Trove1M1R Installation Guide 

- 3 -

Installing Trove1R into Rack Tower:

Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, and with all local

codes and authorities having jurisdiction. These products are for indoor use only and must be installed within 

the protected premises.

Note:

 First assemble and Install Z Bracket Wire Management Accesory

(refer to Z Bracket Installation pg. 4)

1.  Remove backplane from enclosure prior to installing into rack cabinet 

 

(do not discard hardware).

2.  In order to mount included UL Listed tamper switch (Altronix Model TS112 or

 

 equivalent) turn the enclosure upside down. Punch out the knockout in 

 

designated location, on the back of the unit, from outside of the drawer 

 

(Fig. 1, pg. 3)

. Insert the tamper switch into the knockout from outside of the 

 

drawer with the button facing outwards and spaded connectors inside the drawer.

 

Connect tamper switch wiring to the Access Control Panel input or the 

 

appropriate UL Listed reporting device. 

 

To activate alarm signal open the rack drawer.

3.  Slide the rack enclosure into an open 2U location in the four post rack cabinet.

4.  Utilizing proper fasteners attach front ears to the rack rails.

5.  Attach the rear of the adjustable slides to the rear rails of the rack cabinet with the proper fasteners.

6.  Secure the rack cover 

(Fig. 2a, pg. 3)

 and rack drawer to earth ground 

(Fig. 2b, pg. 3).

7.  Make sure that all internal cofigurations (wiring, voltage selection, switch settings, etc.) are complete before 

 

mounting backplane back into enclosure.

8.  After all components are mounted on the backplane, attach it to the enclosure using included hardware. 

Fig. 1

Back of the drawer,

viewed from outside.

Tamper Switch

mounting location

Fig. 2

Fig. 2a

Fig. 2b

Содержание Trove1M1R

Страница 1: ...n Rev TMR112818 More than just power TM Installing Company ________________ Service Rep Name ___________________________________ Address ______________________________________________ Phone __________...

Страница 2: ...673 1mm Includes tamper switch Altronix Model TS112 or equivalent and cam lock TM1R Altronix Mercury backplane 16 Gauge backplane Dimensions H x W x D 18 5 x 15 25 x 0 3125 469 9mm x 387 4mm x 7 9mm O...

Страница 3: ...into the knockout from outside of the drawer with the button facing outwards and spaded connectors inside the drawer Connect tamper switch wiring to the Access Control Panel input or the appropriate...

Страница 4: ...ed Fig 3 pg 4 2 Attach arms to each other using bolts and lock nuts Fig 3a pg 4 3 Attach the hinge brackets to the ends of arms using bolts and nuts positioning them as shown on Fig 3b pg 4 4 Make sur...

Страница 5: ...ding spacers and fasten screws into spacers Fig 5a pg 5 3 Mount backplane to enclosure with hardware Position Chart for the Following Models Altronix Power Supply Charger or Sub Assembly Pem Mounting...

Страница 6: ...n access controller module over corresponding spacers and fasten screws into spacers Fig 6a pg 6 3 Mount backplane to enclosure with hardware Access Controller Position Chart for the Following Models...

Страница 7: ...Trove1M1R Installation Guide 7 TM1R Backplane Dimensions H x W x D 18 5 x 15 25 x 0 3125 469 9mm x 387 4mm x 7 9mm 15 25 387 4mm 18 5 469 9mm...

Страница 8: ...5mm 1 5 38 1mm 11 175 283 8mm 2 4 61mm 4 57 116 1mm 3 375 85 8mm 26 5 673 1mm 19 482 6mm R 1 27 32 3mm 1 25 4mm 0 55 14mm 3 62 92mm Altronix is not responsible for any typographical errors 140 58th S...

Отзывы: