Tempo2 Installation Guide

Trigger Mode Programming:

1. Depress 

Advance

 00:00:00 

will appear in display.

   

Change 

?

2. Depress and Hold 

Confirm

 

00:00:00 

will appear in display.

  for 2 seconds until 

SetDelay

  Enter the desired amount of hours by depressing 

Advance

 to make the selection.

3. Depress 

Confirm

 

00:00:00 

will appear in display.

   

SetDelay

  Enter the desired amount of minutes by depressing 

Advance

 to make the selection.

4. Depress 

Confirm

 

00:00:00 

will appear in display.

   

SetDelay

  Enter the desired amount of seconds by depressing 

Advance

 to make the selection.

5. Depress 

Confirm

 

pulse = 1 

will appear in display.

   

Set 

PLS

 Depress 

Advance

 to select pulse duration (1-60 seconds). If pulse is not needed skip to step 6.

6. Depress 

Confirm

 

TRIG_OFF 

will appear in display.

   

TRG_EDGE

  Enter the desired trigger option (OFF, ON, CNG) by depressing 

Advance

 to make the selection.

  Removal of trigger will start time cycle.

  OFF option starts timing cycle when trigger is removed.

  ON option starts timing cycle when trigger is applied.

  CNG option starts timing cycle when trigger is removed or applied.

7.   Depress 

Confirm

 

RLY = ON 

will appear in display.

   

Event

  

  Enter the desired relay option (OFF, ON, PLS) by depressing 

Advance

 to make the selection.

  OFF option - relay turns off at the end of timing cycle.

  ON option - relay energizes at the end of timing cycle.

  Pulse option - relay energizes momentarily (1 to 60 sec).

 Depress 

Confirm 

to  accept .

Содержание Tempo2

Страница 1: ...er Rev 022807 More than just power TM Installing Company ________________ Service Rep Name ___________________________________ Address ______________________________________________ Phone ___________________ Installation Guide ...

Страница 2: ...C or DC operation Triggers via dry contact closure Output dry Form C contacts are 2A 120VAC 28VDC LCD display facilitates programming and indicates countdown status Current draw stand by 15mA relay energized 30mA Dual function test timer one shot EE Prom memory protects against loss of programming due to power failure Board dimensions L x W x H approximate 3 x 2 5 x 0 75 76 2mm x 63 5mm x 19 1mm O...

Страница 3: ...y Set min Enter the current minute of day by depressing Advance to make the selection 6 Depress Confirm SU 00 00 will appear in display TestMode 7 Depress Advance twice SU 00 00 will appear in display TestTime 8 Depress and Hold Confirm SU 00 00 will appear in display for two 2 seconds Test day Enter the desired day of the week by depressing Advance to make the selection MO SU or for every day tes...

Страница 4: ... display Set PLS Depress Advance to select pulse duration 1 60 seconds If pulse is not needed skip to step 6 6 Depress Confirm TRIG_OFF will appear in display TRG_EDGE Enter the desired trigger option OFF ON CNG by depressing Advance to make the selection Removal of trigger will start time cycle OFF option starts timing cycle when trigger is removed ON option starts timing cycle when trigger is ap...

Страница 5: ...VAC Dry Trigger IN1 Confirm Normally open door contacts CHIME Fig 2 Guard Tour Supervisory Timer Dry relay output Advance C NC NO POWER 12 24 VDC VAC Dry Trigger IN1 Confirm DIALER OR TRANSMITTER Normally open switch contacts For this application select Trigger CHG and Relay PULSE For this application select Trigger CHG and Relay OFF ...

Страница 6: ...l panel For this application select Trigger OFF Relay ON Fig 4 Delay Timer Use for Door Ajar Alarm Delayed Activation of Digital Dialer Defrost Cycle Timer etc Dry relay output Advance C NC NO POWER 12 24 VDC VAC Dry Trigger IN1 Confirm Normally open or normally closed switch contacts SOUNDER For Normally Closed Trigger Contact select Trigger OFF Relay ON For Normally Open Trigger Contact select T...

Страница 7: ...1 Confirm Normally open door contacts For this application select Trigger CHG Relay OFF For this application select Trigger CHG Relay OFF Dry relay output Advance C NC NO POWER 12 24 VDC VAC Dry Trigger IN1 Confirm Normally open or normally closed switch contacts Door Contacts Protective Circuit Fig 6 Timed Shunt for a Door Use to bypass alarm contacts ...

Страница 8: ...PULSE Dry relay output Advance C NC NO POWER 12 24 VDC VAC Dry Trigger IN1 Confirm DIALER OR TRANSMITTER Tempo2 Typical Applications cont d Fig 7 Delayed Egress Fig 8 Test Timer Altronix is not responsible for any typographical errors 140 58th Street Brooklyn New York 11220 USA phone 718 567 8181 fax 718 567 9056 website www altronix com e mail info altronix com Lifetime Warranty IITempo2 I22U MEM...

Отзывы: