WayPoint DC
- 3 -
8. Connect devices to be powered to terminals marked [– DC +] (Fig. 1h, pg. 4).
For auxiliary device connection this output will not be affected by Low Power Disconnect or
Output Disconnect. Connect device to terminals marked [+ AUX –] (Fig. 1f, pg. 4).
9. For Access Control applications batteries are optional. When batteries are not used, a loss of AC will result
in the loss of the output voltage. When the use of stand-by batteries is desired, they must be lead acid or gel
type. Connect battery to terminals marked [– BAT +] (Fig. 1g, pg. 4). Use two (2) 12VDC batteries connected
in series for 24VDC operation (battery leads included) Use batteries - Casil CL1270 (12V/7AH) batteries or
UL recognized BAZR2 batteries of an appropriate rating.
10. Connect appropriate signaling notification devices to AC FAIL & BAT FAIL (Fig. 1b, pg. 4) supervisory
relay outputs.
11. To delay AC reporting for 2 hrs. set dip switch [AC Delay] to OFF position (Fig. 1c, pg. 4).
To delay AC reporting for 1 min. set dip switch [AC Delay] to ON position (Fig. 1c, pg. 4).
12. To enable Output Disconnect set DIP switch [Shutdown] to ON position (Fig. 1c, pg. 4).
To disable Output Disconnect set DIP switch [Shutdown] to OFF position (Fig. 1c, pg. 4).
13. Trigger terminals are end of a line resistor supervised (10k ohms). Opening or shorting trigger terminals
will cause [DC] output to shutdown (Fig. 1d, pg. 4).
14. Place a jumper for non-latching output. A momentary short on these terminals resets output latching
[Trigger EOL Shutdown] (Fig. 1e, pg. 4).
15. Upon completion of wiring secure enclosure door with latches and optional lock.
WARNING: When installing in a non-restricted service area use lock or other fastened means on door
latches. This installation should be made by qualified service personnel and should conform to the
National Electrical Code and all local codes.
LED Diagnostics:
Red (DC)
Green (AC/AC1)
Power Supply Status
ON
ON
Normal operating condition.
ON
OFF
Loss of AC. Stand-by battery supplying power.
OFF
ON
No DC output.
OFF
OFF
Loss of AC. Discharged or no stand-by battery. No DC output.
Terminal Identification:
Terminal
Legend
Function/Description
L, G, N
Connect 120VAC 60Hz to these terminals: L to hot, N to neutral(non power-limited)
(Fig. 1a, pg. 4).
– DC +
(Fig. 1h, pg. 4)
WayPoint102: 12VDC @ 10A continuous output (Non power-limited output).
WayPoint104: 24VDC @ 10A continuous output (Non power-limited output).
Trigger EOL
Supervised
Trigger inputs can be normally open, normally closed from an output circuit
(power-limited input) (Fig. 1d, pg. 4).
NO, GND
RESET
Trigger input latching or non-latching (power-limited) (Fig. 1c, pg. 4).
+ AUX –
Auxiliary power-limited output rated @ 1A (unswitched) (power-limited output)
(Fig. 1f, pg. 4).
AC Fail
NC, C, NO
Indicates loss of AC power, e.g. connect to audible device or alarm panel.
Relay normally energized when AC power is present.
Contact rating 1A @ 30VDC (power-limited) (Fig. 1b, pg. 4).
Bat Fail
NC, C, NO
Indicates low battery condition, e.g. connect to alarm panel.
Relay normally energized when DC power is present. Contact rating 1A @ 30VDC.
A removed battery is reported within 5 minutes.
Battery reconnection is reported within 1 minute (power-limited) (Fig. 1b, pg. 4).
– BAT +
Stand-by battery connections. Maximum charge current 1.54A (non power-limited)
(Fig. 1g, pg. 4).