC or 28VAC fused or PTC protected outputs 1 through 8 Terminal Blocks for Fig 5 ...

Страница 9: ...T MAIN FUSE COMMON POWER OUTPUTS FUSED POWER OUTPUTS N P S 1 2 3 4 5 6 7 8 P N PD8 PD8 24VAC or 28VAC Output 1 Follow same procedure using terminals 2P N through 8P N for outputs 2 through 8 Green Ground Wire Input 115VAC 50 60Hz Fig 6a Fig 6b 24VAC or 28VAC fused or PTC protected outputs 1 through 8 Terminal Blocks for Fig 6 ...

Страница 10: ...procedure using terminals 2P N through 8P N for outputs 2 through 8 LED INPUT MAIN FUSE COMMON POWER OUTPUTS FUSED POWER OUTPUTS N P S 1 2 3 4 5 6 7 8 P N PD8 24VAC Class 2 Not Wet Class 3 Wet 28VAC Class 1 Green Ground Wire Input 115VAC 50 60Hz Fig 7a Fig 7b 24VAC or 28VAC fused or PTC protected outputs 1 through 8 Terminal Blocks for Fig 7 ...

Страница 11: ... through the locking mechanism on the strap then tighten the screw with flat head screwdriver or 5 16 hex socket driver Fig 10 pg 11 and Fig 12 pg 11 3 Attach the bottom bracket to the enclosure by inserting bolts through the flange of the enclosure and into the bracket tightening bolts with a 7 16 hex socket Fig 11 pg 11 4 Thread the second wormgear quick release strap through the slots on the ba...

Страница 12: ... 567 9056 website www altronix com e mail info altronix com Lifetime Warranty Made in U S A IIWPTV248UL Series H24R MEMBER Enclosure Dimensions H x W x D approximate 12 x 8 x 6 304 8mm x 203 2mm x 152 4mm MOUNTING PANEL GALVANIZED CARBON STEEL SHEET 13 330mm 4 05 103mm 6 152 4mm 8 203 2mm 4 21 107mm 12 305mm 6 7 170mm 9 84 250mm 0 08 2mm 14 355 6mm ...

Отзывы: