Overview:

Altronix Trove SALTO kits are pre-assembled and consist of Trove1SA1 or Trove2SA2 enclosure/backplane with factory installed Altronix power 

supply/charger(s) and sub-assemblies. These kits also accommodate various combinations of SALTO modules for up to twelve (12) doors in a 

single enclosure.

Configuration Chart:

Altronix

Model Number

115VAC 60Hz Input Current (A)

Power Supply Board Input Fuse Rating

Power Supply Board Battery Fuse Rating

Nominal DC Output Voltage

Maximum Supply

Current for Main and 

Aux. Outputs on Power 

Supply board and ACM4/

ACM8 Access Power 

Controller’s outputs

Fail-Safe/Fail-Secure or  Dry Form “C” Outputs

Current Per  ACM4/ACM8 Output 

(A)

ACM4/ACM8 Board  Input Fuse Rating

ACM4/ACM8 Board Output Fuse Rating

PDS8 Board Input Fuse Rating

PDS8 Board Output Fuse Rating

Power

Supply 1

Power

Supply 2

Output

Range

(VDC)

Output

Range

(VDC)

T1SAK34

3.5

5A/

250V

N/A

20.19-26.4

24VDC @ 5.6A

4

2.5

10A/

32V

3A/

32V

10A/

32V

3A/

32V

T2SAK78

4.2

5A/

250V

15A/

32V

20.17-26.4

24VDC @ 9.2A

8

2.5

10A/

250V

2.5A/

250V

10A/

32V

3A/

32V

T2SAK7512

6.8

5A/

250V

15A/

32V

20.17-26.4

10.03-

13.2

12VDC @ 9.3A

24VDC @ 9.2A

12

2.5

10A/

250V

2.5A/

250V

10A/

32V

3A/

32V

Installation Instructions:

Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, and with all local codes and authorities having jurisdiction. 

Product is intended for indoor use only. 

1.  Remove backplane(s) from enclosure. Do not discard hardware.

2.  Mark and predrill holes in the wall to line up with the top three keyholes in the enclosure. Install three upper fasteners and screws 

  in the wall with the screw heads protruding. Place the enclosure’s upper keyholes over the three upper screws, level and secure.

  Mark the position of the lower three holes. Remove the enclosure. Drill the lower holes and install the three fasteners. Place the

  enclosure’s upper keyholes over the three upper screws. Install the three lower screws and make sure to tighten all screws.

3.  Mount included UL Listed tamper switch (Altronix Model TS112 or equivalent) in desired location, opposite hinge. Slide the

  tamper switch bracket onto the edge of the enclosure approximately 2” from the right side

 

(Fig. 1, pg. 2)

. Connect tamper switch wiring to the Access Control Panel input or the

  appropriate UL Listed reporting device. To activate alarm signal open the

  door of the enclosure.

4.  Mount SALTO modules to TSA2 backplane, refer to 

pg. 3, 4, 5

.

5.  Refer to the 

ULXB Power Supply/Charger Installation Guide

 for AL600ULXB, AL1012ULXB, 

  AL1024ULXB2 and corresponding 

Sub-Assembly Installation Guides

 for 

  ACM4, ACM8, PDS8, VR6 for further installation instructions. 

Hardware:

Fig. 1

Tamper Switch

(included)

To Access Control Panel or

UL Listed Reporting Device

Edge of

Enclosure

Enclosure

Nylon Spacer |            5/16” Pan Head Screw |         Lock Nut

Содержание Trove T1SAK34

Страница 1: ...ve2 enclosure with TSA2 Altronix SALTO backplane 1 AL1024ULXB2 Power Supply Charger 1 AL1012ULXB Power Supply Charger 1 ACM8 Fused Access Power Controller 1 ACM4 Fused Access Power Controller 1 PDS8 D...

Страница 2: ...ANSI and with all local codes and authorities having jurisdiction Product is intended for indoor use only 1 Remove backplane s from enclosure Do not discard hardware 2 Mark and predrill holes in the...

Страница 3: ...IN2 Fuse PWR1 Altronix PDS8 1 2 3 4 5 6 7 8 Altronix VR6 is mounted under PDS8 A A BAT FAIL NC C NO NC C NO AC FAIL AC DC BAT BAT DC L G N OFF 24V ON 12V ON Altronix AL600ULXB T1SAK34 Configuration o...

Страница 4: ...M PWR2 COM P N Fuse1 Fuse2 Fuse3 Fuse4 Fuse5 Fuse6 Fuse7 Fuse8 IN1 Fuse IN2 Fuse PWR1 1 2 3 4 5 6 7 8 OUTPUT 1 OUTPUT 2 OUTPUT 3 OUTPUT 4 OUTPUT 5 OUTPUT 6 OUTPUT 7 OUTPUT 8 NC C NO COM NC C NO COM NC...

Страница 5: ...T2 OUT3 OUT4 OUT5 OUT6 OUT7 OUT8 Common Power Outputs NEG P N INP1 INP2 DM1 DM2 Common DM2 Common P N Fuse1 Fuse2 Fuse3 Fuse4 Fuse5 Fuse6 Fuse7 Fuse8 IN1 Fuse IN2 Fuse DM1 Dual Voltage Power Distribut...

Страница 6: ...6 Trove SALTO ULXB Kits Installation Guide Notes...

Страница 7: ...1 8mm 1 25 31 8mm 1 5 38 1mm 8 5 215 9mm 6 5 165 1mm 1 5 38 1mm 8 5 215 9mm 6 5 165 1mm 4 5 114 3mm 13 0 330 2mm 0 6 15 2mm 14 5 321 3mm 1 45 36 8mm 7 25 184 2mm 1 95 49 5mm 1 1 27 9mm 0 6 15 2mm 0 57...

Страница 8: ...35mm 5 25 133 35mm 6 25 158 8mm 1 25 31 8mm 0 85 21 6mm 0 5625 14 3mm 2 415 61 3mm 0 685 17 4mm 1 77 45mm 0 885 22 5mm 1 125 28 3mm Knockouts 2 00 50 8mm 2 00 50 8mm T2SAK78 and T2SAK7512 Enclosure D...

Отзывы: