- 2 -  

Trove PX V Kits Installation Guide

Overview:

Altronix Trove Paxton kits are pre-assembled and consist of Trove2PX2 enclosure/backplane with factory installed Altronix power supply/charger 

and sub-assemblies. They also accommodate up to eight (8) Paxton Net2 Plus modules for up to eight (8) doors in a single enclosure.

Configuration Chart:

Altronix

Model 

Number

220VAC 60Hz Input Current (A)

Power Supply Board Input Fuse Rating

Power Supply Board Battery Fuse Rating

Maximum Supply

Current for Main 

and Aux. Outputs on 

Power Supply board 

and ACM8(CB) Access 

Power Controller’s 

outputs

Nominal DC 

Output 

Voltage

Class 2 Rated Power- Limited Outputs

Fail-Safe/Fail-Secure or  Dry Form “C” Outputs

Additional Fuse or PTC  Protected Outputs

ACM8(CB) Board  Input Fuse Rating

ACM8 Board Output Fuse Rating

ACM8CB Board Output PTC Rating

PDS8 Board Input Fuse Rating

PDS8 Board Output Fuse Rating

PDS8CB Board Input PTC Rating

PDS8CB Board Output PTC Rating

[DC] [Aux]

Output Range  (VDC)

Output Range  (VDC)

T2PXK7F8V

2.5 6.3A/

250V

15A/

32V

24VDC @ 9.7A

20.17-

26.4

20.28-

26.4

8

8

10A/

250V

2.5A/

250V

10A/

32V

3A/

32V

T2PXK7F8DV

P

8

8

10A/

250V

2.5A

9A

2.5A

Installation Instructions:

Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, and with all local codes and authorities having jurisdiction. 

Product is intended for indoor use only. 

1.  Remove backplane from enclosure. Do not discard hardware.

2.  Mark and predrill holes in the wall to line up with the top three keyholes in the enclosure. Install three upper fasteners 

  and screws in the wall with the screw heads protruding. Place the enclosure’s upper keyholes over the three upper 

  screws; level and secure. Mark the position of the lower three holes. Remove the enclosure. Drill the lower holes and 

  install the three fasteners. Place the enclosure’s upper keyholes over the three upper screws. Install the three lower 

  screws and make sure to tighten all screws.

3.  Mount included UL Listed tamper switch (Altronix Model TS112 or equivalent)

  in desired location, opposite hinge. Slide the tamper switch bracket onto the edge

  of the enclosure, approximately 2” from the right side 

(Fig. 1, pg. 2)

  Connect tamper switch wiring to the Access Control Panel input or the appropriate

  UL Listed reporting device. To activate alarm signal open the door of the enclosure.

4.  Mount Paxton Net2 Plus modules to TPX2 backplane, refer to

 page 3

.

5.  Refer to the 

eFlow NBV Power Supply/Charger Installation Guide

 for eFlow104NBV and 

 corresponding 

Sub-Assembly Installation Guides

 for the following models: 

  ACM8(CB), PDS8(CB) and VR6 for further installation instructions. 

Hardware:

Fig. 1

Tamper Switch

(included)

To Access Control Panel or

UL Listed Reporting Device

Edge of

Enclosure

Enclosure

Nylon Spacer |            5/16” Pan Head Screw |         Lock Nut