![Altronix WayPoint DC Series Скачать руководство пользователя страница 3](http://html.mh-extra.com/html/altronix/waypoint-dc-series/waypoint-dc-series_installation-manual_2913621003.webp)
WayPoint DC Series Installation Guide
- 3 -
11. Connect devices to be powered to the terminals marked [– DC +]
(Fig. 2b, pg. 4, Fig. 3b, pg. 5)
.
12. Connect optional stand-by battery to the terminals marked [– BAT +]. Battery leads included.
Enclosure accommodates up to two (2) 12VDC/7AH batteries. If larger batteries are required, they need to
be mounted in a separate NEMA rated enclosure adjacent to the power supply
(Fig. 2b, pg. 4, Fig. 3b, pg. 5)
.
Note:
When batteries are not used, a loss of AC will result in a loss of output voltage.
13. Set power switch, if applicable, to the ON position
(Fig. 2c, pg. 4).
14. Upon completion of the wiring secure enclosure door with latches and optional lock.
CAUTION: Equipment to be installed / serviced by authorized / trained personnel only.
Shut branch circuit power before installing / servicing equipment.
WARNING: When installing in a non-restricted service area, use lock or other fastened means on door
latches. This installation should be made by qualified service personnel and should conform to the
National Electrical Code and all local codes.
LED Diagnostics:
Red (DC)
Green (AC)
Power Supply Status
ON
ON
Normal operating condition.
ON
OFF
Loss of AC. Stand-by battery supplying power.
OFF
ON
No DC output. Short circuit or thermal overload condition.
OFF
OFF
No DC output. Loss of AC. Discharged or no battery present.
Terminal Identification:
Terminal Legend
Function/Description
– DC +
WayPoint3:
12VDC or 24VDC @ 2.5A supply current.
WayPoint5:
12VDC or 24VDC @ 3.5A supply current.
WayPoint7:
12VDC or 24VDC @ 6A supply current.
WayPoint7:
12VDC or 24VDC @ 6A supply current.
WayPoint1012V:
12VDC @ 10A supply current.
– BAT +
Stand-by battery connections. Maximum charge rate 500mA (700mA for WayPoint1012V).
Bottom of Enclosure
Suggested
Locations
for Wiring Inlets
Fig. 1