Installation Instructions for Trove1R:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, and with all local codes and authorities having
jurisdiction. Product is intended for indoor use only.
1. Remove backplane from enclosure prior to installing into rack cabinet
(do not discard hardware).
2. In order to mount included UL Listed tamper switch (Altronix Model TS112
or equivalent) turn the enclosure upside down. Punch out the knockout in designated
location, on the back of the unit, from outside of the drawer (Fig. 3, pg. 3).
Insert the tamper switch into the knockout from outside of the drawer
with the button facing outwards and spaded connectors inside the drawer.
Connect tamper switch wiring to the Access Control Panel input or the appropriate
UL Listed reporting device. To activate alarm signal open the rack drawer.
3. Slide the Trove rack enclosure into an open 2U location in the rack cabinet.
4. Utilizing proper fasteners attach front ears to the rack rails.
5. Attach the rear of the adjustable slides to the rear rails of the rack cabinet with the
proper fasteners.
6.
Mounting Boards and Accessories to TBL1R:
a. Carefully plan the boards’ layout and mark their place(s) on backplane.
b. Drill the backplane in the marked spots using appropriate tools.
c. Attach mounting hardware for the boards and mount boards according to
their
specifications.
d. Make all wire connections between boards prior to mounting backplane into
Trove
rack.
e. Ensure all internal cofigurations (voltage selection, switch settings, etc.) are
completed before mounting backplane back into Trove rack enclosure.
7. After all components are mounted on the backplane, fasten backplane into Trove rack
utlizing supplied mounting hardware.
Fig. 3
Tamper Switch mounting location
Back of the drawer,
viewed from outside.