- 2 -
T2M7XK1(D) Installation Guide
Overview:
Altronix Trove Plus kits are pre-wired, pre-assembled and consist of Trove2M2 enclosure/backplane with factory installed Altronix power supply/
charger and sub-assemblies, wire harnesses and finger duct.
Configuration Chart:
Altronix
Model
Number
120VAC 60Hz Input Current (A)
Power Supply Board Input Fuse Rating
Power Supply Board Battery Fuse Rating
Nominal DC Output Voltage
Maximum
Supply
Current for
Main and Aux.
Outputs on
Power Supply
board and
ACMS8(CB)
Access Power
Controller’s
outputs
Fail-Safe/Fail-Secure or Dry Form “C” Outputs
Current Per ACMS8(CB) and PDS8(CB) Output
(A)
ACMS8(CB) Board Input Fuse (PTC) Rating
ACMS8(CB) Board Output Fuse (PTC) Rating
PDS8(CB) Board Input Fuse (PTC) Rating
PDS8(CB) Board Output Fuse (PTC) Rating
Power Supply 1
Power Supply 2
[DC]
[Aux]
[DC]
[Aux]
Output
Range
(VDC)
Output
Range
(VDC)
Output
Range
(VDC)
Output
Range
(VDC)
T2M7XK1
4.5 6.3A/
250V
15A/
32V
20.17-
26.4
20.28-
26.4
20.17-
26.4
20.28-
26.4
24VDC @ 9.4A
8
2.5
15A/
250V
3A/
250V
10A/
250V
3A/
250V
T2M7XK1D
2.0
9A
2.5A
9A
2.5A
Hardware and Accessories:
• One(1) tamper switch (Altronix Model TS112 or equivalent).
• Cam lock.
• Battery leads.
Mechanical:
• 16 Gauge enclosure with ample knockouts for convenient access.
• Enclosure Dimensions (H x W x D): 27.25” x 21.75” x 6.5” (692.2mm x 552.5mm x 165.1mm).
Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, and with all local codes and authorities having jurisdiction.
Product is intended for indoor use only.
1. Remove backplane from enclosure. Do not discard hardware.
2. Mark and predrill holes in the wall to line up with the top three keyholes in the enclosure. Install three upper fasteners and screws in the
wall with the screw heads protruding. Place the enclosure’s upper keyholes over the three upper screws, level and secure. Mark the position
of the lower three holes. Remove the enclosure. Drill the lower holes and install the three fasteners. Place the enclosure’s upper keyholes
over the three upper screws. Install the three lower screws and make sure to tighten all screws.
3. Mount included UL Listed tamper switch (Altronix Model TS112 or equivalent) in desired location, opposite hinge. Slide the tamper switch
bracket onto the edge of the enclosure approximately 2” from the right side
(Fig. 1, pg. 2)
. Connect tamper switch wiring to the Access
Control Panel input or the appropriate UL Listed reporting device. To activate alarm signal open the door of the enclosure.
4. Refer to the
eFlow Power Supply/Charger Installation Guide
for eFlow104NB
and corresponding
Sub-Assembly Installation Guides
for PDS8(CB and ACMS8(CB) for
further installation instructions.
5. Position Mercury access controller modules over corresponding spacers and depress onto
snap on spacers
(Fig. 2, pg. 3)
.
6. Connect wire harnesses to Mercury access controller modules
(Fig. 2, pg. 3)
.
7. Mount backplane to enclosure with hardware.
Fig. 1
Tamper Switch
(provided)
To Access Control Panel or
UL Listed Reporting Device
Edge of
Enclosure
Enclosure