ULXB Power Supply/Chargers 

- 3 -

Wiring:

Use 18 AWG or larger for all low voltage power connections.
Note: Take care to keep power-limited circuits separate from non power-limited wiring (120VAC, Battery).

Maintenance:

Unit should be tested at least once a year for the proper operation as follows:

Output Voltage Test:  Under normal load conditions, the DC output voltage should be checked for proper 
   

voltage level.

Battery Test: 

Under normal load conditions check that the battery is fully charged, check specified 

   

voltage (12VDC @ 13.2 or 24VDC @ 26.4) both at the battery terminal and at the 

   

board terminals marked [– BAT +] to ensure that there is no break in the battery 

   

connection wires.

Replacing Batteries: 

Disconnect existing batteries. Connect battery to the terminals marked [– BAT +].

   

Use two (2) 12VDC batteries connected in series for 24VDC operation.

LED Diagnostics 

(AL400ULXB2 and AL600ULXB)

:

Red (DC)

Green (AC)

Red (BAT)

Power Supply Status

ON

ON

ON 

Normal operating condition.

ON

OFF

ON

Loss of AC. Stand-by battery is supplying power.

OFF

ON

OFF

No DC output, Battery Trouble.

OFF

OFF

OFF

Loss of AC. Discharged or no stand-by battery. No DC output.

ON

ON

OFF

Battery missing / Low.

LED Diagnostics 

(AL1012ULXB and AL1024ULXB2)

:

Red (DC)

Green (AC)

Power Supply Status

ON

ON

Normal operating condition.

ON

OFF

Loss of AC. Stand-by is battery supplying power.

OFF

ON

No DC output.

OFF

OFF

Loss of AC. Discharged or no stand-by battery. No DC output.

Terminal Identification:

Terminal Legend

Function/Description

L, G, N

Connect 115VAC to these terminals: L to hot, N to neutral (Fig. 1a, pg. 4).

+ DC – **

AL400ULXB2: 

12VDC @ 4A or 24VDC @ 3A continuous output 

 

(Power-Limited output) (Fig. 1d, pg. 4).

AL600ULXB: 

12VDC or 24VDC @ 6A continuous output 

 

(Non Power-Limited output) (Fig. 1d, pg. 4).

AL1012ULXB: 

12VDC @ 10A continuous output 

 

(Non Power-Limited output) (Fig. 1d, pg. 4).

AL1024ULXB2:  24VDC @ 8A continuous, 10A in alarm (UL1481). 
 

24VDC @ 10A (UL294) (Non Power-Limited output) (Fig. 1d, pg. 4).

AC FAIL
NO, C, NC

Used to notify loss of AC power, e.g.connect to audible device or alarm panel. 
Relay normally energized when AC power is present. Contact rating 1A @ 28VDC. 
AC or brownout fail is reported within 1 minute of event. 
To delay reporting for up to 6 hrs., cut “AC Delay” jumper and reset power to unit 
(Fig. 1b, pg. 4).

BAT FAIL
NO, C, NC

Used to indicate low battery condition, e.g. connect to alarm panel. 
Relay normally energized when DC power is present. Contact rating 1A @ 28VDC. 
A removed battery is reported within 1 minute. 
Battery reconnection is reported within 1 minute.
Low battery threshold: approximately 21VDC (Fig. 1b, pg. 4).

+ BAT – ***

Stand-by battery connections (Fig. 1c, pg. 4).
AL400ULXB2, AL600ULXB, AL1012ULXB maximum charge current 0.7A.
AL1024ULXB2 maximum charge current 3.6A.

**  AL1012ULXB terminals marked [– DC +]
***  AL1024ULXB2 terminals marked [– BAT +]

Содержание ULXB Series

Страница 1: ... a power limited output is required in the end product application the DC output from the power supply must be connected to a separately Listed control unit or accessory board that provides power limited outputs The product s providing the power limited output s must be listed as appropriate for the particular end product application fire alarm burglar alarm access control and wired in accordance ...

Страница 2: ...tand By 500mA Alarm 10A 4 hrs 8A Not evaluated by UL Installation Instructions Wiring methods shall be in accordance with the National Electrical Code NFPA 70 NFPA 72 ANSI the Canadian Electrical Code and with all local codes and authorities having jurisdiction Product is intended for indoor use only 1 Refer to Sub Assembly Installation Instructions for mounting Rev MS020119 2 Set desired DC outpu...

Страница 3: ...ON OFF Loss of AC Stand by is battery supplying power OFF ON No DC output OFF OFF Loss of AC Discharged or no stand by battery No DC output Terminal Identification Terminal Legend Function Description L G N Connect 115VAC to these terminals L to hot N to neutral Fig 1a pg 4 DC AL400ULXB2 12VDC 4A or 24VDC 3A continuous output Power Limited output Fig 1d pg 4 AL600ULXB 12VDC or 24VDC 6A continuous ...

Страница 4: ... Maximal77 BC300 BC400 BC800 Maximal Trove1 and Trove2 Fig 1 ULXB configuration Output Voltage Selection Dip Switch Not applicable for AL1012ULXB and AL1024ULXB2 AL1012ULXB terminals marked DC AL1024ULXB2 terminals marked BAT DC BAT FAIL NC C NO NC C NO BAT AC FAIL DC AC BAT L G N 5A 250V OFF 24V ON 12V 1a 1b 1c 1d 1e ON Altronix is not responsible for any typographical errors 140 58th Street Broo...

Отзывы: