Vertiline16C Series Installation Guide 

- 3 -

Installation Instructions:

1.  Attach mounting brackets to VertiLine unit for rack or wall mount installation 

(Figs. 4-5, pg. 7)

 

Affix rubber pads to VertiLine for shelf installation 

(Fig. 6, pg. 7)

.

2.  Secure the unit in a rack, mount unit to a wall or place unit on a shelf as desired (unit should be spaced at 

 

least 3” from any video monitors). When installing the unit in a rack allow for one half of a U spacing 

 

above the unit for ventilation.

3.  Plug the grounded AC line cord (included) into the IEC 320 connector of the VertiLine unit 

(Fig. 1f, pg. 4)

 

Insert the plug end of the line cord into a grounded AC receptacle.

4.  Set illuminated master power disconnect circuit breaker to the (ON) position 

(Fig. 3, pg. 6)

.

5.  Select 24VAC or 28VAC power output for cameras 1-16 with the corresponding voltage adjustment 

 switches 

(Fig. 1b, pg. 4)

.

6.  Measure output voltage before connecting cameras. This helps avoiding potential damage.

 

All terminals with common suffix (P) “1P, 2P ...” are the same polarity.

7.  Set illuminated master power disconnect circuit breaker to the (OFF) position 

(Fig. 3, pg. 6)

8.  Connect the power outputs of terminals marked [1P & 1N] to the power inputs of camera 1 

(Fig. 2, pg. 5)

.

 

Repeat this step for each additional camera (Outputs 2-16). After wiring is completed insert terminal block 

 

into the corresponding connector and secure by tightening the screws.

9.  Upon completion of wiring, set illuminated master power disconnect circuit breaker to the ON (RESET) 

 position 

(Fig. 3, pg. 6)

.

10.  The power LEDs (Green) on the faceplate for Outputs 1-16 will illuminate when AC power is present

 

(Fig. 1a, pg. 4).

 If any of these LEDs are off, a loss of AC power output may be due to a blown fuse or a 

 

tripped PTC caused by a short circuit or overload condition. If all of the LEDs are OFF there may be a 

 

complete loss of supply power to the VertiLine unit or the illuminated master power disconnect circuit 

 

breaker is in the OFF position or the main fuse 1-8 or 9-16 is blown 

(Fig. 1c, pg. 4)

.* 

 

To restore the power output for VertiLine16C or VertiLine166C:

 

 

1- Switch corresponding output voltage switch to the OFF position 

(Fig. 1b, pg. 4)

.

 

 

2- Eliminate the trouble condition.

 

 

3- Replace the corresponding automotive blade fuse.*

 

 

4- Switch output voltage switch to the 24VAC or 28VAC position as desired 

(Fig. 1b, pg. 4)

.

 

To restore the power output for VertiLine16CD or VertiLine166CD:

 

 

1- Switch corresponding output voltage switch to the OFF position 

(Fig. 1b, pg. 4)

.

 

 

2- Eliminate the trouble condition.

 

 

3- Allow 1 minute for PTC to cool off.

 

 

4- Switch output voltage switch to the 24VAC or 28VAC position as desired 

(Fig. 1b, pg. 4)

.

*Note: Replace fuses with same type and rating:

 

 

Output fuses are rated @ 3A for all models.

 

 

Main fuse ratings:

 

 

10A for VertiLine16C and VertiLine16CD.

 

 

15A for VertiLine166C and VertiLine166CD.

Automotive

Blade Fuse

Содержание VertiLine16C Series

Страница 1: ...PTC protected outputs VertiLine166CD 24VAC or 28VAC 14A Sixteen 16 PTC protected outputs VertiLine16C Series CCTV Rack Mount Power Supplies Models Include Rev 031808 More than just power TM Installing Company ________________ Service Rep Name ___________________________________ Address ______________________________________________ Phone ___________________ Installation Guide ...

Страница 2: ... Mechanical Units can be rack wall or shelf mounted Modular 1U standard EIA 19 rack mount chassis Enclosure Dimensions H x W x D approx 1 625 x 19 125 x 8 5 41 3mm x 486mm x 216mm Sixteen 16 Output Rack Mount Configuration Reference Chart Altronix Model Number Output Voltage VAC Total Output Current Power Number of Outputs Output Protection Class 2 Rated Power Limited Output protection Current max...

Страница 3: ...k into the corresponding connector and secure by tightening the screws 9 Upon completion of wiring set illuminated master power disconnect circuit breaker to the ON RESET position Fig 3 pg 6 10 The power LEDs Green on the faceplate for Outputs 1 16 will illuminate when AC power is present Fig 1a pg 4 If any of these LEDs are off a loss of AC power output may be due to a blown fuse or a tripped PTC...

Страница 4: ...1 8 1b Output voltage switches Selects 24VAC or 28VAC or OFF for each output 1a LED s 1 16 Power LED indicators 1g IEC 320 Connector 115VAC 60Hz grounded line cord included Fig 1 1e Power Outputs 24VAC or 28VAC 1f Output Fuses Automotive blade fuses VertiLine16C or VertiLine166C rear VertiLine16C VertiLine16CD VertiLine166C or VertiLine166CD front VertiLine16CD or VertiLine166CD rear VertiLine16D ...

Страница 5: ...Fig 2 Typical Hookup 28VAC OFF 24VAC 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 28VAC OFF 24VAC OFF RESET AC POWER 13 14 15 16 N P N P N P N P 9 10 11 12 N P N P N P N P Main Fuse 9 16 5 6 7 8 N P N P N P N P 1 2 3 4 N P N P N P N P Main Fuse 1 8 ...

Страница 6: ...uts powered Circuit breaker tripped Switch not illuminated Power LEDs on faceplate are not illuminated Outputs not powered To reset circuit breaker set power switch to the ON RESET position Fig 3 pg 6 The lightning flash with arrowhead symbol within an equilateral triangle is intended to alert the user to the presence of an insulated DANGEROUS VOLTAGE within the product s enclosure that may be of ...

Страница 7: ...ft Remove Wall Mount Installation 1 Install mounting brackets A on the left and right side of rack chassis using two 2 flat head screws B included Fig 5a 2 Place unit at desired location and secure with mounting screws not included Fig 5b Caution It is necessary to make sure mounting screws are securely fastened to a beam when installing Fig 5 Fig 5a Fig 5b B A Fig 6 Shelf Installation 1 Position ...

Страница 8: ...Notes Altronix is not responsible for any typographical errors 140 58th Street Brooklyn New York 11220 USA phone 718 567 8181 fax 718 567 9056 website www altronix com e mail info altronix com Lifetime Warranty IIVertiLine16C Series K03U MEMBER ...

Отзывы: